The Series 72 Modutrol IV Motors spring return and non-spring return motors are used to control dampers and valves. The motors accept a current or voltage signal from an electronic controller to position a damper or valve at any point between open and closed.
Features
Integral junction box provides NEMA 3 weather protection if motor is mounted in the upright position.
Motor and circuitry operate from 24 Vac.
Quick-connect terminals are standard–screw terminal adapter is available.
Adapter bracket for matching shaft height of older motors is available.
Motors have field adjustable stroke (90 to 160 degrees).
Integral auxiliary switches are available factory mounted, or can be field added.
Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications.
All models have dual shafts (slotted and tapped on both ends).
All models have auxiliary switch cams.
Fixed torque throughout the entire voltage range.
Motors are designed for either normally open or normally closed valves and dampers.
Models available with adjustable start (zero) and span.
Models available with 4 to 20 mA input signal.
Models available with 2 to 10 Vdc input signal.
Die-cast aluminum housing.
Specifications
Application Type: Electric
Fail Safe Mode: Non-Spring Return
Control Signal: Modulating, 4-20 mA
Motor Shaft: Dual ended Shaft
Stroke: Adjustable; 90 to 160 degrees, symmetrical
External Auxiliary Switches Available: Yes
Frequency: 50 Hz, 60 Hz
Power Consumption Driving (VA): 15 VA
Shaft Dimensions (in.): .375 in
Shaft Shape: Square
Mounting: foot-mounted
Dimensions: 6 7/16 in. high x 5 1/2 in. wide x 8 3/4 in. deep
Temperature Range: -40 to 150F
Deadweight Load on Shaft (Either End) (lb): 200 lbs
Deadweight Load on Shaft (Combined on both shafts) (lb): 300 lbs
Auxiliary Switch Ratings AFL – 120 Vac: 7.2A
Auxiliary Switch Ratings AFL – 240 Vac: 3.6A
Auxiliary Switch Ratings ALR- 120 Vac: 43.2A
Auxiliary Switch Ratings ALR- 240 Vac: 21.6A
Specs
Torque: |
150 lb-in |
---|---|
Fail Safe Mode: |
Non-Spring Return |
Voltage: |
120v |
Control Signal: |
Proportional 4 to 20 mA |
Internal Aux Switch: |
0 |
Timing: |
30-60 Seconds |
Temperature Range: |
-40° to 150°F |
Mount: |
Foot |
Feedback: |
No |
Features: |
2 Motor Shafts |
Wiring: |
Screw Terminals |
Request a Quote now or call us at 1-800-755-2883 for expert assistance.