Fireye EP160 Programmer Module

$1,452.00

The Fireye EP160 is a plug-in programmer module for the FLAME-MONITOR Burner Management System on E100 and E110 controls, managing the burner sequence from prepurge to flame supervision. It features six DIP switches for setting purge timing and interlock proving.

Out of stock

SKU: EP160 Category: Brand:

Description

  • Flame Supervision: Monitors flame and shuts off fuel within 4 seconds.
  • Adjustable Purge: Sets pre-purge timing to 30 seconds.
  • Interlock Proving: Confirms safety limit switches before each stage.
  • History Storage: Logs burner cycles, hours, and lockouts.
  • Modbus Communication: Links to E500 interface for remote monitoring.

Technical Specifications

Manufacturer Fireye
Part Number EP160
Type Programmer Module
Compatibility Fireye E100, E110 control modules
Operation Type Non-recycling
Timing Pre Purge: 30 sec (adjustable)
PTFI: 10 sec
MTFI: 10 sec (T5), 15 sec (T6)
FFRT: 4 sec (max)
Post Purge: 15 sec
Communications Modbus, E500 (2× RJ12)
Running Interlock Non-recycle (3/P)
Agency Approval cUL US Listed, FM Approved

Request a Quote

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Description

The Fireye EP160 is a plug-in programmer module for the FLAME-MONITOR system that runs start-up programming, safe-start check, and flame supervision. It sequences open-damper high purge, proof of low fire, and fuel valve end switch checks to confirm each burner stage before the next begins. A monitored running interlock circuit forces a safety lockout when any limit opens at the wrong point.

Micro-processor electronics store burner cycles, hours, and time-stamped lockout history for clear diagnostics after a fault. An RJ45 connector drives the ED510 display for local status readout, while two RJ12 connectors tie into an E500 interface or Modbus network for multi-drop monitoring. A genuine Fireye part that restores the control to original specifications.

Frequently Asked Questions

What system is the Fireye EP160 used with?

The Fireye EP160 is used with the FLAME-MONITOR Burner Management Control System, part numbers E100 and E110, installed in the EB700 or E110 chassis programmer slot.

What is the flame failure response time of the Fireye EP160?

The Fireye EP160 has a flame failure response time of 4 seconds, de-energizing all fuel valve circuits within that period following a loss of flame signal.

Which display module connects to the Fireye EP160?

The Fireye EP160 uses an RJ45 connector for the ED510 alpha-numeric display and is backward compatible with the ED500 display.