The Allen-Bradley 1792D-8BVT8D ArmorBlock MaXum is a rugged, stand-alone 24V DC I/O module designed for seamless communication over a DeviceNet network. Housed in a sealed IP67-rated enclosure, it offers eight inputs and eight outputs, making it ideal for on-machine applications in harsh industrial environments.

Technical Specifications

  • Model: 1792D-8BVT8D
  • Series: ArmorBlock MaXum
  • Product Type: DeviceNet I/O Module
  • Input Channels: 8 (24V DC, automatically configured for PNP or NPN devices)
  • Output Channels: 8 (self-protected 24V DC, sourcing, 0.5 A per output)
  • Communication Protocol: DeviceNet
  • Enclosure Rating: IP67 (requires no additional enclosure)
  • Mounting: Direct machine mounting via compatible cable base (e.g., 1792D-CBFM, 1792D-CB12)
  • Diagnostics: Short circuit, open wire, and no load detection reported to the point level
  • Local Logic Control: Integrated DeviceLogix™ technology for local control and diagnostics
  • Operating Temperature: -25°C to +60°C (-13°F to +140°F)
  • Certifications: CE marked, compliant with EMC and Low Voltage Directives

Key Features

  • Rugged Design: IP67-rated sealed housing suitable for harsh industrial environments without the need for additional enclosures.
  • Flexible Input Configuration: Inputs automatically configure for PNP (sourcing) or NPN (sinking) devices, simplifying integration.
  • Self-Protected Outputs: Each of the eight outputs is self-protected and can source up to 0.5 A, ensuring reliable operation.
  • Advanced Diagnostics: Provides point-level diagnostics including short circuit, open wire, and no load detection for efficient troubleshooting.
  • Integrated Local Logic: DeviceLogix™ technology allows for local control and diagnostics, enhancing system responsiveness and reducing network traffic.

Compatible Accessories

  • Cable Bases: 1792D-CBFM (KwikLink flat media installation), 1792D-CB12 (12mm drop cable installation), 1792D-CB18P (round media DeviceNet and output power)
  • Cord Sets: Standard M12 (micro) style connectors for I/O connections; M12 or Mini style connectors for network and auxiliary power connections
  • Termination Resistors: Required for DeviceNet network integrity

Industry Applications

  • Automotive Manufacturing: On-machine control for assembly lines and robotic systems.
  • Food and Beverage Processing: Suitable for washdown environments requiring IP67 protection.
  • Material Handling: Conveyor systems and packaging machinery.
  • Pharmaceuticals: Process control in cleanroom environments.

Installation & Maintenance Notes

  • Node Addressing: Set the node address using the rotary switches located on the underside of the module. Valid addresses range from 00 to 63. Settings between 64 and 99 allow software control of the address.
  • Mounting: Attach the module to a compatible cable base, ensuring proper alignment of the captive screws to complete the connections between the module and base contacts.
  • Wiring: Utilize appropriate cord sets with M12 connectors for I/O devices and ensure secure connections to maintain IP67 rating.
  • Diagnostics Monitoring: Regularly monitor the module’s diagnostic indicators for input/output status, network status, and auxiliary power status to ensure optimal performance.

 

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

TCI Supply is not an authorized Allen Bradley Distributor

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!