Johnson Controls V47AR-1 Modulating Water Valve

The Johnson Controls V47AR-1 is a temperature-actuated, modulating water valve designed to regulate water flow in response to sensed temperature changes. This direct-acting valve opens proportionally as the temperature increases, providing accurate water flow control in cooling applications. The V47AR-1 features a large 1-1/2 inch pipe size and operates in a 75°F to 135°F cross-ambient temperature range, making it ideal for condenser water regulation in refrigeration and industrial cooling systems.

Technical Specifications

  • Model: V47AR-1
  • Valve Type: Direct-acting, temperature modulating
  • Pipe Size: 1-1/2 inch NPT
  • Temperature Range (Opening Point): 75°F to 135°F (cross ambient)
  • Actuation Type: Temperature-sensitive sensing element with capillary
  • Capillary Length: Typically 6 feet
  • Maximum Operating Pressure: 150 psi
  • Maximum Water Temperature: 170°F
  • Bulb Well: Not applicable (cross-ambient sensing)

Key Features

  • Opens gradually as ambient temperature increases, ideal for condenser and cooling water control
  • Large 1-1/2″ size suitable for higher flow systems
  • Proportional modulation ensures smooth operation and stable process temperature
  • Designed for applications requiring cross-ambient temperature sensing
  • Compatible with remote-mounted sensing elements for flexible installation

Repair and Replacement Parts

  • Seat Repair Kit: STT17A-610R
  • Replacement Sensing Element: SET29A-605R
  • Bulb Well: Not required (cross-ambient sensing model)

Industry Applications

  • Refrigeration condenser water regulation
  • Industrial equipment cooling
  • Water-cooled compressors and machinery
  • Process cooling systems in manufacturing and production facilities
  • Systems using ambient air temperature for modulation

Installation & Maintenance Notes

  • Mount valve vertically with the bellows down and the spring cage up
  • Position sensing element in a representative cross-ambient location for accurate response
  • Avoid damaging capillary tubing during installation
  • Regularly inspect for scale, corrosion, or mechanical wear
  • Ensure valve is flushed during maintenance to maintain flow accuracy

We ship this product worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Pipe
Size, in.
Range
(Opening Point) °F
Seat Repair Kit Replacement
Sensing Element
Bulb Well Number
Order Separately
1 1/2 6 75 to 135 Cross Ambient STT17A-610R SET29A-605R

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.