Honeywell RM7897C1018 Burner Control

Honeywell RM7897C1018 Relay Module

The Honeywell RM7897C1018 is a microprocessor-based primary burner control module engineered for automatically fired gas, oil, or combination fuel single-burner applications. As part of Honeywell’s 7800 Series, the RM7897C provides automatic burner sequencing, flame supervision, post-purge, and safety shutoff function for commercial and industrial combustion systems.

Technical Details

  • Model / Part Number: RM7897C1018
  • Manufacturer / Brand: Honeywell
  • Product Line: 7800 Series Flame Safeguard Controls
  • Module Type: Primary Burner Control / Relay Module
  • Supply Voltage: 120 VAC (+10% / -15%), 50/60 Hz
  • Power Consumption: 10 W Maximum
  • Pre-Purge Period: Configurable via ST7800 Plug-In Purge Timer Card
  • Post-Purge Period: Programmable 15-second Post-Purge
  • Flame Amplifier: Requires Plug-In R7800 Series Flame Signal Amplifier
  • Mounting Base: Q7800A, B, or C Wiring Subbase
  • Operating Temperature: -40°C to 60°C (-40°F to 140°F)
  • Storage Temperature: -40°C to 65°C (-40°F to 150°F)
  • Relative Humidity: 0% to 85% Non-Condensing
  • Approvals / Standards: UL Listed, CSA Certified, FM Approved
  • Shipping Weight & Dimensions: 2.0 lbs | 7 x 5 x 3 Inches
  • Alternate Part Numbers: RM7897C1018, RM7897C1018/U, 7800 RM7897C1018

Key Features

  • Microprocessor Safety Logic: Manages pre-purge, ignition, pilot/main flame trial, and post-purge timing with continuous self-diagnostics.
  • Programmable Post-Purge: Features an integrated post-purge cycle to safely clear unburned combustion gases from the furnace after burner shutdown.
  • Status Diagnostic LEDs: Front-panel LEDs provide real-time visual feedback for operational phases (Power, Fault, Purge, Flame, Pilot, Main).
  • Modular Component Architecture: Integrates with ST7800 purge timer cards, R7800 flame amplifiers, and S7800 keyboard display modules.
  • Non-Volatile Memory: Retains lockout status, fault codes, and operational cycle statistics through power loss.

Applications

  • Primary flame safeguard control for commercial boilers, industrial process heaters, and warm air furnaces.
  • Gas, oil, or dual-fuel single-burner management installations requiring post-purge capabilities.
  • Direct replacement and maintenance servicing for Honeywell 7800 Series burner control units.

We ship this product worldwide! Delivery is normally stock.

Request a Quote now on Honeywell RM7897C1018 or call us at 1-800-755-2883 for expert assistance.

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!