TCI Supply is a master distributor for Honeywell Flame Safety Controls including product, flame amplifiers, scanners (UV and IR), modutrol motors, gas valves and actuators, and burner boiler controls. We started our business over 30 years ago based on this product line. Nobody will beat our price on new relay modules, and nobody will top our quality of repairs. We have a quick turnaround time and get them back to you in pristine condition.
Cross Reference Guide (PDF)
We ship all products worldwide! Delivery is normally stock.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
BARBER COLMAN | |||
MA-12313 | M8415A1004 | 90 sec, 1 aux switch | |
MA-12323 | M8415A1004 | ||
MA-305 | M836A1042 | 75° stroke, 30 sec, 32-125°F | |
MA-305-500 | M836A1042 | ||
MA-318 | M8185D1006 | M8185A1002 | 160° stroke, 60 sec |
MA-318-500 | M8185D1006 | ||
MA-405 | M436A1116 | 75° stroke, 30 sec, 32-125°F | |
MA-405-500 | M436A1116 | ||
MA-406 | M836A1042 | Requires 208 Vac transformer | |
MA-406-500 | M836A1042 | ||
MA-407 | M436A1124 | 75° stroke, 30 sec, 32-125°F | |
MA-407-500 | M436A1124 | ||
MA-416 | M8185D1006 | M4185B1017 | 160° stroke, 60 sec |
MA-416-500 | M8185D1006 | M4185B1017 | M8185D: 60 sec |
MA-418 | M8185D1006 | M4185A1001 | |
MA-418-500 | M8185D1006 | M4185B1009 | |
MA-419 | M8185D1006 | M4185B1017 | 160° stroke, 60 sec |
MA-419-500 | M8185D1006 | M4185B1017 | TRADELINE is 60 sec |
MA-5330 | MA-5330: Damper DCA | ||
MA-5333 | MA-5333: Damper DCA | ||
MA5-419 | M8185D1006 | M4185B1017 | MA5 includes special enclosure |
MA5-419-500 | M8185D1006 | M4185B1017 | TRADELINE is 240 sec |
MC-351 | M6194D1017 | Original: unidirectional operation | |
TRADELINE is 240 sec | |||
MC-421 | M6184D1035 | Original: unidirectional operation | |
TRADELINE is 60 sec | |||
MC-431 | M6194D1017 | Original: unidirectional operation | |
MC-4311 | M6194D1017 | TRADELINE is 240 sec | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
MC5-4311 | M6194D1017 | Original: unidirectional operationTRADELINE is 240 sec; ES-650 is explosion proof housing (see Accessories) | |
MC-9610 | Original: unidirectional operation | ||
MC-9810 | |||
ME-12313 | M8405A1006 | Original: economizer | |
ME-12313-102 | M8405A1006 | ||
MP-2110 | |||
MP-2113-500 | M6184D1035 | M6184D1001 + Q607A | 75 lb-in, 60 sec |
MP-2130-500 | M6184D1035 | M6184D1001 + Q607A | TRADELINE is 60 sec, 150 lb-in |
MP-2150-500 | M6184D1035 | M6184A1023 + Q607A | |
MP-2151-500 | M6184D1035 | TRADELINE is 60 sec, 150 lb-in | |
MP-371 | M6294D1008 | TRADELINE is 160°, 240 sec | |
MP-381 | M6194D1017 | Replacement is 160°, 240 sec | |
TRADELINE is 160°, 240 sec | |||
MP-481 | M9194D1003 | Set signal range | |
MP-483-600 | M6294D1008 | M6294D1008 | Check timing and stroke |
MP-485 | M6194D1017 | ||
MP-4851 | M6294D1008 | ||
MP-486 | M6294D1008 | ||
MP-9710 | |||
MU-12313 | M7415A1006 | ||
PENN JOHNSON | |||
M110AAB-1 | M8185D1006 | ||
M110AGA-1 | M8185D1006 | ||
M110AGB-1 | M8185D1006 | ||
M110GGA-1 | M9175D1014 | ||
M110JGA-1 | M9185D1004 | M9175D1014 | Replacement is 90°-160° stroke |
M110JGB-1 | M9175D1014 | M9175D1014 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M110QGA-1 | |||
M120AAA-1 | M6184D1035 | ||
M120AAB-1 | M8185D1006 | ||
M120AAC-1 | M6184D1035 | ||
M120AGA-1 | M6184D1035 | ||
M120GGA-1 | M9164D1009 | Select signal range | |
M120JAA-1 | M9164D1009 | M9164D1009 | Replacement is 90°-160° stroke |
M120JAC-1 | M9164D1009 | M9164C1050 | |
M120JGA-1 | M9164D1009 | M9164A1021 | M9164A1021: wire to 24 Vac |
M120QGA-1 | |||
M130AGA-1 | M8185D1006 | Replacement is 90°-160° stroke | |
M130AGB-1 | M8185D1006 | ||
M130GGA-1 | M9185D1004 | M7285Q1016 | Replacement is 90°-160° stroke |
M130JGA-1 | M9185D1004 | M9185A1018 | |
M130JGB-1 | M9185D1004 | M9185E1019 | Replacement is 90°-160° stroke |
M130QGA-1 | |||
M140AAA-1 | M6184D1035 | ||
M140AGA-1 | M6184D1035 | ||
M140GGA-1 | M9174D1007 | Select signal range | |
M140JAA-1 | M9174D1007 | M9174D1007 | Replacement is 90°-160° stroke |
M140JGA-1 | M9174D1007 | M9174D1007 | |
M150AGA-1 | M6184D1035 | M6184D1035 | |
M150AGB-1 | M6184D1035 | M6184F1017 | |
M150GGA-1 | M9184D1013 | Select signal range | |
M150JGA-1 | M9184D1013 | M9184A1019 | |
M150JGB-1 | M9184D1013 | M9184F1000 | Replacement is 90°-160° stroke |
M150JGC-1 | M9184D1013 | M9184F1000 | |
M150QGA-1 | M7284Q1017 | ||
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M40AAA-1 | M9164D1009 | M9164A1005 | |
M40AAC-1 | M9164D1009 | M9164C1068 | |
M40AGA-1 | M6184D1035 | M6184A1015 | |
M40AGC-1 | M9164D1009 | ||
M80AAA-3 | M6284D1000 | M6284F1013 | Check voltage & stroke of motor |
M80AAB-1 | M6284D1000 | M6284F1013 | |
M80ACA-1 | M6285A1005 | M6285A1005 | Check voltage & stroke of motor |
M80ADA-1 | M6285A1005 | M6285A1005 | |
M80BAA-1 | M9184D1021 | M9184A1019 | |
M80BAA-4 | M9184D1005 | ||
M80BCA-1 | M9185D1004 | M9185D1004 | |
M80BDA-1 | M9185D1004 | M9185D1004 | |
M80BEA-1 | M9185D1004 | M9186G1006 | N.O.; Check motor voltage & stroke |
M80FAA-2 | M9184D1021 | M9184A1019 | Check voltage & stroke of motor |
M80FCA-2 | M9185D1004 | M9185D1004 | |
M80FDA-1 | M9185D1004 | M9185D1004 | |
M80FEA-1 | M9185D1004 | M9186G1006 | N.O.; Check motor voltage & stroke |
M80FFA-1 | M9185D1004 | M9185A1018 | Check voltage & stroke of motor |
M80HAB-1 | M9184D1021 | M9184F1034 | |
M80HAC-1 | M9184D1021 | M9184F1034 | |
M80JAA–2 | M9184D1021 | M9184A1019 | Replacement is 90°-160° stroke |
M80JAB–1 | M9184D1021 | M9184F1034 | |
M80JAC–1 | M9484E1017 | ||
M80JCA–2 | M9185D1004 | M9185A1018 | |
M80JCB–1 | M9185D1004 | M9185E1019 | |
M80JDA-1 | |||
M80JFA-1 | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M81AAA–12 | M6184D1035 | M6184F1014 | Replacement is 90°-160° stroke |
M81AAA–13 | M6184D1035 | M6184D1001 | |
M81AAB–5 | M6184D1035 | M6184F1015 | |
M81AAC-1 | M6184D1035 | M6184F1016 | |
M81ACA-3 | M8185D1006 | M8185A1002 | |
M81ACB-1 | M8185D1006 | ||
M81ADA-2 | M8185D1006 | M4185B1017 | |
M81AEA-2 | M8185D1006 | M4185B1009 | |
M81AFA-2 | M8185D1006 | Use aux shaft | |
M81AFB-1 | M8185D1006 | M4185B1017 | Check stroke and aux switch |
WHITE RODGERS | |||
3402–7 | M8415A1004 | 90 sec, 90° | |
3402A–7 | |||
3403–4 | M8405A1006 | 90 sec, 90° | |
3405–2 | M836A1042 | 30 sec, 75° | |
3405–3 | M836A1042 | ||
3405A–2 | M436A1116 | ||
3405–11 | M836A1042 | 30 sec, 75° | |
3405A–11 | M436A1116 | ||
3405–14 | M836A1042 | ||
3420–4 | M9175D1014 | M9175D1014 | 30 sec |
3420A–4 | M9175D1014 | M9175D1014 | |
3430–7 | M7415A1006 | 30 sec | |
3430-18 | |||
3430-21 | |||
3440–4 | M9184D1013 | M9184A1019 | 150 lb-in, 60 sec |
OS # to be Replaced | Functional Replacement | Comments | |
M436A1017 | M436A1116 | ||
M436A1025 | M436A1124 | ||
M436A1033 | M436A1124 | ||
M436A1041 | M436A1116 | ||
M436A1058 | M436A1124 | ||
M436A1066 | M436A1124 | M436A1124 has 30 sec timing | |
M436A1074 | M436A1140 | M436A1140 has 50 sec timing | |
M436A1082 | M436A1116 | ||
M436A1090 | M436A1124 | ||
M436A1108 | M436A1124 | ||
M436A1116 | M436A1116 | ||
M436A1124 | M436A1124 | ||
M436A1132 | M436A1124 | M436A1124 has 30 sec timing | |
M436A1140 | M436A1124 | ||
M436A1157 | M436A1116 | ||
M436A1165 | M436A1116 | Ray Special | |
M436A1173 | M436A1124 | M436A1124 has 30 sec timing | |
M6414A1009 | |||
M6415A1008 | M6415A1016 | Trane Special, CCW Open | |
M6415A1016 | M6415A1016 | CCW to Open | |
M6415B1006 | M6415B1014 | Trane Special, CCW Open | |
M6415B1014 | M6415B1014 | CW to Open | |
M7405A1008 | M7405A1016 | ||
M7405A1016 | M7405A1016 | ||
M7415A1006 | M7415A1006 | ||
M7415A1014 | M7415A1006 | York Special | |
OS # to be Replaced | Functional Replacement | Comments | |
M7415A1048 | M7415A1006 | ||
M7415B1004 | M7415B1004 | Opens CW, spring return CCW | |
M828A ALL | M836A1042 | ||
M828B ALL | M836A1042 | ||
M828C ALL | M836A1042 | ||
M828D ALL | M836A1042 | ||
M828X ALL | M836A1042 | ||
M829A ALL | Rewire & replace control system with M835 | ||
M833A1007 | M833A1007 | ||
M833A1015 | M833A1007 | ||
M833A1023 | G.E. Special, special rotation | ||
M833A1031 | Trane Special, special rotation | ||
M835A1002 | M835A1051 | ||
M835A1010 | M835A1051 | Reset heat anticipator setting | |
M835A1028 | M835A1051 | ||
M835A1036 | M835A1051 | ||
M835A1044 | M835A1051 | Reset heat anticipator setting | |
M835A1051 | M835A1051 | Tradeline | |
M835A1069 | M835A1051 | ||
M836A1000 | M836A1042 | ||
M836A1018 | M836A1042 | ||
M836A1026 | M836A1042 | International | |
M836A1034 | M836A1042 | ||
M836A1042 | M836A1042 | Tradeline | |
M836A1059 | M836A1042 | International | |
M836A1067 | M836A1042 | ||
Request a Quote | |||
OS # to be Replaced | Functional Replacement | Comments | |
M836B1009 | M836B1033 | ||
M836B1017 | M836B1033 | ||
M836B1025 | M836B1033 | ||
M836B1033 | M836B1033 | Tradeline | |
M836B1041 | M836B1033 | Carrier Special | |
M8405A1006 | M8405A1006 | ||
