Fireye 95DSS2-1 Dual Flame Scanner UV/IR

$6,850.00

The Fireye 95DSS2-1 is a dual-spectrum UV/IR flame scanner using microprocessor technology for reliable flame detection and background rejection in industrial burner systems. Ideal for harsh combustion environments.

Contact Us to Guarantee Best Pricing

SKU: 95DSS2-1 Category: Brand:

Description

  • Dual Sensor Detection: Combines infrared and ultraviolet sensing.
  • Integrated Flame Relay: Eliminates the remote flame amplifier.
  • Adjustable Relay Thresholds: Sets ON 5-100, OFF 0-95.
  • Expanded Model Capability: Includes AutoTune and remote communications.
  • Hazardous Area Rating: Carries NEMA 4X, IP66, Class I Div. 2.

Technical Specifications

Manufacturer Fireye
Part Number 95DSS2-1
Type Flame Scanner
Series / Model InSight, S2 (Expanded Features)
Sensor Type Dual (IR and UV)
Input Power 24 Vdc, +10% / -15%
0.35A, 8.5VA
Electrical Connection 12-pin quarter-turn quick-disconnect
Relay Output Flame relay, SPST (N.O.)
Fault relay, SPST (N.C.)
Contact Rating 240 Vac (Max)
Enclosure Rating NEMA 4X, IP66
Class I Div. 2, Groups A, B, C & D
Class II Div. 2, Groups F & G
Analog Output 4-20 mA dc,
750 ohm maximum load
Agency Approvals UL C/US, FM
Weight 11 lbs

Request a Quote

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Description

The Fireye 95DSS2-1 detects flame using infrared and ultraviolet sensors working together, a pairing suited to multi-fuel applications. Its integrated flame relay carries ON thresholds adjustable from 5 to 100 and OFF thresholds from 0 to 95, delivering a switched contact to the burner management system without a separate amplifier.

A cast aluminum housing with gray polyester powder coat finish mates to a 1" NPT or 1" BSP sight pipe connection and terminates in a 12-pin quarter-turn quick-disconnect. Power comes from a 24 Vdc supply drawing 0.35A, and an eight-character alphanumeric LED display with four pushbutton keys handles setpoint entry.

Frequently Asked Questions

What fuels is the 95DSS2-1 suited to?

Its paired infrared and ultraviolet sensors make it best suited to multi-fuel applications.

Does this scanner require a separate flame amplifier?

No. The internal flame relay carries adjustable ON and OFF thresholds and performs the switching, eliminating the remote flame amplifier.

What power and connection does the 95DSS2-1 need?

It runs on 24 Vdc at 0.35A, 8.5VA, wired through the 12-pin quarter-turn quick-disconnect.