This HME module has 512 KB of SRAM that is battery-backed and a 128K L1 / 128K L2 Cache. In addition, this 1756-HIST1G module has CompactFlash Type II with DMA Flash Memory and One Ethernet 10/100T IEEE 802.3 type of port. The 1756-HIST1G uses an irremovable rechargeable lithium form of battery.
The 1756-HIST1G has Fanless operation and consumes a maximum of 7 Watts (5 Watts typical) of electrical power. Thus, it has a supply voltage and current ratings of 5.1V DC at 800 mA and 24V DC at 3 mA. The 1756-HIST1G must be within a range of -40-185 °F non-operating and from 32-140 °F during operation. It has a Single-slot ControlLogix physical form factor and has a dimension of 145mm x 35mm x 140 mm or 5.6 in x 1.4 in x 5.5 in (Height x Width x Depth). The 1756-HIST1G can be installed in a ControlLogix chassis to use backplane communications and it can collect data from multiple controllers.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
TCI Supply is not an authorized Allen Bradley Distributor
Manufacturer | Rockwell Automation |
Brand | Allen Bradley |
Part Number/Catalog No. | 1756-HIST1G |
Series | ControlLogix |
Power Consumption | 5 Watts (7 Watts Max) |
Ports | 1 Ethernet 10/100T IEEE 802.3 |
Battery | Rechargable Lithium (Non-Removable) |
Clock | Precision Real-Time Clock |
Indicators | Status LEDs and 4-Character Alphanumeric Display |
System Memory | AMD LX800 500 MHz x86 |
Battery-Backed Memory | 512 Kbytes SRAM |
Cache Memory | 128 K L1/128 K L2 |
Compact Flash Memory | Compact Flash Type 2 w/ DMA |
Dimensions | 5.6 x 1.4 x 5.5 in (145 x 35 x 140 mm) |