M8405A1014 | M8405A1006 | York Special | |
M8405B1004 | Carrier Special | ||
M8414A1005 | M8414A1005 | Non spring return | |
M8415A1004 | M8415A1004 | ||
M842A1008 | M842A1008 | ||
M847A1008 | M847A1080 | ||
M847A1023 | M847A1072 | ||
M847A1031 | M847A1080 | Canada only, with 38 in. chain linkage & extended mount bracket | |
M847A1049 | M847A1072 | Canada Special with disengaging actuator arm | |
M847A1056 | M847A1072 | Arm not mounted | |
M847A1064 | M847A1072 | ||
M847A1072 | M847A1072 | With disengaging actuator arm | |
M847A1080 | M847A1080 | With 38 in. chain linkage, with extended mount bracket | |
M847A1098 | M847A1098 | Canada Special, with disengaging actuator arm, extended | |
mounting bracket included | |||
M984B1015 | Canada Versa Drive | ||
M986A1011 | |||
M986B1002 | |||
ML984A1030 | ML984A1030 | Canada Special | |
ML984B1004 | ML984B1004 | Liebert Special, no balance relay, with feedback potentiometer | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M204A1001 | M6184D1001 | Unidirectional stroke; Replacement is 160°, 30 sec timing | |
M204A1019 | M6184D1035 | M6184D1001 | Unidirectional stroke |
M204A1027 | Unidirectional stroke; For use with 25 Hz | ||
M204A1035 | M6184D1035 | M6184D1035 | Unidirectional stroke; Replacement is 160° |
M204A1043 | Unidirectional stroke; 25 Hz | ||
M204A1050 | M6184D1035 | M6194D1017 | Unidirectional stroke; Replacement is 160°, 300 lb-in. |
M204A1068 | M6184D1035 | M6184D1035 | Unidirectional stroke; Replacement is 160° |
M204B1000 | M6184D1035 | M6184D1035 | |
M405A1004 | Special timing and stroke | ||
M405A1020 | |||
M405B1003 | M8185D1006 | M4185B1009 | |
M405B1011 | M8185D1006 | M4185B1017 | |
M405B1029 | M8185D1006 | M4185B1017 | |
M405B1037 | M8185D1006 | M4185A1001 | |
M405B1045 | M8185D1006 | ||
M405B1052 | M8185D1006 | M4185B1017 | Replaced Motor is 60° |
M405B1086 | M8185D1006 | Replacement is 160°, 60 sec timing | |
M405B1094 | M8185D1006 | M4185A1001 | |
M405B1102 | M8185D1006 | M4185A1001 | |
M405C1002 | M8185D1006 | M4185A1001 | |
M405C1010 | M8185D1006 | M4185B1017 | |
M405C1028 | M8185D1006 | ||
M405C1036 | M8185D1006 | M4185B1058 | |
M405C1044 | M8185D1006 | M4185B1058 | |
M405C1051 | M8185D1006 | M4185B1058 | |
M405C1069 | M8185D1006 | M4185B1017 | |
M405D1001 | M8185D1006 | M4185B1009 | Use aux. end; N.O. |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M405D1019 | M8185D1006 | Use aux. end; N.O. | |
M405D1027 | M8185D1006 | ||
M405D1035 | M8185D1006 | ||
M445A1000 | M8185D1006 | M4185B1009 | |
M445A1018 | M8185D1006 | M4185B1009 | |
M445A1026 | M8185D1006 | M4185B1017 | |
M445A1034 | M8185D1006 | M4185B1017 | |
M445A1042 | M8185D1006 | M4185B1017 | |
M445A1059 | M8185D1006 | M4185B1017 | |
M445A1067 | M8185D1006 | ||
M445A1075 | M8185D1006 | M4185B1058 | 30 sec timing & 90° stroke |
M445A1091 | M8185D1006 | M4185B1009 | |
M445A1109 | M8185D1006 | M4185B1009 | |
M445A1117 | M8185D1006 | M4185B1058 | |
M445A1125 | M8185D1006 | M4185B1058 | |
M445A4004 | M8185D1006 | Canada Special, aux. switch set at 120° | |
M445C1008 | M8185D1006 | M4185B1009 | |
M445C1016 | M8185D1006 | M4185B1009 | Aux. switch set at 155° |
M445C1024 | M8185D1006 | M4185B1009 | |
M445D1007 | M8185D1006 | M4185A1001 | |
M445D1015 | M8185D1006 | M4185B1058 | |
M445D1023 | M8185D1006 | ||
M445D1031 | M8185D1006 | M4185B1017 | |
M445D1049 | M8185D1006 | M4185A1001 | 60 sec timing & 160° stroke |
M445D1056 | M8185D1006 | M4185A1001 | M445D was moisture fungus treated |
M465A1008 | M8185D1006 | M4185B1009 | 60 sec timing |
M465B1007 | M8185D1006 | M4185A1001 | |
M604A1002 | M6184D1035 | M6184A1023 | TRADELINE is 90°/160° |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M604A1028 | M6184D1035 | TRADELINE is 90°/160° | |
M604A1036 | M6184D1035 | ||
M604A1051 | Special shaft length | ||
M604A1069 | M6184D1035 | Bahnson Special; TRADELINE is 90°/160° | |
M604A1077 | M6184D1035 | TRADELINE is 90°/160° | |
M604B1001 | M6184D1035 | M6184A1023 | Change control circuit to 24 Vac |
M604B1019 | M6184D1035 | ||
M604B1027 | M6184D1035 | M6184A1023 | |
M604B1035 | M6184D1035 | ||
M604B1043 | M6184D1035 | ||
M604B1050 | Designed for use with 25 Hz | ||
M604B1068 | M6184D1035 | M6184A1023 | Change control circuit to 24 Vac |
M604B1076 | M6184D1035 | ||
M604C1059 | Micronik System | ||
M604C1083 | |||
M604D1009 | M6184D1035 | ||
M604D1017 | M6184D1035 | ||
M604E1008 | M6184D1035 | M6184F1014 | Replacement is 90°/160° stroke |
M604E1016 | M6184D1035 | M6184F1014 | |
M604E1024 | M6184D1035 | M6184F1014 | |
M634A1009 | M6184D1035 | M6184D1035 | Replacement is150 lb-in. torque |
M634B1008 | M6184D1035 | Change control circuit to 24 Vac | |
M634B1016 | M6184D1035 | ||
M634C1007 | M6184D1035 | M6184F1014 | Check torque |
M634C1015 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162AA |
M634C1023 | M6184D1035 | M6184F1014 | |
M634C1031 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162GA |
M634C1049 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162EA |
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M634C1056 | M6184D1035 | M6184F1014 | Check torque |
M634C1064 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162GA |
M634C1072 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162EA |
M634C1080 | M6184D1035 | M6184F1014 | 150 lb-in. torque; Replacement: requires 198162GA |
M634C1098 | M6184D1035 | M6184F1014 | |
M644A1008 | M6184D1035 | M6184D1035 | |
M644A1016 | M6184D1035 | M6184D1035 | |
M644A1024 | M6184D1035 | M6184A1015 | |
M644A1032 | |||
M644A1107 | |||
M644A1115 | |||
M644A1149 | M6184D1035 | ||
M644A1180 | M6184D1035 | M6184D1035 | Carrier Special |
M644B1007 | M6184D1035 | Change control circuit to 24 Vac | |
M644B1015 | |||
M644B1031 | M6184D1035 | Change control circuit to 24 Vac | |
M644B1049 | M6184D1035 | M6184A1023 | TRADELINE is 30/60 sec timing; Replacement is 150 lb-in. |
M644B1056 | M6194D1017 | ||
M644C1006 | M6184D1035 | M6184D1001 | TRADELINE is 30/60 sec timing |
M644C1014 | M6194D1017 | M6194D1017 | |
M644C1022 | M6184D1035 | ||
M644C1030 | M6194D1017 | M6194D1017 | |
M644C1055 | M6194D1017 | M6194D1017 | Lennox Special |
M644C1063 | M6184D1035 | ||
M644C1071 | M6194D1017 | York Special | |
M644C4000 | M6194D1017 | M6194D1017 | Canada Special |
M644D1005 | M6184D1035 | M6184F1014 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M644D1013 | M6184D1035 | M6184F1014 | |
M644D1021 | M6184D1035 | M6184F1014 | |
M644D1039 | M6184D1035 | M6184F1014 | |
M644D1047 | M6194D1017 | Lennox Special | |
M644E1004 | M6184D1035 | M6184F1014 | Aux. switch set at 4° |
M644E1012 | M6194D1017 | M6194B1011 | TRADELINE: 30/60 sec timing |
M644E1020 | M6184D1035 | Aux. switch set at 4° | |
M644E1038 | M6184D1035 | M6184D1001 | Requires Q607A1050; Set aux. switch at 40° |
M644E1053 | M6194D1017 | M6194E1006 | |
M644F1003 | M6184D1035 | M6184D1001 | Trane Special; Requires 198162AA & 24 Vac control circuit |
M644L1006 | M6194D1017 | ||
M644L1014 | M6184D1035 | M6184F1014 | Requires 198162AA |
M644L1022 | M6194D1017 | ||
M644L1030 | M6194D1017 | Trane Special, aux. switch set at 7° | |
M734A1007 | M7964A1001 | Special circuit | |
M734A1015 | M7964A1001 | ||
M734A1023 | M7964A1001 | Nesbitt Special; Special circuit | |
M734B1006 | M7964B1009 | Special circuit; Check transformer | |
M734B1014 | M7964B1009 | ||
M734B1022 | M7964B1009 | Nesbitt Special; Special circuit | |
M734B1030 | M7964B1017 | Special circuit | |
M734B1048 | M7964B1017 | Check transformer | |
M734C1005 | M7964C1015 | Special circuit | |
M734C1013 | M7964C1007 | Nesbitt Special; Special circuit | |
M734C1021 | M7964C1007 | ||
M734D1004 | M9164D1009 | ||
M734D1012 | M9164D1009 | ||
M734D1020 | M9164D1009 | ||
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M734D1038 | M9164D1009 | ||
M734D1046 | M9164D1009 | ||
M734D1053 | M9164D1009 | ||
M734E ALL | M9164D1009 | Use aux end of N.C. motor; N.O. | |
M734F ALL | M9164D1009 | ||
M734G ALL | M9164D1009 | ||
M734H1000 | M9164D1009 | M7164G1030 | Adjust for 10.5-13.5 Vdc, select CCW rotation; Elec. N.O. |
M734H1018 | M9164D1009 | Adjust for 4-7 Vdc, Select CCW; Electrically N.O. | |
M734H1026 | M9164D1009 | ||
M734H1034 | M9164D1009 | M7164G1030 | Adjust for 10.5-13.5 Vdc, select CCW rotation; Elec. N.O. |
M734J1007 | M9164D1009 | Adjust for 6-9 Vdc | |
M734J1015 | M9164D1009 | Adjust for 4-7 Vdc | |
M734J1023 | M9164D1009 | M7164A1017 | Lennox Special; Adjust for 10.5-13.5 Vdc |
M734J1031 | M9164D1009 | York Special; Adjust for 10.5-13.5 Vdc | |
M734J1049 | M9164D1009 | Lennox Special; Adjust for 10.5-13.5 Vdc | |
M734J1056 | M9164D1009 | M7164A1017 | Adjust for 10.5-13.5 Vdc |
M734J1064 | M9164D1009 | Adjust for 6-9 Vdc | |
M734J1072 | M9164D1009 | Adjust for 4-7 Vdc | |
M734K1006 | 3 wire output | ||
M734K1014 | Micronik system | ||
M741B1001 | Cleaver Brooks BRCS | ||
