Allen Bradley 1746-IO12

The Allen Bradley 1746-IO12 is a 12-point combination I/O module from the SLC 500 series, featuring six 120V AC inputs and six relay outputs with normally open contacts.

Technical Specifications

  • Model: 1746-IO12
  • Series: SLC 500
  • Type: Digital I/O Combination Module
  • Mounting: Rack-mounted
  • Inputs: 6 x 120V AC
  • Outputs: 6 x Relay (Form A, Normally Open)
  • Input Operating Voltage: 85–132V AC
  • Output Operating Voltage: 5–125V DC; 5–265V AC
  • Signal Delay: 35–45 milliseconds
  • Current per Output: 1.2A @ 24V DC; 1.5A @ 120V AC
  • Continuous Current per Module: 8.0A
  • Backplane Current: 90 mA @ 5V DC; 70 mA @ 24V DC
  • Heat Dissipation: 0.20W per input point; 0.133W per output point; 4.60W total
  • Isolation Voltage: 1500V AC (I/O to backplane)
  • Operating Temperature: 0°C to 60°C (32°F to 140°F)
  • Storage Temperature: -40°C to 85°C (-40°F to 185°F)
  • Relative Humidity: 5% to 95% non-condensing
  • Slot Width: 1
  • Area Classification: Class I, Division 2 hazardous location certified by CSA
  • Lifecycle Status: Discontinued
  • Manufacturer: Allen Bradley (Rockwell Automation)

Key Features

  • Combination module with both input and output capabilities
  • Space-saving design with 12 channels in a single slot
  • Relay outputs suitable for various load types
  • LED indicators for channel status monitoring
  • Compatible with SLC 500 chassis and processors

Compatible Components & Accessories

  • Allen Bradley SLC 500 chassis and processors
  • Allen Bradley I/O and communication modules
  • RSLogix 500 programming software
  • PanelView HMIs and expansion I/O

Industry Applications

  • Manufacturing automation
  • Packaging and labeling systems
  • Water treatment and utilities
  • Food and beverage processing
  • Automotive and material handling

Installation & Maintenance Notes

  • Install in a clean, dry panel or cabinet
  • Ensure proper alignment in the chassis slot
  • Periodically inspect for dust or electrical wear
  • Use RSLogix 500 for diagnostics and setup
  • Power down before removing or inserting module

Request a Quote

For pricing and availability, please Contact Us or call 1-800-755-2883.

Disclaimer: TCI Supply is not an authorized distributor of Allen Bradley products.

Frequently Asked Questions

What is the signal delay for the 1746-IO12 module?

The module has a signal delay ranging between 35 to 45 milliseconds, depending on the operating conditions.

Is the 1746-IO12 suitable for hazardous locations?

Yes, the module is certified for use in Class I, Division 2 hazardous locations by CSA.

What is the maximum continuous current the module can handle?

The 1746-IO12 can handle a continuous current of up to 8.0A across all outputs.