Fireye M4RT1 Integrated Control

$701.38

The Fireye M4RT1 is a flame safeguard control for automatic ignition and continuous flame monitoring on commercial heating and process gas burners. With a safety-checking circuit active at each start, it prevents fuel-valve energization when flame is detected before startup or during purge.

Contact us for lead times on M4RT1

SKU: M4RT1 Category: Brand:

Description

  • Flame Monitoring: Uses flame rod detection continuously.
  • Startup Safety: Prevents fuel-valve energization without a prestart flame.
  • Timing Control: Supports configurable purge and PTFI timing.
  • Failure Response: Provides a fixed three-second flame failure response.
  • Status Indicators: Provides five LEDs for operating status.

Technical Specifications

Manufacturer Fireye
Part Number M4RT1
Type Integrated Control
Supply 120V (102–132V), 60Hz
Flame Detection Flame Rod
Timings FFRT: 3 seconds
PTI: 5 or 10 seconds
Purge: Jumper-Selectable
Operating Temp -40°F to 125°F (-40°C to 52°C)

Request a Quote

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Description

The Fireye M4RT1 is a flame safeguard control for commercial heating and process gas burners, providing automatic ignition and continuous flame monitoring. It uses a flame rod detector with a built-in amplifier and programmer to supervise burner operation, with safety shutdown and lockout functions responding to ignition or flame failures.

Five LED indicators display operating control, airflow, pilot trial for ignition, flame, and alarm status for clear sequence monitoring. Onboard jumpers configure purge timing, PTFI timing, and recycle or non-recycle operation, while a fixed three-second flame failure response time and test jacks support flame-safeguard operation and signal checking.

Frequently Asked Questions

What applications is the Fireye M4RT1 designed for?

It provides automatic ignition and continuous flame monitoring for commercial heating and process burners using gaseous fuels.

How does the Fireye M4RT1 detect flame?

The M4RT1 uses a flame rod detector with a built-in amplifier and programmer for continuous flame monitoring.

How is the Fireye M4RT1 reset after lockout?

A minimum one-second power interruption to terminal 7 resets the standard control; pushbutton and remote reset are special-order options.