Search

Honeywell M9484F4001 Modutrol IV Motor, Non-Spring Return

Description

Series 90 Modutrol IV motors are non-spring return modulating proportional control motors designed for use with controllers that provide a Series 90 output, enabling the operation of dampers or valves.

Features

Integral junction box provides NEMA 3 weather protection.
Integral spring return returns motor to normal position when power is interrupted.
Motor and circuitry operate from 24 Vac. Models available with factory installed transformer, or a field added internal transformer.
Quick-connect terminals are standard-screw terminal adapter is available.
Adapter bracket for matching shaft height of older motors is available.
Motors have field adjustable stroke (90° to 160°).
Die-cast aluminum housing.
Integral auxiliary switches are available factory mounted, or can be field added.
Nominal timing standard of 30 seconds (90° stroke), and 60 seconds (160° stroke). Other timings available.
Spring return motors can operate valve linkages form power end or auxiliary end shafts for normally closed or normally open valve applications.
All models have dual shafts (slotted and tapped on both ends).
All models have auxiliary switch cams.
Fixed torque throughout the entire voltage range.
Motors are designed for either normally open or normally closed valves and dampers.
Field addable interface modules can be mounted in the junction box to upgrade the motor to Series 70 (electronic) control.

Specifications

Application Type: Electric
Fail Safe Mode: Non-Spring Return
Control Signal: Proportional, 135 ohm
Feedback: no
Motor Shaft: Dual ended Shaft
Stroke: Adjustable; 90 to 160 degrees, Asymmetrical
Torque Rating (lb-in.): 60 lb-in
External Auxiliary Switches Available: Yes
Frequency: 50 Hz, 60 Hz
Power Consumption Driving (VA): 20 VA
Electrical Connections: Quick Connect Terminals
Shaft Dimensions (in.): .375 in
Shaft Shape: Square
Mounting: foot-mounted
Dimensions: 6 7/16 in. high x 5 1/2 in. wide x 8 3/4 in. deep
Temperature Range: -40 to 150F
Deadweight Load on Shaft (Either End) (lb): 200 lbs
Deadweight Load on Shaft (Combined on both shafts) (lb): 300 lbs
Nominal Timing (sec): 30 -60 sec
Shaft Rotation (upon control signal increase): Counter-clockwise (as viewed from power end) (normally open)
Auxiliary Switch Ratings AFL – 120 Vac: 7.2A
Auxiliary Switch Ratings AFL – 240 Vac: 3.6A
Auxiliary Switch Ratings ALR- 120 Vac: 43.2A
Auxiliary Switch Ratings ALR- 240 Vac: 21.6A

Specs

Fail Safe Mode:

Non-Spring Return

Control Signal:

Proportional

Voltage:

24v

Torque:

150 lb-in

Internal Aux Switch:

2

 

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Specificationsheet.pdf

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

Full Product Catalog