M741B1019 | M7484A1010 | BRCS | |
M744A1006 | M9184D1021 | ||
M744A1014 | M9184D1021 | ||
M744A1022 | M9184D1013 | Westinghouse Special | |
M744B ALL | |||
M744D1003 | M9184D1021 | Adjust for 4-7 Vdc | |
M744D1011 | M9184D1013 | For use with W7080 systems | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M744D1029 | |||
M744D1037 | Despatch Industries | ||
M744D1045 | |||
M744E1002 | Micronik, with external overdrive | ||
M744F1001 | M9184D1013 | Includes internal heater | |
M744G1000 | 3 wire output | ||
Micronik system | |||
M744J1006 | With zero adjustment | ||
M744S1005 | M9184D1021 | M7284A1004 | Adjust for 4-20 mA |
M744S1013 | M9184D1021 | M7284A1012 | |
M744T1004 | M9184D1021 | M7284C1000 | |
M744T1012 | M9184D1021 | M7284C1018 | |
M744Y1009 | M9184D1021 | M7284Q1009 | Adjust for desired range |
M744Y1017 | M9184D1021 | M7284Q1017 | Adjustable zero span |
M745A1003 | M9185D1004 | ||
M745A1011 | M9185D1004 | ||
M745A1029 | M9185D1004 | ||
M745B1002 | M9185D1004 | Use aux end of N.C. motor; N.O. mech. and elec. | |
M745C1001 | M9185D1004 | Used with W936 & W945 systems | |
M745D ALL | N.O. | ||
M745E1009 | M9185G1006 | N.O. mechanically, N.C. electrically | |
+Q7330A1006 | |||
M745F1008 | N.C. mechanically, N.O. electrically | ||
M745G1007 | M9185D1004 | M7185A1004 | Adjust for 4-7 Vdc, Select CCW, use aux shaft; N.O. mech. |
and elec. | |||
M745H1006 | M9185D1004 | ||
M745J1003 | 3 wire output, Micronik System, electrically N.O. | ||
M745K1002 | M9185D1004 | Lennox Special, select CCW rotation, electrically N.O. | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M745L1001 | M9185D1004 | Lennox Special | |
M745L1019 | M9185D1004 | York Special | |
M745L1027 | M9185D1004 | ||
M745L1035 | M9185D1004 | Lennox Special | |
M745L1043 | M9185D1004 | ||
M745M1000 | M9185D1004 | Adjust for 6-9 Vdc, use aux. end; Mechanically N.O. | |
M745M1018 | M9185D1004 | Lennox Special; Adjust for 10.5-13.5 Vdc, use aux. end | |
M745M1026 | M9185D1004 | Adjust for 4-7 Vdc, use aux. end; Mechanically N.O. | |
M745M1034 | M9185D1004 | Lennox Special, Adjust for 4-7 Vdc, use aux. end, mech. N.O. | |
M745M1042 | M9185D1004 | Adjust for 4-7 Vdc, use aux. end; Mechanically N.O. | |
M745N1009 | M9185D1004 | Lennox Special; Adjust for 10.5-13.5 Vdc, select CCW | |
rotation | |||
M745N1017 | M9185D1004 | Mammoth Special, Adjust for 10.5-13.5 Vdc, select CCW | |
rotation; elect. N.O. | |||
M745N1025 | M9185D1004 | Adjust for 4-7 Vdc, Select CCW; Electrically N.O. | |
M745P1007 | M9185D1004 | M7185A1004 | Adjust for 4-7 Vdc |
M745P1015 | M9185D1004 | Lennox Special; Adjust for 10.5-13.5 Vdc | |
M745Q1006 | |||
M745S1002 | M9185D1004 | M7285A1003 | Adjust for 4-20 mA |
M745S1010 | M9185D1004 | M7285A1011 | |
M745T1001 | M9185D1004 | M7285C1009 | |
M745T1019 | M9185D1004 | M7285C1017 | |
M745Y1006 | M9185D1004 | M7285Q1008 | Adjustable zero span, Adjust for desired range |
M745Y1014 | M9185D1004 | M7285Q1016 | |
M765A1001 | M9175D1014 | ||
M765A1019 | M9175D1014 | ||
M765K1000 | M9175D1014 | Select CCW rotation; Use with W7080 system, elec. N.O. | |
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M765L1009 | M9175D1014 | For use with W7080 system | |
M765L1017 | M9175D1014 | ||
M765L1025 | M9175D1014 | Trane Special; use with W7080 system | |
M765N1007 | M9175D1014 | Lennox Special; Adjust for 10.5-13.5 Vdc, select CCW | |
M765N1015 | M9175D1014 | rotation, elect. N.O. | |
M765P1005 | McDonald’s Special; 3 wire output | ||
M765P1013 | York Special; 3 wire output | ||
M765Q1004 | Nesbitt Special | ||
M805B1004 | M8185D1006 | M8185A1002 | |
M805B1012 | Designed for use with 25 hz | ||
M805B1020 | M8185D1006 | M8185A1002 | |
M805B1038 | M8185D1006 | ||
M805C1003 | M8185D1006 | M8185A1002 | |
M805D1002 | M8185D1006 | M4185B1009 | Use aux. motor end; N.O. |
M845A1001 | M8185D1006 | ||
M845A1027 | M8185D1006 | M4185B1017 | |
M845A1035 | M8185D1006 | M4185B1058 | Requires 198162AA |
M845A1050 | |||
M845A1068 | |||
M845A4005 | M8185D1006 | Canada Special, Aux. switch set at 120° | |
M845B1000 | M8185D1006 | ||
M845B1018 | M8185D1006 | M4185B1017 | |
M845B1026 | M8185D1006 | ||
M845C1009 | M8185D1006 | M8185A1002 | |
M845D1008 | M8185D1006 | Univac Special | |
M845D1016 | M8185D1006 | M4185B1017 | G.E. Special |
M845D1024 | M8185D1006 | Braden Special | |
M845E1007 | M8185D1006 | M4185B1009 | Use aux. motor end; N.O. |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M845E4001 | M8185D1006 | M4185B1009 | Canada Special; Use aux. motor end |
M865A1009 | M8185D1006 | ||
M865B1008 | M8185D1006 | ||
M904A1006 | M9184D1013 | M9184A1019 | |
M904E1002 | M9184D1013 | M9184A1019 | |
M904E1010 | 25 Hz | ||
M904E1028 | 40 Hz | ||
M904E1036 | M9184D1013 | M9184A1019 | Add Q181 for slaved motor applications |
M904E1051 | M9184D1013 | ||
M904E1085 | M9184D1013 | Special cam for few positions | |
M904E1119 | M9194D1003 | TRADELINE is 90/160 degrees | |
M904E1150 | M9184D1013 | M9194D1003 | Add Q181 for slaved motor applications |
M904E1176 | M9184D1013 | M9194D1003 | |
M904E1218 | |||
M904E1226 | Ariel Davis Mfg., special cam | ||
M904E1234 | Special timing; For 30 sec 160° motor, Select M9184D1013 | ||
M904E1242 | |||
M904E1267 | M9184D1013 | M9184D1005 | Add Q181 for slaved motor applications |
M904E1358 | M9184D1013 | M9184A1019 | |
M904E1366 | M9184D1013 | M9184A1035 | Univac Special |
M904E1374 | Fungus treated | ||
M904F1001 | |||
M904F1019 | |||
M904F1027 | M6284D1000 | M6284D1000 | No internal balance circuit, requires Q181 when using R927 |
M904F1035 | M6284D1000 | M6284D1000 | |
M904F1043 | M6284D1000 | M6284F1013 | |
M904F1050 | M6284D1000 | ||
M904G1000 | M6284D1000 | M6284D1000 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M905E1009 | M9185D1004 | M9185A1018 | Add Q181 for slaved motor applications |
M905E1025 | M9185D1004 | M9185A1018 | |
M905E1058 | M9185D1004 | M9185A1018 | |
M905E1066 | M9185D1004 | M9185A1026 | |
M905E1074 | M9185D1004 | M9185A1018 | |
M905E1082 | M9185D1004 | M9185A1018 | |
M905E1108 | M9185D1004 | M9185A1018 | |
M905E1116 | M9185D1004 | M9185A1018 | |
M905E1124 | M9185D1004 | M9185A1018 | |
M905F1008 | M9185D1004 | M9185A1018 | |
M905F1016 | M905F1016 designed for 25 Hz | ||
M905F1024 | M9185D1004 | M9185A1018 | Add Q181 for slaved motor applications |
M905F1032 | M9185D1004 | M9185A1018 | |
M905G1007 | M9185D1004 | M9186G1006 | Use aux. motor end |
M905G1015 | M9185D1004 | M9186G1006 | N.O. |
M905G1023 | M9185D1004 | M9186G1006 | Use aux. end; Add Q181 for slaved motor applications |
M905H1006 | M6285A1005 | M6285A1005 + Q209/S963 | No internal balance circuit, requires Q181 when using R927 |
M905H1014 | M6285A1005 | ||
M905J1003 | M6285A1005 | M6285A1005 | |
M905K1002 | M6285A1005 | M6285A1005 | |
M905K1010 | M905K1010 designed for 25 Hz | ||
M905L1001 | M6285A1005 | M6285A1005 | Use aux. motor end, No internal balance circuit; N.O. |
M905L1019 | M905L1019 designed for 25 Hz | ||
M905N1009 | M9185D1004 | M9185C1006 | |
M905N1017 | M6285A1005 | M9185C1006 | For use with W841 |
M905N1025 | M6285A1005 | M9185C1006 | Replacement is less power supply cord, for use with W841, |
no internal balance circuit | |||
M905P1007 | M6285A1005 | M6285A1005 | For use with W841 No internal balance circuit |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M905P1015 | M6285A1005 | M6285A1005 | Replacement is less power supply cord, for use with W841, |
no internal balance circuit | |||
M931A1009 | M9484D1010 | ||
M931A1017 | |||
M931A1025 | M9484D1010 | ||
M931A1033 | |||
M931A1041 | M9484D1002 | ||
M931A1058 | M9484D1002 | ||
M931A1066 | M9484D1010 | ||
M931A1074 | M9484D1010 | ||
M931A1082 | |||
M931A1090 | |||
M931A1108 | |||
M931A1116 | M9484D1010 | ||
M931A1124 | M9494D1000 | ||
M931A1132 | M9484D1002 | ||
M931A1140 | M9484D1010 | ||
M931A1157 | Special timing | ||
M931A1165 | M9484D1002 | ||
M931A1173 | M9484D1010 | ||
M931A1181 | |||
M931A1199 | M9484D1010 | ||
M931A1207 | M9484D1010 | ||
M931A1215 | M9484E1017 | ||
M931A1223 | |||
M931A1231 | M9484E1017 | ||
M931A1249 | Special timing | ||
M931A1256 | M9484E1009 | ||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M931A1264 | M9484E1017 | ||
M931A1272 | |||
M931A1280 | M9484E1033 | ||
M931A1298 | |||
M931A1306 | M9484D1010 | ||
M931A1314 | M9494D1000 | ||
M931A1322 | M9484D1010 | ||
M931A1330 | |||
M931B1008 | M6284F1013 | No internal balance circuit, requires Q181 when using R927 | |
M931B1016 | M6284F1013 | ||
M931B1024 | M6284D1000 | ||
M931B1032 | |||
M931B1040 | M6284D1000 | No internal balance circuit, requires Q181 when using R927 | |
M931B1057 | |||
M931C1007 | M9484E1017 | ||
M931C1015 | |||
M931C1023 | M9484E1017 | ||
M931C1031 | International special timing | ||
M931C1049 | M9484E1009 | ||
M931C1056 | |||
M931C1064 | M9484E1017 | International | |
