The Allen Bradley 1756-IR6I is a temperature-measuring analog module. This is an analog module that is used with Resistance-Temperature Detectors (RTD) sensors.

The 1756-IR6I module provides two data formats such as integer mode and the floating-point mode. When choosing the integer mode, the integrated features are multiple input ranges, notch filter, and real-time sampling. The floating mode includes all these features with the addition of temperature linearization, process alarms, rate alarms, and digital filtering. It also has selectable temperature unit to such as Celsius or Fahrenheit. These ranges designate the minimum and maximum signals detectable by the module. It has Six (6) individually isolated RTD inputs and a resolution of 16 bits. The module’s notch filter line noise filtering. Make sure to choose the filter that closely matches the application’s anticipated noise frequency. The digital filter smoothens data by eliminating noise transients on each input channel.

The 1756-IR6I’s real-time sampling feature lets the module multicast data it gathered from scanning all of its input channels. To enable multicast, configure Real-Time Sampling (RTS) period and a Requested Packet Interval (RPI) period.

Protection features are also embedded with this module such as under-range/over-range detection, feature of the module which is used to monitor if the input signal falls beyond the limits set by the input range. The process alarms work similarly however the process limits are manually set by the user. The integrated rate alarm allows the module to detect a rapid increase or decrease within a short defined period of time. Rate alarm is only available in applications using floating point. Wire off detection feature provide loop wiring completeness. It can detect if the RTB or a wire in the module has been disconnected.

Small offset errors in a 10-ohm copper RTD can be compensated with the 10 ohms offset feature of the module. Sensor types can also be configured for each channel in the module. This linearizes the analog signal into a temperature value.

The Allen Bradley 1756-IR6I is an ControlLogix module that is used to receive signals from Resistance Temperature Detectors (RTD). This module belongs to the analog input category and especially used for Temperature measurement applications.

 

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

TCI Supply is not an authorized Allen Bradley Distributor

Specification Sheet .pdf

 

Manufacturer Rockwell Automation
Brand Allen Bradley
Part Number/Catalog No. 1756-IR6I
Series ControlLogix
Module Type Analog RTD Module
Inputs 6-Point Isolated RTD
Module Scan Time 25 ms min floating point (ohms) 50 ms min floating point (temperature) 10 ms min integer (ohms)(1)
Maximum Input Current, Off-State 2.75 milliamperes
Data Format Integer mode (left justified, 2s complement) IEEE 32-bit floating point
Backplane Current (5Volts) 250 milliamps
Backplane Current at 24 Volts 2 milliamperes
Backplane Current (24 Volts) 125 milliamps
Power Dissipation (Max) 4.3 Watts
Removable Terminal Blocks 1756-TBNH, 1756-TBSH
Maximum Operating Current 1.2 milliamperes at 30 Volts AC, 60 Hertz