Yaskawa CIMR-ZU4A0414AAA Z1000 AC VFD 350HP 480V

CIMR-ZU4A0414AAA

The Yaskawa CIMR-ZU4A0414AAA (Z1000 Series) is a high-power 350 HP, 480 VAC 3-phase variable frequency drive (VFD) specifically engineered for commercial building automation, HVAC fan and pump control, and cooling tower applications. Rated for 414 Amps of continuous output current, this energy-efficient AC drive combines advanced motor vector control with integrated building automation system (BAS) communication protocols, a full-text LCD operator keypad with Hand-Off-Auto (HOA) functionality, and an integrated DC reactor for harmonic mitigation in high-capacity facility installations.

Technical Details

  • Model / Part Number: CIMR-ZU4A0414AAA (Z1000 HVAC Series)
  • Manufacturer: Yaskawa Electric
  • Device Type: Variable Frequency Drive (VFD) / AC Inverter
  • Horsepower Rating: 350 HP (Variable Torque / Normal Duty @ 110% Overload for 60 sec)
  • Input Voltage & Phase: 380 to 480 VAC (+10%/-15%) | 3-Phase | 50/60 Hz
  • Output Voltage & Current: 0 to 480 VAC 3-Phase | 414 Amps Rated Continuous Output
  • Output Frequency Range: 0.01 to 240 Hz (0.01 to 400 Hz adjustable)
  • Enclosure Rating: IP00 / Protected Chassis (UL Open Type)
  • Embedded BAS Communications: BACnet MS/TP, Modbus RTU, Metasys N2
  • Operator Keypad: 5-line 16-character Alpha-Numeric LCD with Real-Time Clock & Hand-Off-Auto (HOA) switches
  • Harmonic Mitigation: Integrated DC Link Reactor / Choke (Standard)
  • Dimensions & Weight: 44.9 in H x 26.4 in W x 14.6 in D | ~124.7 lbs (56.6 kg)
  • Standards & Approvals: UL Listed, CSA, CE, Plenum Rated (UL 1995), IBC 2006 Seismic Certified, RoHS Compliant

Key Features

  • Dedicated Z1000 HVAC drive architecture designed to optimize energy efficiency across large-scale facility air and fluid handling systems.
  • Integrated Hand-Off-Auto (HOA) multi-language LCD keypad features an intuitive interface and real-time clock for scheduled operation and troubleshooting.
  • Embedded building automation protocols (BACnet, Modbus, Metasys) enable seamless direct integration into building management networks without option cards.
  • Independent dual PI controllers allow closed-loop feedback management for temperature, flow, and pressure regulation without external controllers.
  • Internal DC link reactor mitigates line harmonics and protects internal drive electronics from utility line transients.

Applications

  • Large-scale commercial facility HVAC air handling units (AHUs), supply and return fans, and industrial exhaust blowers.
  • Chilled water circulation pumps, condenser water pumps, booster pumps, and municipal water management systems.
  • Cooling tower variable-speed fan control, central boiler loops, and hydronic heating systems.
  • Plenum and mechanical room energy-management retrofits requiring high-horsepower 480V VFD control.

We ship this product worldwide! Delivery is normally stock.