M931C1072 | M9484E1033 | Switch set in 90° position | |
M931D1006 | M6284F1013 | No internal balance circuit | |
M931D1014 | M6284F1013 | ||
M934A1003 | M9164D1009 | ||
M934A1011 | M9164D1009 | ||
M934A1029 | M9164D1009 | M9164A1021 | Wire M9164A1021 to 24 Vac |
M934A1037 | M9164D1009 | M9164A1088 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M934A1045 | M9164D1009 | M9164C1050 | Wire M9164C1050 to 24 Vac |
M934A1052 | M9164D1009 | M9164C1050 | |
M934A1060 | M9164D1009 | ||
M934A1078 | M9164D1009 | ||
M934A1086 | M9164D1009 | M9164A1021 | |
M934A1094 | M9164D1009 | M9164C1050 | |
M934A1102 | M9164D1009 | York Special | |
M934A1128 | M9164D1009 | M9164C1068 | |
M934A1136 | M9164D1009 | M9164A1005 | |
M934A1144 | M9164D1009 | ||
M934A1169 | M9164D1009 | M9164A1021 | Wire M9164A1021 to 24 Vac |
M934A1193 | M9164D1009 | M9164C1050 | Wire M9164C1050 to 24 Vac |
M934A1201 | M9164D1009 | M9164A1013 | |
M934A1219 | M9164D1009 | M9164A1021 | |
M934A1227 | M9164D1009 | M9164D1009 | |
M934A1235 | M9164D1009 | M9164A1088 | |
M934A1243 | M9164D1009 | M9164C1050 | Wire M9164C1050 to 24 Vac |
M934A1250 | M9164D1009 | M9164C1050 | |
M934A1268 | M9164D1009 | ||
M934A1276 | M9164D1009 | ||
M934A1284 | M9164D1009 | M9164A1021 | |
M934A1292 | M9164D1009 | M9164C1050 | |
M934A1300 | M9164D1009 | York Special | |
M934A1318 | M9164D1009 | M9164C1068 | |
M934A1326 | M9164D1009 | M9164A1005 | Carrier Special |
M934A1334 | M9164D1009 | ||
M934A1342 | M9164D1009 | M9164A1021 | Wire M9164A1021 to 24 Vac |
M934A1359 | M9164D1009 | M9164C1050 | Wire M9164C1050 to 24 Vac |
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M934A1367 | M9164D1009 | Carrier Special | |
M934A1375 | M9164D1009 | ||
M934A1383 | M9164D1009 | M9164A1013 | For use with W899A systems |
M934A1391 | M9164D1009 | M9164A1005 | |
M934A1409 | M9164D1009 | ||
M934A1425 | M9164D1009 | M9164A1021 | Use with W899A,E,F systems; Wire M9164A1021 to 24 Vac |
M934A1433 | M9164D1009 | For use with W899A systems | |
M934A1441 | M9164D1009 | M9164A1021 | |
M934A1458 | M9164D1009 | ||
M934A1466 | M9164D1009 | ||
M934A1474 | M9164D1009 | M9164C1050 | Wire M9164C1050 to 24 Vac |
M934A1482 | M9164D1009 | M9164C1050 | |
M934A1490 | M9164D1009 | Carrier Special | |
M934A1508 | M9164D1009 | Use with W899A systems | |
M934A1516 | M9164D1009 | M9164C1068 | |
M934A1524 | M9164D1009 | M9164A1021 | Wire M9164A1021 to 24 Vac |
M934A1532 | M9164D1009 | ||
M934A1540 | M9164D1009 | M9164A1005 | York Special |
M934A1557 | M9164D1009 | G.E. Special | |
M934A1565 | M9164D1009 | M9164C1068 | Reset aux. switch |
M934A1573 | M9164D1009 | M9164A1021 | Carrier Special |
M934A1599 | M9164D1009 | ||
M934B1036 | M6284D1000 | M6284F1013 | No internal balance circuit, requires Q181 when using R927 |
M934C1001 | M9164D1009 | M9164A1005 | Nesbitt Special; Q181 for Nesbitt Relay Driver |
+Q181A1004 | |||
M934D1000 | M9174D1007 | M9174B1043 | |
M934D1018 | M9174D1007 | M9174C1033 | |
M934D1026 | M9174D1007 | M9174B1027 + | |
220738A | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M934D1034 | M9174D1007 | M9174C1025 | |
M934D1042 | M9174D1007 | Cleaver Brooks Special | |
M934D1059 | M9174D1007 | ||
M934E1009 | M9174D1007 | M9174B1043 | Remove transformer |
M934E1017 | M9174D1007 | M9174B1043 | |
M934E1025 | M9174D1007 | M9174B1043 | |
M941A1008 | M9484D1002 | Shipped in 160° position | |
M941A1016 | M9484D1010 | Tapped aux shaft, Shipped in 160° position | |
M941A1024 | M9484D1002 | Shipped in 160° position | |
M941A1032 | M9484D1010 | Tapped aux shaft; Shipped in 90° position | |
M941A1040 | Special timing | ||
M941A1057 | M9484D1002 | Shipped in 90° position | |
M941A1065 | M9484D1002 | International Shipped in 160° position | |
M941A1073 | M9484D1010 | Tapped aux shaft; International Shipped in 90° position | |
M941A1081 | M9484D1010 | Tapped aux shaft; International Shipped in 160° position | |
M941A1099 | M9494D1000 | International Shipped in 90° position | |
M941A1107 | Special timing shipped in 90° position | ||
M941A4002 | M9484D1010 | Canada Special; Tapped aux shaft | |
M941B1007 | M6284F1013 | No internal balance circuit | |
M941B1015 | M6284D1000 | ||
M941C1006 | M9484E1009 | Shipped in 160° position | |
M941C1014 | M9484E1017 | Tapped aux shaft; Shipped in 160° position | |
M941C1022 | M9484E1033 | Shipped in 90° position | |
M941C1030 | M9484E1033 | Tapped aux shaft, aux switch set to 7°; Shipped in 90° | |
position, switch set at 4°, with crankarm | |||
M941C1048 | M9484E1033 | Aux. switch set at 4°, with crankarm; Shipped in 90° | |
position. | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M941C1055 | M9484E1033 | Tapped aux shaft, aux. switches set to 4°; International, | |
shipped in 90° position, with tapped shaft | |||
M941C1063 | M9484E1033 | Tapped aux shaft, replaced model includes crank arm; Tapped shaft | |
M941C1089 | Cleaver Brooks Special, Tapped aux shaft | ||
M941C4000 | M9484E1017 + | Canada Special, Tapped aux shaft, aux switch set at 5°, | |
220741A | tapped shaft | ||
M941C4018 | M9484E1017 + | Canada Special, Tapped aux shaft, aux switch set at 30°, | |
220741A | tapped shaft | ||
M941D1005 | M9484F1007 | Aux switched set to 7°/57°; Shipped in 90° position, | |
switches set at 5°/54°, no tapped shaft | |||
M941D1013 | M9484F1007 | Tapped aux shaft, aux. switch set to 7°/57°; Shipped in 90° | |
position, Switches set at 5°/54°, crankarm, no tapped shaft | |||
M941D1021 | M9484F1023 | Tapped aux shaft, shipped in 160° position | |
M941D1039 | M9484F1031 | Tapped aux shaft, aux switches set to 5°/54°; tapped shaft, | |
shipped in 90° position | |||
M941D1047 | M9484F1049 | Tapped aux shaft, aux switches set to 35°/120° | |
M941D1054 | M9484F1031 | Tapped aux shaft, aux switches set to 5°/54°; International, Shipped in 90° position | |
M941D1062 | M9484F1031 | Tapped aux shaft, aux switches set to 90°/107°; International | |
M941D1070 | M9484F1007 | Cleaver Brooks Special; Tapped aux shaft, aux switches set | |
to 5°/54° | |||
M941D1112 | Aux. switches to 7°/57° | ||
M941D4009 | M9484F4001 | Canada Special, requires 220741A, switch preset at 5°/54°; Tapped aux shaft, aux. shaft set to 5°/54° | |
M941D4017 | M9484F4019 | ||
M941E1012 | M9484D1002 | International | |
M941E1038 | M9484D1010 | ||
M941E1046 | M9484D1010 | ||
M941E1053 | |||
M941E1061 | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M943A1004 | Singer Special, 240° stroke | ||
M944A1002 | M9184D1013 | M9184A1019 | |
M944A1010 | M9184D1021 | M9184A1019 | |
M944A1028 | M9184D1021 | M9184A1035 | |
M944A1036 | |||
M944A1044 | |||
M944A1051 | M9184D1013 | M9184F1000 | Univac Special |
M944A1069 | M9184D1013 | M9184F1000 | Requires 198162AA |
M944A1119 | No 335° stroke motors | ||
M944A1127 | |||
M944A1150 | M9184D1013 | M9194D1003 | Chrysler Special, check timing |
M944A1168 | M9184D1013 | M9184A1019 | |
M944A1176 | M9184D1013 | M9184A1019 | |
M944A1192 | M9184D1013 | M9184F1000 | Nesbitt Special |
M944B1001 | M6284D1000 | M6284D1000 | No internal balance circuit, requires Q181 when using R927 |
M944B1019 | M6284D1000 | M6284D1000 | |
M944B1027 | |||
M944B1035 | M6284D1000 | ||
M944B1043 | M6284D1000 | M6284A1055 | No internal balance circuit, check timing and stroke, |
M944B1167 | M6284D1000 | M6284D1000 | requires Q181 when using R927 |
M944B1175 | M6284D1000 | M6284D1000 | |
M944B1183 | M6284D1000 | M6284D1000 | |
M944B1191 | M6294D1008 | No internal balance circuit, requires Q181 when using R927 | |
M944B1209 | M6284D1000 | M6284D1000 | |
M944B1241 | M6294D1008 | ||
M944B4005 | M6284D1000 | M6284D1000 | Canada Special, no internal balance circuit, requires Q181 |
when using R927 | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M944C1000 | M9184D1021 | M9184D1005 | M9184D is 30/60 sec timing |
M944C1018 | M9194D1003 | M9194D1003 | |
M944C1042 | M9184D1021 | M9184D1013 | |
M944C1059 | M9194D1003 | M9194E1000 | |
M944C4004 | M9184D1013 | M9184D1013 | Canada Special |
M944C4012 | M9184D1021 | M9194D1003 | |
M944D1009 | M9184D1013 | M9184F1000 | |
M944D1017 | M9184D1021 | M9184F1000 | |
M944E1008 | M6284D1000 | M6284 is 30/60 sec timing, No internal balance circuit | |
M944E1016 | M6284D1000 | M6284F1013 | No internal balance circuit |
M944E1024 | M6284D1000 | M6284F1013 | Set aux switches at 4°/54°, no internal balance circuit |
M944E1032 | M6284D1000 | Replaced motor is 2X faster, No internal balance circuit | |
M944E1040 | M6284D1000 | M6284F1013 | No internal balance circuit |
M944E1057 | M6284D1000 | M6284F1013 | Set aux switches at 4°/54°, no internal balance circuit |
M944E1081 | M6284D1000 | M6284F1013 | Set aux switches at 42°/48°, no internal balance circuit |
M944E1099 | M6284D1000 | M6284F1013 | No internal balance circuit |
M944F1007 | M9184D1013 | M9184A1019 | Use Q181 for slaved motor applications |
M944G1006 | M9184D1013 | M9184F1000 | |
