Siemens 3RT2015-1KB41 Power Contactor

$64.00

The Siemens 3RT2015-1KB41 contactor is a Size S00 3-pole device from the SIRIUS coupling-contactor line, built with a 24V DC coil and integrated suppressor diode. It switches loads up to 3 kW at 400 V AC-3 directly from PLC outputs.

3 in stock

SKU: 3RT2015-1KB41 Category: Brand:

Description

  • PLC-Compatible Coil: Accepts 24V DC PLC output signals directly.
  • Integrated Suppressor Diode: Protects PLC outputs from inductive transients.
  • Size S00 Frame: Saves panel space at 45 mm width.
  • Three Main Poles: Switches three-phase loads to 3 kW.
  • Long Mechanical Life: Delivers 30 million switching cycles typically.

Technical Specifications

Manufacturer Siemens
Part Number 3RT2015-1KB41
Type IEC Contactor
Application Motor Control, Power Switching
Series SIRIUS 3RT2
Compatibility SIRIUS Overload Relays
Operating Current/Power 18A at 400V AC-1
7A / 3kW at 400V AC-3
1.15kW at 400V AC-4
Coil Voltage 24V DC
Connection Type Screw Terminals

Request a Quote

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Description

The Siemens 3RT2015-1KB41 is a 3-pole contactor from the SIRIUS 3RT2 family, classified by Siemens as a coupling contactor because it is built to interface PLC outputs directly with three-phase loads in industrial automation panels. The 24V DC coil with a wide 0.7…1.25*Us operating range accepts standard PLC output signals without an intermediate interface relay, simplifying the wiring path between controller and load. The Size S00 frame fits PLC-driven motor and resistive circuits up to 3 kW at 400 V AC-3.

An integrated suppressor diode across the coil protects PLC output stages from inductive switching transients, removing the need to add a separate diode externally. The contactor uses three NO main contacts plus one NO auxiliary, with screw-type terminals on both circuits that accept conductors down to 0.5 mm². A typical mechanical life of 30 million switching cycles supports the high cycle counts typical of PLC-driven control where the contactor may pulse continuously over a shift.

Frequently Asked Questions

Can I drive this contactor directly from a PLC output?

Yes. The 24V DC coil with 0.7–1.25*Us range and integrated suppressor diode is specifically designed for direct connection to standard PLC outputs.

What loads can the 3RT2015-1KB41 switch?

It handles up to 3 kW at 400 V under AC-3 (motor) duty and 18 A under AC-1 (resistive) duty, plus three-phase motors to 3 hp at 480 V.

Does this contactor need an external flyback diode?

No. A suppressor diode is integrated across the 24V DC coil, protecting the driving PLC output from inductive kickback without additional components.