Siemens 6EP1933-2EC41 Uninterruptible Power Supply

$618.00

The Siemens 6EP1933-2EC41 is a maintenance-free, capacitor-based uninterruptible power supply for 24V DC industrial control systems. With 2.5 kWs of stored energy, it sustains a 15A load for up to 3 seconds during a power interruption, keeping critical processes running through brief outages.

SKU: 6EP1933-2EC41 Category: Brand:

Description

  • Capacitor Storage: Delivers maintenance-free buffering, no battery replacement.
  • 24V DC In/Out: Designed for 24V DC circuits, input range 22–29V.
  • 15A Output: Rated 15A continuous in normal and buffering modes.
  • 2.5 kWs Storage: Buffers 15A for 3 s, or 2A for up to 38 s.
  • Scalable Buffering: Supports extended runtime via UPS501S expansion module.

Technical Specifications

Manufacturer Siemens
Part Number 6EP1933-2EC41
Type Power Module
Series SITOP
Application Power Backup
Size / Rating 24V DC
Output Current 15A rated
Energy Storage 2.5 kWs, capacitor-based
Connection Type Terminals
Compatibility SITOP PSU8200

Request a Quote

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Description

The Siemens 6EP1933-2EC41 is a maintenance-free DC UPS module in the SITOP UPS500S series, designed to bridge 24V DC control circuits through power interruptions. It accepts 22–29V DC input, delivers a stable 24V DC output at up to 15A, and holds an adjustable buffer threshold factory-set at 22.5V.

Capacitor-based storage eliminates battery cycles, supplying 2.5 kWs of energy — enough to sustain 15A for 3 seconds or 2A for 38 seconds. It snaps onto a 35mm DIN rail, terminates via screw connections, and reports system status through onboard LEDs, floating relay contacts, and a USB interface. Rated IP20 for panel installation.

Frequently Asked Questions

What buffer duration does the 6EP1933-2EC41 provide at full 15A load?

At 15A, the unit buffers for 3 seconds. Lower loads extend runtime: 10A for 6 s, 5A for 15 s, or 2A for 38 s.

Can the buffer time be extended beyond what the base unit provides?

Yes. The SITOP UPS501S expansion module connects to the 6EP1933-2EC41 to increase available buffering capacity.

Does the 6EP1933-2EC41 require battery replacement or scheduled maintenance?

No. Capacitor-based energy storage eliminates batteries, so no scheduled replacement or maintenance cycles are required.