M944G1014 | M9184D1013 | M9184F1000 | |
M944G1022 | M6284D1000 | M6284A1048 | No internal balance circuit, change control circuit to 24 Vac |
M944G1030 | M6284D1000 | M6284A1055 | |
M944G1048 | M6284D1000 | M6284A1048 | |
M944G1055 | M6284D1000 | No internal balance circuit | |
M944G1063 | M6284D1000 | M6284A1048 | No internal balance circuit, change control circuit to 24 Vac |
M944G1071 | M6284D1000 | M6284A1055 | |
M944G1089 | M6284D1000 | M6284A1048 | |
M944G1097 | M6284D1000 | M6284A1055 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M944G1105 | M6294D1008 | No internal balance circuit | |
M944G1121 | M6294D1008 | ||
M944H1013 | M6284D1000 | M6284F1013 | No internal balance circuit, change control circuit to 24 Vac; Requires 198162EA |
M944H1021 | M6284D1000 | M6284F1013 | |
M944H1039 | M6284D1000 | M6284F1013 + | York Special, no internal balance circuit, change control |
198162EA | circuit to 24 V | ||
M944H1047 | M6284D1000 | M6284F1013 + | No internal balance circuit; Change control circuit to 24V |
198162EA | |||
M944H1062 | M6294D1008 | Trane Special, no internal balance circuit | |
M944J1002 | M6284D1000 | M6284D1000 | No internal balance circuit, requires Q181 for aux. pot and |
M944J1051 | M6284D1000 | M6284D1000 | when using R927 |
M944K1001 | M6284D1000 | M6284F1013 | No internal balance circuit, change control circuit to 24 Vac; Requires 198162EA |
M944K1019 | M6284D1000 | M6284F1013 | |
M944L1018 | M9184D1013 | ||
M944N1024 | M9184D1021 | M6184D1001 | Tapped shaft |
+Q607A1050 | |||
M944N1032 | M9184D1021 | M9184F1034 | |
M944N1040 | M9184D1021 | M9184F1034 | |
M944N1057 | M9184D1021 | M9184F1034 | |
M944N1065 | M9184D1021 | M6184D1001 | M9184D is 60 sec at 160° stroke; Tapped shaft; Requires Q607A1050 |
M944N1073 | M9184D1021 | M9184F1034 | Tapped shaft |
M944N1081 | M9184D1021 | M9184F1034 | |
M944P1014 | M9184D1021 | M9184F1034 | |
M944P1022 | M9184D1021 | M9184F1034 | |
M944P1030 | M9184D1021 | M9184F1034 | |
M944P1048 | M9184D1021 | M9184F1034 | |
M944R1012 | M6294D1008 | Carrier Special; Check timing and stroke, requires Q181 | |
M944R1020 | M6294D1008 | when using R927 | |
Request a Quote | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M944S1001 | M6284D1000 | M6284 is 30/60 sec timing, No internal balance circuit | |
M944S1019 | M6284D1000 | M6284F1013 | No internal balance circuit; Requires 198162EA |
M944S1027 | M6284D1000 | M6284F1013 | |
M945A1009 | M9185D1004 | M9185A1018 | |
M945A1017 | M9185D1004 | M9185A1018 | |
M945A1025 | M9185D1004 | M9185A1018 | Less power supply cord |
M945A1033 | M9185D1004 | M9185A1018 | |
M945A1066 | M9185D1004 | M9185A1018 | For use with W899B systems |
M945A1074 | M9185D1004 | M9185A1026 | |
M945A1082 | M9185D1004 | M9185A1026 | |
M945A1090 | M9185D1004 | M9185D1004 | |
M945A1108 | M9185D1004 | M9185A1018 | York Special |
M945A1116 | M9185D1004 | M9185A1026 | |
M945A1124 | M9185D1004 | M9185A1026 | Nesbitt Special |
M945A1157 | M9185D1004 | M9185D1004 | |
M945A4003 | M9185D1004 | M9185D1004 | Canada Special |
M945AA1007 | M9185D1004 | Nesbitt Special, N.O. mech.; M9185D is 30 sec., 90° stroke, | |
use aux. end | |||
M945AB1005 | M9185D1004 | Nesbitt Special; M9185 is 30 sec at 90° stroke | |
M945AB1013 | M9185D1004 | ||
M945AD1001 | M6285A1013 | Trane Special, No internal balance circuit | |
M945B1057 | M6285A1005 | M6285A1005 | No internal balance circuit, requires Q181 when using R927 |
M945B1065 | M6285A1013 | M6285A1013 | |
M945B1073 | Nesbitt Special, includes 1.0K ohm feedback pot | ||
M945B1081 | |||
M945B1115 | M6285A1013 | Trane Special, no internal balance circuit | |
M945B4002 | M6285A1005 | M6285A1005 | Canada Special, no internal balance circuit, requires Q181 |
when using R927 | |||
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M945C1007 | M6285A1005 | M6285C1001 | No internal balance circuit, requires Q181 when using R927 |
M945C1015 | M6285A1005 | M6285C1001 | |
M945C1031 | M6285A1013 | ||
M945D1006 | M9185D1004 | M9185C1006 | |
M945D1030 | |||
M945D1048 | |||
M945E1005 | M9185D1004 | M9185A1018 | Q181: slaved motor application |
M945E1013 | M9185D1004 | M9185A1018 | Add Q181 for slaved motor applications |
M945F1004 | M9185D1004 | M9186G1006 | Use aux. motor end; N.O. |
M945F1038 | M9185D1004 | M9186G1006 | Use aux. motor end; For use with W899M systems, N.O. |
M945F1046 | M9185D1004 | Use aux. motor end; N.O. | |
M945F1053 | M9185D1004 | M9186G1006 | York Special, N.O.; Use aux. motor end |
M945F4008 | M9185D1004 | M9186G1006 | Canada Special, N.O.; Use aux. motor end |
M945G1003 | M6285A1005 | M6285A1005 | Use aux. motor end; No internal balance circuit, requires Q181 when using R927 |
M945G1037 | M6285A1005 | M6285A1005t | |
M945G1045 | Includes 1.8K ohm feedback pot | ||
M945G1052 | IBM Special, N.O., 100K-ohm pot. | ||
M945H1002 | M9185D1004 | M9185C1006 | M945H includes internal heater |
M945H1010 | M9185D1004 | M9185C1006 | |
M945J1009 | M9185D1004 | M9185C1006 | |
M945J1017 | M9185D1004 | M9185C1006 | Less power supply cord |
M945J1025 | M9185D1004 | M9185C1006 | |
M945J1033 | M9185D1004 | ||
M945K1008 | M6285A1005 | M6285C1001 | No internal balance circuit |
M945K1016 | M6285A1005 | M6285C1001 | |
M945L1007 | M6285A1005 | M6285A1005 | No internal balance circuit, requires Q181 when using R927 |
M945L1015 | M6285A1005 | M6285A1005 | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M945M1006 | M9185D1004 | M9185A1018 | |
M945M1022 | M9185D1004 | G.E. Special | |
M945M1030 | M9185D1004 | M9185A1018 | Use with W899C systems |
M945M1048 | M9185D1004 | M9185A1018 | |
M945Y1002 | M6285A1005 | M6285A1005 | Add Q181 for slaved motor applications |
M945Y1010 | Nesbitt Special | ||
M945Z1001 | M9185D1004 | M9186G1006 | N.O.; Requires Q607B1067 |
M945Z1019 | M9185D1004 | N.O. | |
M954A1001 | M9184D1021 | M9184D1021 | |
M954A1019 | M9184D1021 | M9184D1021 | |
M954A1027 | M9184D1021 | M9184D1021 | |
M954A1035 | M9184D1021 | M9184D1021 | |
M954B1000 | M9184D1021 | M9184F1034 | |
M954B1018 | M9184D1021 | M9184C1031 | |
M954B1026 | M9184D1021 | M9184C1031 | |
M954B1034 | M9184D1021 | M9184C1031 | |
M954B1042 | M9184D1021 | M9184C1031 | |
M954B1059 | M9184D1013 | M9184D1005 | Requires 198162AA |
M954B1067 | M9184D1021 | M9184F1034 | |
M954B1075 | M9184D1013 | Cleaver Brooks Special | |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M954C1009 | M9184D1013 | M9184D1005 | |
M954C1017 | M9184D1021 | M9184F1034 | |
M954C1025 | M9184D1021 | M9184F1034 | |
M954C1033 | M9184D1021 | M9184F1034 | |
M954C1041 | M9184D1013 | M9184D1005 | |
M954C1058 | M9184D1021 | M9184F1034 | |
M954C1066 | M9184D1013 | M9184F1034 | |
M954C1074 | M9184D1021 | M9184F1034 | |
M954C1082 | M9184D1013 | M9184F1034 | Cleaver Brooks Special |
M954C4003 | M9184D1021 | Canada Special, aux. switch set at 120° | |
M954D1008 | M9184D1013 | M9184F1034 | |
M954D1016 | M9184D1021 | M9184F1034 | |
M954G1052 | IBM Special, N.O., 100K-ohm pot. | ||
M955A1008 | M9185D1004 | M9185D1004 | |
M955A1016 | M9185D1004 | M9185D1004 | |
M955A1024 | M9185D1004 | M9185D1004 | |
M955A1032 | M9185D1004 | M9185D1004 | |
M955B1007 | M9185D1004 | M9185E1019 | |
+Q607A1050 | |||
M955C1006 | M9185D1004 | M9185E1019 | |
M955C1014 | M9185D1004 | M9185E1019 | |
M955C4000 | M9185D1004 | M9185E1019 | Canada Special, Tapped shaft; TRADELINE shaft not |
tapped | |||
M955D1005 | M9185D1004 | M9185A1018 | |
M955D1013 | M9185D1004 | M9185A1026 | |
M955D1039 | M9185D1004 | ||
M955D1047 | M9185D1004 | M9185A1026 | Lennox Special |
M955D1054 | M9185D1004 | M9184A1035 | York Special |
OS # to be Replaced | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | Comments |
Model Number | |||
M955E1004 | M9185D1004 | ||
M955E1012 | M9185D1014 | Trane Special, includes Q209C | |
M965A1007 | M9175D1014 | M9175D1014 | |
M965A1015 | M9175D1014 | M9175D1014 | For use with W963B systems |
M965A1023 | M9175D1014 | ||
M965A1031 | M9175D1014 | York Special | |
M965A1049 | M9175D1014 | M9175D1014 | Requires 198162EA |
M965A1064 | M9175D1014 | M9175D1014 | No balance relay |
M965A1072 | M9175D1014 | M9175D1014 | Trane Special |
M965B1006 | M9175D1014 | ||
M965B1014 | M9175D1014 | ||
M965B1022 | M9175D1014 | ||
M965B1030 | M9175D1014 | Reznor Special | |
M975A1006 | M9175D1014 | M9175D1014 | |
M975A1014 | M9175D1014 | M9175D1014 | |
M975A1022 | M9175D1014 | M9175D1014 | Requires 198162EA |
M975A1030 | M9175D1014 | Trane Special | |
M975A1055 | M9175D1014 | Carrier Special | |
M975A1071 | M9175D1014 | M9175D1014 | |
M975A1089 | M9175D1014 | M9175D1014 | |
M975A1097 | M9175D1014 | M9175D1014 | Requires 198162EA |
M975B1005 | M9175D1014 | ||
M975B1013 | M9175D1014 | ||
M975B1021 | M9175D1014 | Trane Special | |
M975B1039 | M9175D1014 | Carrier Special | |
M975B1047 | M9175D1014 | Trane Special, aux. switches set at 35° | |
