Fireye EP160 ProgrammerThe Fireye EP174 is a non-recycle programmer module with selectable purge timing, 5- and 10-second TFI, and early spark termination. This unit uses a required M-D circuit proof through MTFI to ensure controlled sequencing.

Technical Specifications

  • Manufacturer: Fireye
  • Part Number: EP174
  • Product Type: Programmer Module
  • Series: Flame-Monitor
  • Purge Time: Selectable, 30-second minimum
  • TFI Duration: 5 or 10 seconds
  • Operation Mode: Non-recycle
  • Spark Function: Early spark termination
  • M-D Circuit: Must be proven through completion of MTFI

Key Features and Functionality

  • Selectable Purge: Establishes required prepurge duration.
  • Early Termination: Limits spark output during ignition.
  • TFI Options: Provides 5–10 second ignition timing selection.
  • Interlock Proof: Requires M-D circuit verification through MTFI.
  • Non-Recycle Logic: Supports controlled shutdown after faults.

Compatible Components and Related Parts

  • Fireye EP160, EP161, EP163, EP165, EP166, EP174 & EP177 Programmer Modules
  • Fireye ED510 & ED500 Display Modules
  • Fireye E500 Communication Interface
  • Fireye ED550 Cables

Compliance and Approvals

  • UL Listed & FM Approved

Installation and Operational Notes

  • Set dip switches to the desired purge and interlock settings.
  • Verify the 3-P running interlock before starting the cycle.
  • Use correct cabling for the ED510 or ED500 display.
  • Ensure proper communication wiring for E500/Modbus.
  • Confirm all limits and airflow switches are satisfied before operation.

Series Information

Fireye EP-1601 EP Programmer Modules

 

We ship this product worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!