The Allen Bradley 22-COMM-P is a PROFIBUS communication adapter designed for seamless integration between PowerFlex 4-Class drives and PROFIBUS DP networks. This adapter facilitates efficient and reliable data exchange in industrial automation environments, supporting both Single and Multi-Drive modes of operation.
Technical Specifications
- Model: 22-COMM-P
- Type: PROFIBUS Communication Adapter
- Compatible Drives: PowerFlex 4, PowerFlex 4M, PowerFlex 40, PowerFlex 40P, PowerFlex 400
- Mounting: Internal Mount or via DSI External Comms Kit (22-XCOMM-DC-BASE)
- Power Supply: 5V DC (supplied by the drive)
- Current Draw: 370 mA
- Communication Ports:
- PROFIBUS Connector: 9-pin, female D-Sub
- DSI Connector: 20-pin, single-row shrouded male header
- Data Transfer Rates: 9.6 kbps to 12 Mbps (auto baud rate detection)
- Operating Temperature: -10°C to 50°C (14°F to 122°F)
- Storage Temperature: -40°C to 85°C (-40°F to 185°F)
- Relative Humidity: 5% to 95% (non-condensing)
- Manufacturer: Rockwell Automation
Key Features
- Supports both Single and Multi-Drive modes (up to 5 drives in Multi-Drive mode)
- Auto baud rate detection for seamless network integration
- Three LED indicators for module, network, and communication status
- Node address configuration via DIP switches (SW1–SW7)
- Mode selection jumper (J2) for Single or Multi-Drive operation
- SWAP jumper (J3) to select data format (Intel or Motorola)
- User-defined fault actions for communication disruptions and idle conditions
- Compatible with configuration tools such as DriveExplorer and DriveTools SP
Compatible Components & Accessories
- Allen Bradley PowerFlex 4-Class drives
- DSI External Comms Kit (22-XCOMM-DC-BASE)
- Configuration software: DriveExplorer, DriveTools SP
- PROFIBUS cables and connectors
Industry Applications
- Factory automation systems
- Process control applications
- Material handling systems
- Packaging machinery
- Water and wastewater treatment facilities
Installation & Maintenance Notes
- Ensure proper installation within the drive or DSI External Comms Kit
- Set the operating mode jumper (J2) to select between Single or Multi-Drive mode
- Configure node address switches (SW1–SW7) for unique PROFIBUS node identification
- Use appropriate configuration tools for parameter setup and diagnostics
- Refer to the user manual for detailed installation and maintenance guidelines
Request a Quote now or call us at 1-800-755-2883 for expert assistance.