M975B1062 | M9175D1014 | Reznor Special, aux. switches set at 35° | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M4172A1006 | M8185D1006 | M4185A1001 | |
M4172B1004 | M8185D1006 | M4185B1009 | |
M4175D1015 | M8185D1006 | ||
M4175E1012 | M8185D1006 | ||
M4182A1004 | M8185D1006 | M4185A1001 | |
M4182B1002 | M8185D1006 | M4185B1009 | |
M4182B1010 | M8185D1006 | M4185B1017 | |
M4182B1028 | M8185D1006 | ||
M4182B1036 | M8185D1006 | M4185B1058 | |
M4182B1044 | M8185D1006 | M4185B1058 | |
M4182B1051 | M8185D1006 | M4185B1058 | With weatherproof kit; Requires 4074ERU |
M4182B1069 | M8185D1006 | M4185B1009 | |
M4185A1001 | M8185D1006 | M4185A1001 | |
M4185A1019 | |||
M4185A1027 | M8185D1006 | M4185A1001 | |
M4185B1009 | M8185D1006 | M4185B1009 | |
M4185B1017 | M8185D1006 | M4185B1017 | |
M4185B1025 | M8185D1006 | ||
M4185B1033 | M8185D1006 | M4185B1009 | |
M4185B1041 | M8185D1006 | M4185B1017 | |
M4185B1058 | M8185D1006 | M4185B1058 | |
M4185B1066 | M8185D1006 | M4185B1058 | |
M4185B1074 | M8185D1006 | ||
M4185C1007 | M8185D1006 | ||
M4185D1013 | M8185D1006 | ||
M4185E1010 | M8185D1006 | ||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M4185E4006 | M8185D1006 | Canada TRADELINE | |
M4185E4014 | M8185D1006 | Canada TRADELINE | |
M4186H1005 | M8185D1006 | M4185B1009 | Use auxiliary shaft |
M4186H4009 | M8185D1006 | Canada, use auxiliary shaft | |
M4186L4000 | M8185D1006 | ||
M6161A1004 | M6184D1035 | M6184A1015 | |
M6161B1002 | M6184D1035 | ||
M6174A1009 | M6184D1035 | Includes aux. switch cams | |
M6174D1003 | M6184D1035 | M6184D1035 | |
M6181A1000 | M6184D1035 | Less junction box | |
M6181A1018 | M6184D1035 | ||
M6181A1026 | M6184D1035 | M6184A1015 | |
M6181A1034 | M6184D1035 | M6184A1023 | |
M6181A1042 | M6184D1035 | ||
M6181A1059 | M6184D1035 | Carrier | |
M6181D1004 | M6184D1035 | M6184D1001 | |
M6181F1009 | M6184D1035 | M6184F1014 | |
M6181F1017 | M6184D1035 | M6184F1014 | Replacement requires |
198162AA | |||
M6182D1003 | Carrier | ||
M6182D1011 | |||
M6182F1008 | |||
M6182F1016 | With weatherproof kit | ||
M6184A1007 | M6184D1035 | ||
M6184A1015 | M6184D1035 | M6184A1015 | |
M6184A1023 | M6184D1035 | M6184A1023 | |
M6184A1031 | M6184D1035 | Carrier | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M6184A1049 | M6184D1035 | M6184A1023 | |
M6184A1056 | M6184D1035 | Trane | |
M6184B1005 | M6184D1035 | ||
M6184B1013 | M6184D1035 | Trane | |
M6184B1021 | M6184D1035 | M6184F1014 | |
M6184D1001 | M6184D1035 | M6184D1001 | |
M6184D1035 | M6184D1035 | M6184D1035 | TRADELINE |
M6184D1050 | M6184D1035 | M6184D1001 | |
M6184D1068 | M6184D1035 | M6184D1068 | |
M6184D1076 | M6184D1035 | Trane | |
M6184F1006 | M6184D1035 | M6184F1014 | |
M6184F1014 | M6184D1035 | M6184F1014 | |
M6185D1000 | |||
M6191A1008 | M6194D1017 | ||
M6191B1006 | M6194D1017 | M6194B1011 | |
M6191D1002 | M6194D1017 | M6194D1017 | |
M6191D1010 | M6194D1017 | York | |
M6194A1005 | M6194D1017 | ||
M6194A1021 | M6194D1017 | With aux. switch cams | |
M6194B1003 | M6194D1017 | M6194B1011 | |
M6194B1011 | M6194D1017 | M6194B1011 | |
M6194B1029 | M6194D1017 | M6194E1006 | Requires 198162EA |
M6194B1037 | M6194D1017 | Trane | |
M6194B1045 | M6194D1017 | M6194E1006 | Requires 198162EA |
M6194D1017 | M6194D1017 | M6194D1017 | TRADELINE |
M6194D1025 | M6194D1017 | Lennox | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M6194D1033 | M6194D1017 | York | |
M6194D1041 | M6194D1017 | Japan, includes 220741A | |
M6194D4003 | M6194D1017 | M6194D1017 | Canada TRADELINE |
M6194E1006 | M6194D1017 | M6194E1006 | |
M6194E1014 | M6194D1017 | M6194E1006 | Includes weatherproof kit |
+ 4074ERU | |||
M6194F1004 | M6194D1017 | ||
M6281A1009 | M6284D1000 | M6284A1048 | |
M6281F1008 | M6284D1000 | M6284F1013 | |
M6281F1016 | M6284D1000 | M6284F1013 | Requires 198162EA |
M6282A1008 | M6285A1005 | M6285A1005 | |
M6282A1016 | M6285A1013 | Trane | |
M6282A1024 | M6285A1013 | ||
M6282A1032 | M6285A1005 | ||
M6282B1006 | M6285A1013 | ||
M6282E1009 | Carrier | ||
M6284A1006 | M6284D1000 | M6284A1048 | |
M6284A1014 | M6284D1000 | M6284A1048 | |
M6284A1022 | M6284D1000 | M6284A1055 | |
M6284A1030 | M6284D1000 | Japan, includes 220741A | |
M6284A1048 | M6284D1000 | M6284A1048 | |
M6284A1055 | M6284D1000 | M6284A1055 | |
M6284A1063 | M6284D1000 | M6284A1048 | Includes 220741A |
+ 4074ERU | |||
M6284A1071 | M6284D1000 | M6284A1055 | |
M6284A1089 | M6284D1000 | ||
M6284A1097 | M6284D1000 | M6284A1055 | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M6284B1004 | M6294D1008 | Trane | |
M6284C1002 | M6284D1000 | M6284F1013 | |
M6284C1010 | M6284D1000 | Includes 220741A | |
M6284C1028 | M6284D1000 | Japan, includes 220741A | |
M6284C1036 | M6284D1000 | Includes weatherproof kit | |
M6284C1044 | M6284D1000 | ||
M6284D1000 | M6284D1000 | M6284D1000 | TRADELINE |
M6284D1026 | M6284D1000 | Includes 220741A | |
M6284D4004 | M6284D1000 | M6284D1000 | Canada TRADELINE |
M6284F1005 | M6284D1000 | M6284F1013 | |
M6284F1013 | M6284D1000 | M6284F1013 | |
M6284F1021 | M6284D1000 | M6284F1013 | Requires 198162EA |
M6284F1039 | M6284D1000 | M6284F1013 | Japan, includes 220741A |
M6284F1047 | M6284D1000 | M6284F1013 | Requires 198162EA |
M6284F1054 | M6284D1000 | ||
M6285A1005 | M6285A1005 | M6285A1005 | TRADELINE |
M6285A1013 | M6285A1013 | M6285A1013 | |
M6285A1021 | M6285A1013 | ||
M6285A1039 | Trane | ||
M6285A1047 | M6285A1005 | Japan, includes 220741A | |
M6285A1054 | M6285A1005 | Snyder General | |
M6285A4009 | M6285A1005 | M6285A1005 | Canada TRADELINE |
M6285B1003 | M6285A1013 | ||
M6285C1001 | M6285A1005 | M6285C1001 | |
M6286G1001 | M6285A1005 | M6285A1005 | Use auxiliary shaft |
M6286G1019 | M6285A1005 | ||
Request a Quote | |||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M6286G1027 | M6285A1005 | M6285A1005 | Japan, includes 220741A, |
+ 4074ERU | use auxiliary shaft | ||
M6294A1004 | M6294D1008 | ||
M6294B1002 | M6294D1008 | ||
M6294B1010 | M6294D1008 | ||
M6294B1028 | M6294D1008 | Trane | |
M6294B1036 | M6294D1008 | ||
M6294C1000 | M6294D1008 | Includes 220741A | |
M6294D1008 | M6294D1008 | M6294D1008 | |
M7161A1002 | M9164D1009 | ||
M7161B1000 | M9164D1009 | ||
M7161B1018 | M9164D1009 | Trane | |
M7161G1009 | M9164D1009 | M7164G1030 | |
M7161G1017 | M9164D1009 | ||
M7161G1025 | M9164D1009 | ||
M7164A1009 | M9164D1009 | ||
M7164A1017 | M9164D1009 | M7164A1017 | |
M7164A1025 | M9164D1009 | Lennox | |
M7164A1033 | M9164D1009 | ||
M7164A1041 | M9164D1009 | ||
M7164A1058 | M9164D1009 | M7164A1017 | |
M7164B1007 | M9164D1009 | ||
M7164G1006 | M9164D1009 | M7164G1030 | |
M7164G1014 | M9164D1009 | ||
M7164G1022 | M9164D1009 | ||
M7164G1030 | M9164D1009 | M7164G1030 | |
M7183G1003 | M9185D1004 | M7185A1004 | Use auxiliary shaft |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M7184A1005 | M9184D1013 | ||
M7184A1013 | |||
M7184A1021 | |||
M7185A1004 | M9185D1004 | M7185A1004 | |
M7186G1000 | M9185D1004 | M7185A1004 | Use auxiliary shaft |
M7261A1001 | M9164D1009 | Trane | |
M7272A1008 | M9175D1014 | ||
M7274A1006 | M9174D1007 | M7274A1006 | |
M7274G1003 | M9174D1007 | M7274A1006 | |
M7281A1007 | M9184D1013 | M7284A1004 | Includes 220741A |
M7281C1003 | M9184D1013 | M7284C1000 | |
M7281C1011 | M9184D1013 | M7284C1018 | |
M7281Q1002 | M9184D1013 | M7284Q1009 | Includes 203709D |
M7282A1006 | M9185D1004 | M7285A1003 | Includes 220741A |
M7282A1014 | M9185D1004 | Trane | |
M7282A1022 | Trane, with wiring harness | ||
M7282B1004 | M9185D1004 | Trane | |
M7282B1012 | M9185D1004 | ||
M7282C1002 | M9185D1004 | ||
M7282D1000 | Carrier, with 205118A | ||
M7282D1018 | |||
M7282F1005 | Carrier, 205118A and | ||
crank arm | |||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M7284A1004 | M9184D1013 | M7284A1004 | Includes 220741A |
M7284A1012 | M9184D1013 | M7284A1012 | |
M7284A1020 | M9184D1013 | M7284A1012 | |
M7284A1038 | M9184D1013 | M7284A1038 | |
M7284A1046 | M9184D1013 | M7284A1004 | |
M7284A1053 | M9184D1013 | Trane | |
M7284A1061 | M9184D1013 | ||
M7284A1079 | M9184D1013 | M7284A1079 | |
M7284A1087 | M9184D1013 | Trane | |
M7284C1000 | M9184D1013 | M7284C1000 | Includes 220741A |
M7284C1018 | M9184D1013 | M7284C1018 | |
M7284C1026 | M9184D1013 | M7284C1000 | |
M7284C1034 | M9184D1013 | M7284C1018 | |
M7284C1042 | International, incl.220741A | ||
M7284C1059 | M7284C1059 | Enhanced | |
M7284C1067 | M7284C1067 | ||
M7284G1001 | M9184D1013 | M7284A1079, | |
use aux shaft | |||
M7284Q1009 | M9184D1013 | M7284Q1009 | Includes 203709D |
M7284Q1017 | M9184D1013 | M7284Q1017 | |
M7284Q1025 | International, incl.203709D | ||
M7284Q1033 | M7284Q1033 | Enhanced | |
M7284Q1041 | M7284Q1041 | ||
M7285A1003 | M9185D1004 | M7285A1003 | Includes 220741A |
M7285A1011 | M9185D1004 | M7285A1011 | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M7285A1029 | M9185D1004 | ||
M7285A1037 | M9185D1004 | ||
