Fireye SP-32-NG-ND-1.2 SureFire Pilot Igniter
$1,678.56
The Fireye SP-32-NG-ND-1.2 is a SureFire II natural draught gas pilot designed to ignite oil- and gas-fired main burners. It accommodates intermittent light-off or continuous pilot operation with a 1.2 m (3.93 ft) insertion length.
Description
- Natural Draught: Uses adjustable inlets to regulate combustion air.
- Gas Capacity: Delivers 17–34 kW at 20–80 kPa.
- Insertion Length: Supports 1.2 m (3.93 ft) pilot positioning within the burner.
- Flame Stabilization: Maintains a protected ignition zone for repeatable light-off.
- Temperature: Withstands 300°C and 500°C at specified tube ends/stabilizer.
Technical Specifications
| Manufacturer | Fireye |
|---|---|
| Part Number | SP-32-NG-ND-1.2 |
| Type | Pilot Igniter |
| Series | Surefire II |
| Fuel / Draft | Natural Gas, Natural Draught (ND) |
| Insertion Length | 1.2 m (3.93 ft) |
| Air Tube Diameter | 32 mm |
| Capacity | 17–34 kW at 20–80 kPa |
| Material | 304/316 Stainless Steel 310/330 Heat-Resistant Steel |
| Operating Temp | 300°C max continuous 500°C at orifice stabilizer and tube ends |
| Gas Connection | 1/2" BSP |
Request a Quote
"*" indicates required fields
Description
The Fireye SP-32-NG-ND-1.2 is a SureFire II natural draught gas pilot that initiates main burner ignition in power generation, refinery, and petrochemical applications. Its 1.2 m (3.93 ft) insertion length provides the specified installation reach, with a 32 mm outer-diameter air tube. The pilot delivers 17–34 kW at natural gas pressures of 20–80 kPa.
Inside the pilot, gas passes through main and bleed orifices, forming ignition and combustion zones around the stabilizer plate. A sliding sleeve adjusts combustion air intake to maintain the required flame position. The assembly uses a 1/2" BSP female gas inlet and accommodates separately ordered Fireye HESI or HTI ignition equipment with rods up to 16 mm OD.
Frequently Asked Questions
Where is the Fireye SP-32-NG-ND-1.2 typically used?
It serves oil- and gas-fired main burners in power generation, refinery, and petrochemical facilities, operating as an intermittent light-off or continuous gas pilot.
How does the Fireye SP-32-NG-ND-1.2 establish its pilot flame?
Gas flows through main and bleed orifices, while a stabilizer plate helps establish the flame. An adjustable sleeve controls combustion air entering the pilot.
What mounting arrangements are available for this pilot?
The air tube can be welded directly to the burner plate or installed using an optional flanged or weld-on mounting tube, ordered separately.