Siemens 6EP1933-2EC41 Uninterruptible Power Supply
$618.00
The Siemens 6EP1933-2EC41 is a maintenance-free, capacitor-based uninterruptible power supply for 24V DC industrial control systems. With 2.5 kWs of stored energy, it sustains a 15A load for up to 3 seconds during a power interruption, keeping critical processes running through brief outages.
Description
- Capacitor Storage: Delivers maintenance-free buffering, no battery replacement.
- 24V DC In/Out: Designed for 24V DC circuits, input range 22–29V.
- 15A Output: Rated 15A continuous in normal and buffering modes.
- 2.5 kWs Storage: Buffers 15A for 3 s, or 2A for up to 38 s.
- Scalable Buffering: Supports extended runtime via UPS501S expansion module.
Documentation
Technical Specifications
| Manufacturer | Siemens |
|---|---|
| Part Number | 6EP1933-2EC41 |
| Type | Power Module |
| Series | SITOP |
| Application | Power Backup |
| Size / Rating | 24V DC |
| Output Current | 15A rated |
| Energy Storage | 2.5 kWs, capacitor-based |
| Connection Type | Terminals |
| Compatibility | SITOP PSU8200 |
Request a Quote
"*" indicates required fields
Description
The Siemens 6EP1933-2EC41 is a maintenance-free DC UPS module in the SITOP UPS500S series, designed to bridge 24V DC control circuits through power interruptions. It accepts 22–29V DC input, delivers a stable 24V DC output at up to 15A, and holds an adjustable buffer threshold factory-set at 22.5V.
Capacitor-based storage eliminates battery cycles, supplying 2.5 kWs of energy — enough to sustain 15A for 3 seconds or 2A for 38 seconds. It snaps onto a 35mm DIN rail, terminates via screw connections, and reports system status through onboard LEDs, floating relay contacts, and a USB interface. Rated IP20 for panel installation.
Frequently Asked Questions
What buffer duration does the 6EP1933-2EC41 provide at full 15A load?
At 15A, the unit buffers for 3 seconds. Lower loads extend runtime: 10A for 6 s, 5A for 15 s, or 2A for 38 s.
Can the buffer time be extended beyond what the base unit provides?
Yes. The SITOP UPS501S expansion module connects to the 6EP1933-2EC41 to increase available buffering capacity.
Does the 6EP1933-2EC41 require battery replacement or scheduled maintenance?
No. Capacitor-based energy storage eliminates batteries, so no scheduled replacement or maintenance cycles are required.