M7285A1045 | M9185D1004 | M7285A1045 | |
M7285A1052 | M9185D1004 | ||
M7285B1001 | M9185D1004 | Trane | |
M7285C1009 | M9185D1004 | M7285C1009 | Includes 220741A |
M7285C1017 | M9185D1004 | M7285C1017 | |
M7285C1025 | M9185D1004 | ||
M7285C1033 | M9185D1004 | ||
M7285Q1008 | M9185D1004 | M7285Q1008 | Includes 203709D |
M7285Q1016 | M9185D1004 | M7285Q1016 | |
M7286G1009 | M9185D1004 | M7285A1045, | |
use aux shaft | |||
M7294A1002 | M9194D1003 | M7294Q1007 | Includes 220741A |
M7294A1010 | M9194D1003 | M7294A1010 | |
M7294G1009 | M9194D1003 | M7294A1010, | |
use aux shaft | |||
M7294Q1007 | M9194D1003 | M7294Q1007 | Includes 203709D |
M7361A1000 | M9164D1009 | ||
M7361A1018 | Liebert, with 203709B | ||
M7364A1007 | M9164D1009 | ||
M7364A1015 | M9164D1009 | ||
M7364A1023 | M9164D1009 | ||
M7364A1031 | Liebert | ||
M7381A1006 | Liebert, with 203709B | ||
board | |||
M7382A1005 | Liebert | ||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M7384A1003 | M9184D1013 | ||
M7384A1011 | M9184D1013 | ||
M7384A1029 | Liebert | ||
M7385A1002 | M9185D1004 | ||
M7385A1010 | M9185D1004 | Includes isolation | |
transformer | |||
M7385A1028 | M9185D1004 | ||
M7385A1036 | M9185D1004 | ||
M7385A1044 | Liebert | ||
M7484A1002 | Cleaver Brooks | ||
M7484A1010 | M7484A1010 | ||
M7675A1001 | M9175D1014 | ||
M7675A1019 | M9175D1014 | Trane | |
M7675G1008 | M9175D1014 | ||
M7682A1010 | Includes Q209F1001 | ||
M7685A1009 | M9185D1004 | ||
M7685A1017 | M9185D1004 | ||
M7685A1025 | M9185D1004 | ||
M7685A1033 | M9185D1004 | York | |
M7685A1041 | M9185D1004 | Lennox | |
M7685G1006 | M9185D1004 | ||
M7964A1001 | M7964A1001 | ||
M7964B1009 | M7964B1009 | Nesbitt ITT | |
M7964B1017 | M7964B1017 | ||
M7964C1007 | M7964C1007 | ||
Request a Quote | |||
M7964C1015 | M7964C1015 | ||
M7964D1005 | |||
M7964D1013 | |||
M7975E1009 | |||
M7975E1017 | |||
M7983G1005 | IBM | ||
M7984D1001 | Includes 220741A | ||
M7984N1008 | |||
M7985D1000 | |||
M8175B1002 | |||
M8182A1005 | M8185A1002 | ||
M8182B1003 | |||
M8182B1011 | Includes weatherproof kit | ||
M8185A1002 | M8185A1002 | ||
M8185A1010 | M8185A1010 | ||
M8185A1028 | |||
M8185B1000 | |||
M8185B1018 | M8185A1010 | ||
M8185B1026 | |||
M8185B1034 | |||
M8185D1006 | M8185D1006 | TRADELINE | |
M8186G1008 | Includes aux. switch cams, | ||
use aux. shaft | |||
M9161A1008 | M9164A1021 | ||
M9161A1016 | M9164A1021 | Wire to 24 Vac | |
M9161A1024 | M9164A1005 | ||
M9161A1032 | Carrier | ||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9161A1040 | M9164D1009 | M9164A1005 | Includes weatherproof kit |
+ 4074ERU | |||
M9161C1004 | M9164D1009 | M9164C1050 | Wire to 24 Vac |
M9161C1012 | M9164D1009 | M9164C1068 | |
M9161V1009 | M9164D1009 | Carrier | |
M9164A1005 | M9164D1009 | M9164A1005 | |
M9164A1013 | M9164D1009 | M9164A1013 | |
M9164A1021 | M9164D1009 | M9164A1021 | |
M9164A1039 | M9164D1009 | M9164A1021 | |
M9164A1047 | M9164D1009 | M9164A1088 | |
M9164A1054 | M9164D1009 | M9164A1005 | |
M9164A1062 | M9164D1009 | M9164A1005 | Wire to 24 Vac |
M9164A1070 | M9164D1009 | M9164A1021 | |
M9164A1088 | M9164D1009 | M9164A1088 | |
M9164A1096 | M9164D1009 | M9164A1021 | |
M9164A1104 | M9164D1009 | Carrier | |
M9164A1112 | M9164D1009 | York | |
M9164A1120 | M9164D1009 | M9164A1005 | Wire to 24 Vac |
M9164A1138 | M9164D1009 | Carrier | |
M9164B1003 | M9164D1009 | M9164C1068 | |
M9164C1001 | M9164D1009 | M9164C1050 | Wire to 24 Vac |
M9164C1019 | M9164D1009 | M9164C1050 | |
M9164C1027 | M9164D1009 | ||
M9164C1035 | M9164D1009 | M9164C1068 | |
M9164C1043 | M9164D1009 | M9164C1050 | |
M9164C1050 | M9164D1009 | M9164C1050 | |
M9164C1068 | M9164D1009 | M9164C1068 | |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9164D1009 | M9164D1009 | M9164D1009 | TRADELINE |
M9164V1006 | M9164D1009 | Carrier | |
M9164V1014 | M9164D1009 | ||
M9164V1022 | M9164D1009 | Carrier, with Q209E, crank | |
arm | |||
M9171A1006 | M9174D1007 | M9174B1043 | |
M9171B1004 | M9174D1007 | M9174B1043 | |
M9171B1012 | M9174D1007 | M9174B1027 | |
M9171B1020 | Cleaver Brooks | ||
M9171C1002 | M9174D1007 | M9174C1025 | |
M9171C1010 | Cleaver Brooks | ||
M9172A1005 | M9175D1014 | ||
M9172A1013 | M9175D1014 | ||
M9172A1021 | M9175D1014 | Carrier | |
M9172C1001 | M9175D1014 | Reznor | |
M9172W1004 | M9175D1014 | Trane, with Q209E1010 | |
M9172W1012 | M9175D1014 | Carrier | |
M9174B1001 | M9174D1007 | M9174B1043 | |
M9174B1019 | M9174D1007 | M9174B1027 | Requires 220738A |
M9174B1027 | M9174D1007 | M9174B1027 | |
M9174B1035 | Cleaver Brooks | ||
M9174B1043 | M9174D1007 | M9174B1043 | |
M9174C1009 | M9174D1007 | M9174C1033 | |
M9174C1017 | M9174D1007 | M9174C1025 | |
M9174C1025 | M9174D1007 | M9174C1025 | |
M9174C1033 | M9174D1007 | M9174C1033 | |
M9174C1041 | Cleaver Brooks | ||
Request a Quote | |||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9174D1007 | M9174D1007 | M9174D1007 | TRADELINE |
M9175A1002 | M9175D1014 | ||
M9175A1010 | M9175D1014 | Includes crank arm | |
M9175A1028 | M9175D1014 | ||
M9175A1036 | M9175D1014 | York | |
M9175A1044 | M9175D1014 | ||
M9175A1051 | M9175D1014 | ||
M9175A1069 | M9175D1014 | Carrier | |
M9175A1077 | M9175D1014 | Trane | |
M9175B1000 | M9175D1014 | ||
M9175C1008 | M9175D1014 | Reznor | |
M9175D1006 | M9175D1014 | M9175D1014 | Requires 198162EA |
M9175D1014 | M9175D1014 | M9175D1014 | TRADELINE |
M9175V1003 | M9175D1014 | Trane | |
M9175V1011 | Carrier, leadwires | ||
M9175W1001 | M9175D1014 | Carrier | |
M9175W1019 | M9175D1014 | Trane | |
M9175Y1007 | M9175D1014 | ||
M9181A1004 | M9184D1013 | M9184A1019 | Less junction box |
M9181A1012 | M9184D1013 | M9184A1019 | |
M9181A1020 | M9184D1013 | M9184A1019 | |
M9181A1038 | M9184D1013 | M9184A1035 | |
M9181B1002 | M9184D1013 | M9184C1031 | |
M9181B1010 | M9184D1013 | ||
M9181B1028 | Cleaver Brooks | ||
M9181C1000 | |||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9181D1008 | M9184D1013 | M9184D1005 | |
M9181D1016 | M9184D1013 | Trane | |
M9181D1024 | Special Timing | ||
M9182A1003 | M9185D1004 | M9185A1018 | Less junction box |
M9182A1011 | M9185D1004 | M9185A1018 | |
M9182A1029 | M9185D1004 | M9185A1026 | |
M9182A1037 | M9185D1004 | Trane | |
M9182A1045 | M9185D1004 | M9185A1018 | |
M9182A1052 | M9185D1004 | M9185A1018 | Includes weatherproof kit |
+ 4074ERU | |||
M9182A1060 | M9185D1004 | York | |
M9182C1009 | M9185D1004 | M9185C1006 | |
M9182C1017 | M9185D1004 | ||
M9182D1007 | M9185D1004 | M9185D1004 | Less junction box |
M9182D1015 | M9185D1004 | M9185D1004 | |
M9182D1023 | Special Timing | ||
M9182D1031 | M9185D1004 | Includes Q209E | |
M9182D4001 | M9185D1004 | M9185D1004 | Canada |
M9182W1002 | M9185D1004 | Trane, includes Q209E | |
M9183G1009 | M9185D1004 | M9186G1006 | Use auxiliary shaft |
M9184A1001 | M9184D1013 | M9184A1019 | |
M9184A1019 | M9184D1013 | M9184A1019 | |
M9184A1027 | M9184D1013 | M9184A1035 | |
M9184A1035 | M9184D1013 | M9184A1035 | |
M9184A1043 | M9184D1013 | M9184A1019 | Japan; replacement |
requires 220741A | |||
M9184B1009 | Cleaver Brooks | ||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9184B1017 | M9184D1013 | M9184C1031 | |
M9184B1025 | Cleaver Brooks | ||
M9184B1033 | M9184D1021 | M9184F1000 | With tapped shaft |
M9184B1041 | M9184D1013 | M9184C1031 | Includes weatherproof kit |
M9184C1007 | M9184D1021 | M9184C1031 | With tapped shaft |
M9184C1015 | M9184D1021 | ||
M9184C1023 | Cleaver Brooks | ||
M9184C1031 | M9184D1021 | M9184C1031 | With tapped shaft |
M9184C1049 | Cleaver Brooks | ||
M9184D1005 | M9184D1013 | M9184D1005 | |
M9184D1013 | M9184D1013 | M9184D1013 | TRADELINE |
M9184D1021 | M9184D1021 | M9184D1021 | TRADELINE, with tapped |
shaft | |||
M9184D1039 | M9184D1013 | M9184D1005 | Japan; replacement |
requires 220741A | |||
M9184D1047 | M9184D1013 | M9184D1005 | |
M9184D1054 | M9194D1003 | M9194D1003 | |
M9184D1062 | M9184D1021 | M9184D1021 | |
M9184D4009 | M9184D1013 | M9184D1013 | Canada, TRADELINE |
M9184E4006 | M9184D1021 | Canada, TRADELINE, | |
tapped shaft | |||
M9184F1000 | M9184D1013 | M9184F1000 | |
M9184F1018 | M9184D1021 | M9184F1034 | With tapped shaft |
M9184F1026 | M9184D1013 | M9184F1000 | Requires 220741A |
M9184F1034 | M9184D1021 | M9184F1034 | With tapped shaft |
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9185A1000 | M9185D1004 | M9185A1018 | |
M9185A1018 | M9185D1004 | M9185A1018 | |
M9185A1026 | M9185D1004 | M9185A1026 | |
M9185A1034 | M9185D1004 | M9185A1018 | |
M9185A1042 | M9185D1004 | M9185A1026 | Requires 198162EA |
M9185A1059 | M9185D1004 | Lennox | |
M9185A1067 | M9185D1004 | York | |
M9185A1075 | M9185D1004 | M9185A1018 | Requires 220741A |
M9185A1083 | M9185D1004 | M9185A1018 | |
M9185A1091 | M9185D1004 | M9185A1026 | Less junction box |
M9185B1008 | M9185D1004 | ||
M9185C1006 | M9185D1004 | M9185C1006 | |
M9185C1014 | M9185D1004 | ||
M9185C1022 | M9185D1004 | ||
M9185D1004 | M9185D1004 | M9185D1004 | TRADELINE |
