The Allen Bradley 1756-OC8 module is a ControlLogix DC output module that has 8 points available, with 4 points in a group. It is a module that has not been fused so it is recommended to use a fused IFM to protect the outputs. The recommended fuse for the 1756-OC8 module is the 5x20mm 4A quick acting fuse supplied by the SOC p/n MQ2-4A. Note that the chassis and power supply must be installed and grounded first before installing the module into any available slot in the chassis. Also, a removable terminal block housing, or RTB, must be connected to the module when installing it to the chassis. For the 1756-OC8 module, the compatible 20-pin RTBs are the 1756-TBNH and the 1756-TBSH.
It is a 48V DC source module with a 30 to 60V DC operating voltage range. It has a pilot duty of 2 A and a minimum load current of 2 mA. The module also has a current draw of 165 mA at 5.1V and 2 mA at 24V with a total backplane power of 0.89 W. Its surge current is 4 A for 10 ms per point that is repeatable every second at 60 Degrees Celsius. The maximum current per module is 8 A at 60 Degrees Celsius, while the maximum current per point is 2 A at 60 Degrees Celsius. It has a maximum off-state leakage current of 1 mA per point and a maximum on-state voltage drop of 2V DC at 2 A.
The module has a maximum output delay time of 1 ms from off to on and 2 ms from on to off. It has a thermal dissipation of 16.71 BTU/hr and a maximum power dissipation of 4.9W at 60 Degrees Celsius.
The 1756-OC8 module has the following communication formats available: rack optimization, scheduled output data, output data, listen-only rack optimization, and listen-only output data. You can also choose the states in Fault or Program mode per point with this module. Options available are On, Off, and Hold Last State, with Off as the default state.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
TCI Supply is not an authorized Allen Bradley Distributor
Manufacturer | Rockwell Automation |
Brand | Allen Bradley |
Part Number/Catalog No. | 1756-OC8 |
Series | ControlLogix |
Module Type | DC Output Module |
Outputs | 8-Point |
Voltage | 48 Volts DC Source |
Operating Voltage Range | 30-60 Volts DC |
Maximum Output Current Rating-Point | 2 Amps at 60 Celsius |
Maximum Output Current Rating-Module | 8 Amps at 60 Celsius |
Power Dissipation (Max) | 4.9 Watts at 60 Celsius |
Removeable Terminal Block(s) | 1756-TBNH, 1756-TBSH |
Isolation Voltage | 50 Volts Continuous |
Enclosure | None |