Fireye to Honeywell Flame Sensor Cross Reference Guide
Transitioning from Fireye to Honeywell flame sensors can be driven by the need to replace obsolete models, ensure compatibility with modern systems, or meet specific operational requirements. This process can seem challenging due to differences in specifications or limited cross-reference information. This Cross Reference Guide is designed to assist engineers and technicians by providing detailed tables mapping Fireye flame sensors to their Honeywell equivalents. At TCI Supply, we aim to simplify your upgrade with our extensive inventory and expert support, ensuring a seamless transition to your new flame detection system.
Important Note on System Compatibility: The Fireye and Honeywell flame sensors in this guide are not direct, interchangeable replacements. This guide serves as a reference for planning and executing a complete system transition. Always consult with a qualified engineer or contact TCI Supply to verify compatibility.
Quick Menu
Infrared Flame Detectors
The following table maps Fireye infrared flame detectors to Honeywell equivalents, including specifications for mounting, lead length, and additional features.
Fireye Infrared to Honeywell C7915A Series
|
Fireye Model |
Honeywell Replacement |
Mounting Pipe Size NPT (in.) |
Lead Length (in.) |
Orifice |
Collimating LensWAN |
With Cell |
Comments |
|---|---|---|---|---|---|---|---|
|
48PT11000 |
C7915A1028 (1) |
1/2 in. |
24 in. |
No |
No |
Yes |
With heat block, straight body. |
|
C7915A1028 (2) |
1/2 in. |
96 in. |
No |
No |
Yes |
With heat block, straight body. |
|
|
48PT11007 |
C7915A1028 (1) |
1/2 in. |
48 in. |
No |
No |
Yes |
With heat block, straight body. |
|
48PT19000 |
C7915A1028 (3) |
1/2 in. |
24 in. |
No |
No |
Yes |
With heat block, angle body. |
|
C7915A1028 (4) |
1/2 in. |
96 in. |
No |
No |
Yes |
With heat block, angle body. |
|
|
C7915A1028 (3) |
1/2 in. |
48 in. |
No |
No |
Yes |
With heat block, angle body. |
|
|
48PT21000 |
C7915A1028 (1) |
1/2 in. |
24 in. |
No |
No |
Yes |
With heat block, straight body. |
|
C7915A1028 (2) |
1/2 in. |
96 in. |
No |
No |
Yes |
With heat block, straight body. |
|
|
C7915A1028 (1) |
1/2 in. |
48 in. |
No |
No |
Yes |
With heat block, straight body. |
|
|
48PT29000 |
C7915A1028 (3) |
1/2 in. |
24 in. |
No |
No |
Yes |
With heat block, angle body. |
|
C7915A1028 (4) |
1/2 in. |
96 in. |
No |
No |
Yes |
With heat block, angle body. |
|
|
C7915A1028 (3) |
1/2 in. |
48 in. |
No |
No |
Yes |
With heat block, angle body. |
Footnotes for Infrared Flame Detectors:
(1) Perform pilot turndown test after installation.
(2) For 96-inch leadwires, use C7915A1036 instead.
(3) Straight-body replacement for angle-body models; check alignment.
(4) For 96-inch leadwires on angle-body models, use C7915A1036.
Visible Light Flame Detectors
The following table maps Fireye visible light flame detectors to Honeywell equivalents, noting that direct replacements may require system upgrades.
Fireye Visible Light to Honeywell 7800 Series
|
Fireye Model |
Honeywell Replacement |
With Housing |
With Lens |
With Filter |
Comments |
|---|---|---|---|---|---|
|
45AM11000 |
See footnote (1) |
Yes |
No |
No |
– |
|
See footnote (1) |
Yes |
No |
No |
– |
|
|
45CM11000Y |
See footnote (1) |
No |
No |
No |
– |
Footnotes for Visible Light Flame Detectors:
(1) No direct replacement; upgrade to 7800 Series with R7852B amplifier and C7962B detector.
Ultraviolet Flame Detectors
The following tables map Fireye ultraviolet flame detectors to Honeywell equivalents, including specifications for mounting, lead length, and electrical requirements.
Fireye Ultraviolet to Honeywell C7027A Series
|
Fireye Model |
Honeywell Replacement |
Mounting Pipe Size NPT (in.) |
Lead Length (ft./in.) |
Ambient Temp (°F) |
Comments |
|---|---|---|---|---|---|
|
UV-1 |
C7027A1080 (1) |
1/2 in. |
6/72 |
-40 to 212 |
Angle body. |
|
UV-1A3 |
C7027A1080 (1) |
1/2 in. |
3/36 |
-40 to 212 |
Straight body. |
|
UV-1A6 |
C7027A1080 (1) |
1/2 in. |
6/72 |
-40 to 212 |
Straight body. |
|
UV-2 |
C7027A1080 (2) |
3/8 in. |
3/36 |
-40 to 212 |
Straight body. |
|
UV-6 |
C7027A1080 (1) |
1/2 in. |
6/72 |
-40 to 212 |
Angle body. |
|
UV-7 |
C7027A1080 (2) |
3/8 in. |
6/72 |
-40 to 212 |
Angle body. |
|
45UV21010 |
C7027A1080 (3) |
3/4 in. |
None |
-40 to 200 |
Angle body. |
|
45UV21112 |
C7027A1080 (3) |
3/4 in. |
None |
-40 to 200 |
Angle body. |
|
45UV21113 |
C7027A1080 (3) |
3/4 in. |
None |
-40 to 200 |
Angle body. |
|
C7027A1080 (3) |
3/4 in. |
None |
212 max. |
Angle body. |
Footnotes for Ultraviolet Flame Detectors (C7027A Series):
(1) For applications below 0°F, use C7027A1031.
(2) Use a 1/2 x 3/8 reducer coupling for mounting.
(3) Use a 3/4 x 1/2 reducer coupling for mounting.
Fireye Ultraviolet to Honeywell C7012/C7076 Series
|
Fireye Model |
Honeywell Replacement |
Voltage/Frequency (HZ) |
Mounting Pipe Size NPT (in.) |
Lead Length (ft./in.) |
Ambient Temp (°F) |
Solid State |
Comments |
|---|---|---|---|---|---|---|---|
|
C7012A1152 (1) |
120/50,60 |
1 in. |
None |
200 max. |
N/A |
– |
|
|
45UV11021 |
C7012A1152 (1) |
120/50,60 |
1 in. |
None |
200 max. |
N/A |
– |
|
C7012E1112 (1) |
120/50,60 |
1 in. |
None |
200 max. |
Yes |
– |
|
|
C7012E1112 (2) |
120/50,60 |
1 in. |
8/96 |
200 max. |
Yes |
– |
|
|
45RM11000 |
C7076A1007 (3) |
120/50,60 |
1 in. |
None |
32 to 131 |
Yes |
Adjustable sensitivity. |
Footnotes for Ultraviolet Flame Detectors (C7012/C7076 Series):
(1) Max temperature is 175°F; verify system range.
(2) Includes 96-inch leadwires; adjust if needed.
(3) Operates at 32°F to 131°F; ensure compatibility.