M9185D1012 | M9185D1004 | M9185D1004 | |
M9185D4008 | M9185D1004 | M9185D1004 | Canada, TRADELINE |
M9185E1001 | M9185D1004 | M9185E1019 | |
M9185E1019 | M9185D1004 | M9185E1019 | |
M9185E4005 | M9185D1004 | M9185D1004 | Canada, TRADELINE, |
tapped shaft | |||
M9185F1009 | Carrier (W957G1006) | ||
M9185W1017 | M9185D1004 | Trane, with Q209E | |
M9186G1006 | M9185D1004 | M9186G1006 | Use auxiliary shaft |
M9186G1014 | M9185D1004 | M9186G1006 | Japan, use auxiliary shaft |
M9186G4000 | M9185D1004 | M9186G1006 | Canada, use auxiliary shaft |
Request a Quote | |||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9191D1006 | M9194D1003 | M9194D1003 | |
M9191F1001 | M9194D1003 | ||
M9194C1005 | M9194D1003 | ||
M9194D1003 | M9194D1003 | M9194D1003 | TRADELINE |
M9194D4007 | M9194D1003 | M9194D1003 | Canada, TRADELINE |
M9194E1000 | M9194D1003 | M9194E1000 | |
M9481D1005 | M9484D1010 | ||
M9481E1002 | M9484E1017 | ||
M9481F1000 | M9484F1007 | ||
M9484D1002 | M9484D1002 | ||
M9484D1010 | M9484D1010 | With tapped shaft | |
M9484D1028 | M9484D1010 | ||
M9484D1036 | M9484D1002 | ||
M9484D1044 | M9484D1010 | With tapped shaft | |
M9484D1051 | M9484D1010 | ||
M9484D4006 | M9484D1010 | Canada, tapped shaft, | |
220741A | |||
M9484E1009 | M9484E1009 | With tapped shaft | |
M9484E1017 | M9484E1017 | ||
M9484E1025 | M9484E1033 | ||
M9484E1033 | M9484E1033 | ||
M9484E1041 | M9484E1033 | With 221455A | |
M9484E1058 | M9484E1033 | ||
M9484E1066 | M9484E1033 | ||
M9484E1074 | M9484E1033 | ||
OS # to be | Modutrol IV TRADELINE Replacement Specifications | Functional Replacement | TRADELINE |
Replaced | Model Number | Comments | |
M9484E1082 | M9484E1033 | With tapped shaft | |
M9484E1090 | M9484E1017 | ||
M9484E1116 | M9484E1009 | ||
M9484E4003 | M9484E1017 | Canada, tapped shaft, | |
220741A | |||
M9484F1007 | M9484F1007 | ||
M9484F1015 | M9484F1007 | ||
M9484F1023 | M9484F1023 | With tapped shaft | |
M9484F1031 | M9484F1031 | ||
M9484F1049 | M9484F1049 | ||
M9484F1056 | M9484F1023 | With tapped shaft | |
M9484F1064 | M9484F1031 | ||
M9484F1072 | M9484F1007 | ||
M9484F4001 | M9484F1007 | Canada, tapped shaft, | |
M9484F4019 | M9484F1023 | 220741A | |
M9491D1003 | M9494D1000 | ||
M9494D1000 | M9494D1000 |
Accessory | For Use With | Description | Works | Mod IV Equivalent | |
Part Number | with Mod | ||||
III | IV | ||||
27,518 | 5/16 inch Rod | Ball Joint | Yes | Yes | 27,518 |
101662A | Series 90 Mod Motors | Bracket, external damper mount | Yes | Yes | 101662A |
104643A | Drive two dampers from one crank arm | Crank Arm Adapter | Yes | Yes | 220767A |
112894FB | Series 90 Motor | Remote Manual Potentiometer, 270 ohm | Yes | Yes | 112894FB |
112894FD | Series 90 Motor | Remote Manual Potentiometer, 135 ohm | Yes | Yes | 112894FD |
112894FE | Series 90 Motor | Remote Manual Potentiometer, 270 ohm, with | Yes | Yes | 112894FE |
wallplate | |||||
112894GB | Series 90 Motor | Remote Manual Potentiometer, 72 ohm | Yes | Yes | 112894FE |
198162AA | Mod IV Motors | Internal Transformer, 120/208/240 Vac, 50/60 Hz | No | Yes | 198162AA |
198162EA | Mod IV Motors | Internal Transformer, 120 Vac, 50/60 Hz | No | Yes | 198162EA |
198162GA | Mod IV Motors | Internal Transformer, 220 Vac, 50/60 Hz | No | Yes | 198162GA |
198162JA | Mod IV Motors | Internal Transformer, 24 Vac, 50/60 Hz, Isolation | No | Yes | 198162JA |
220736A | Mod IV Tradeline Motors | Auxiliary Switch Kit, 1 Switch | No | Yes | 220736A |
220736B | Mod IV Tradeline Motors | Auxiliary Switch Kit, 2 Switches | No | Yes | 220736B |
203977A | Mod IV Motors with W859 Economizer | Economizer Adapter Kit | No | Yes | 203977A |
220738A | Mod IV Motors to match Mod III shaft height | Adapter Bracket | No | Yes | 220738A |
220741A | Mod IV Motors | Screw Terminal Adapter | No | Yes | 220741A |
221455A | Dampers, Mod IV Motors | Infinitely Adjustable Crank Arm | Yes | Yes | 221455A |
221508A | With 4074BYK, 4074EAU, 4074EDC, 4074EED | Resistor Board | No | Yes | 221508A |
34343A | Dampers, Valves | Connecting Rod | Yes | Yes | 34343A |
4074BYK | 2-6 Series 90 in Unison | Resistor Kit – Series 90 | Yes | Yes | 221508A |
4074EAU | 2-3 Series 90 from W973 | Resistor Kit – W973 | Yes | Yes | 221508A |
4074EDC | 1 Series 90 from 4 to 20 mA Controller | Resistor Kit – 4 to 20 mA | Yes | Yes | 221508A |
4074EED | 1 to 4 Series 90 from 4 to 20 mA Controller | Resistor Kit – 4 to 20 mA | Yes | Yes | 221508A |
4074ELR | Dampers, 300 lb-in Mod III Motors | Heavy Duty Crank Arm | Yes | Yes | 4074EQE |
4074ELY | Dampers, Mod III Motors | Infinitely Adjustable Crank Arm | Yes | Yes | 221455A |
4074ERU | Mod IV Motors | Weatherproof Kit | No | Yes | 4074ERU |
4074EQE | Dampers, 300 lb-in Mod IV Motors | Heavy Duty Crank Arm | Yes | Yes | 4074EQE |
Accessory | For Use With | Description | Works | Mod IV Equivalent | |
Part Number | with Mod | ||||
III | IV | ||||
4074EUB | W859F | Economizer Weatherproof Kit | No | Yes | 4074EUB |
7616BR | Dampers, Mod IV Motors | Adjustable Crank Arm | Yes | Yes | 7617ADW |
7617ADW | Dampers, Mod IV Motors | Adjustable Crank Arm | Yes | Yes | 7617ADW |
7617DM | Explosion Proof Housings | Coupling | Yes | Yes | 7617DM |
7640QY | Mod Motors | Bracket, DR/ZR valve to Mod Motor | Yes | Yes | 7640QY |
ES-650-117 | Dampers, Mod IV Motors | Explosion Proof Housing Nelson Electric | Yes | Yes | ES-650-117 |
ES-650-118 | Dampers, Mod IV Motors | Explosion Proof Housing Nelson Electric | Yes | Yes | ES-650-118 |
Q100A1007 | V51B Valves 1-1/2 to 2 inch | Valve Linkage | Yes | Yes | Q100A1007 |
Q100A1015 | V51B Valves 2-1/2 to 3 inch | Valve Linkage | Yes | Yes | Q100A1015 |
Q100A1023 | V51B Valves 4 inch | Valve Linkage | Yes | Yes | Q100A1023 |
Q181A1007 | Series 90 motors, includes cover | Auxiliary Potentiometer (1 Potentiometer) | Yes | Yes | Q181A1007 |
Q181A1015 | Series 90 motors, includes cover | Auxiliary Potentiometer (2 Potentiometer) | Yes | Yes | Q181A1015 |
Q181A1064 | Series 90 motors, does not include cover | Auxiliary Potentiometer (3 Potentiometer) | Yes | Yes | Q181A1064 |
Q181A1072 | Series 90 motors, does not include cover | Auxiliary Potentiometer (4 Potentiometer) | Yes | Yes | Q181A1072 |
Q209E1002 | Series 70 and 90 Mod IV Motors | Cover Mounted Minimum Position Pot 135 ohm | No | Yes | Q209E1002 |
Q209E1010 | Series 70 and 90 Mod IV Motors | Cover Mounted Minimum Position Pot 270 ohm | No | Yes | Q209E1010 |
Q209F1001 | Series 70 and 90 Mod IV Motors | Internal Minimum Position Pot 135 ohm | No | Yes | Q209F1001 |
Q209F1019 | Series 70 and 90 Mod IV Motors | Internal Minimum Position Pot 270 ohm | No | Yes | Q209F1019 |
Q5001A1006 | Valve Linkage, 80 lb, 3/4 in. lift, 1-3/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001A1006 |
Q5001A1014 | Valve Linkage, 160 lb, 3/4 in. lift, 1-3/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001A1014 |
Q5001A1022 | Valve Linkage, 320 lb, 3/4 in. lift, 1-3/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001A1022 |
Q5001B1004 | Valve Linkage, 160 lb, 1-1/2 in. lift, 1-7/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001B1004 |
Q5001B1012 | Valve Linkage, 320 lb, 1-1/2 in. lift, 1-7/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001B1012 |
Q5001D1000 | Valve Linkage, 80/160 lb, 3/4 in. lift, 1-3/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001D1000 |
Q5001D1018 | Valve Linkage, 160/320 lb, 3/4 in. lift, 1-3/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001D1018 |
Q5001D1026 | Valve Linkage, 160/320 lb, 3/4 in. lift, 1-7/8 in. bonnet | V5011, V5013 Valves | Yes | Yes | Q5001D1026 |
Q68B1005 | Auxiliary Potentiometer 86.0 ohm | Series 90 Motors | Yes | Yes | Q68B1005 |
Q68B1013 | Auxiliary Potentiometer 58.0 ohm | Series 90 Motors | Yes | Yes | Q68B1013 |
Accessory | For Use With | Description | Works | Mod IV Equivalent | |
Part Number | with Mod | ||||
III | IV | ||||
Q68B1039 | Auxiliary Potentiometer 34.5 ohm | Series 90 Motors | Yes | Yes | Q68B1039 |
Q7130A1006 | Interface Module 4-7, 6-9, 10.5-13.5 Vdc | Series 90 Motors | No | Yes | Q7130A1006 |
Q7230A1005 | Interface Module 4-20 mA or 2-10 Vdc | Series 90 Motors | No | Yes | Q7230A1005 |
Q7330A1004 | Interface Module W936 Control Interface | Series 90 Motors | No | Yes | Q7330A1004 |
Q7630A1001 | Interface Module 14-17 Vdc with Min Position | Series 90 Motors | No | Yes | Q7630A1001 |
S443A1007 | Manual Potentiometer 135 ohm | Remote mount Series 90 motor manual control | Yes | Yes | S443A1007 |
S963B1128 | External Minimum Position Potentiometer 135 ohm | Series 90 Motors | Yes | Yes | S963B1128 |
S963B1136 | External Minimum Position Potentiometer 270 ohm | Series 90 Motors | Yes | Yes | S963B1136 |
W859 | Economizer Control | Series 90 Mod III | Yes | Yes | W9157 |
W9157 | Economizer Control | Series 90 Mod IV | No | Yes | W9157 |