Johnson Controls V47AA-2C Modulating Water Valve

The Johnson Controls V47AA-2C is a temperature-actuated, modulating water valve designed for use in heating applications. It opens proportionally as the sensed temperature increases, providing smooth and precise water flow control to regulate system temperature. With a compact 3/8-inch pipe size and a 160°F to 230°F opening range, the V47AA-2C is well-suited for high-temperature equipment such as compressor jackets, heat exchangers, and process control systems.

Technical Specifications

  • Model: V47AA-2C
  • Valve Type: Direct-acting, temperature modulating
  • Pipe Size: 3/8 inch NPT
  • Temperature Range (Opening Point): 160°F to 230°F
  • Bulb Size: 11/16 inch diameter x 3-1/4 inch length
  • Standard Bypass Orifice Diameter: 0.062 inch
  • Capillary Length: 6 feet
  • Maximum Operating Pressure: 150 psi
  • Maximum Water Temperature: 170°F
  • Bulb Well (Ordered Separately): WEL18A-602R

Key Features

  • Direct-acting design opens with rising temperature at the sensing bulb
  • Compact 3/8-inch valve ideal for small-line applications
  • Proportional modulation for accurate thermal regulation
  • Built-in bypass orifice allows continuous minimal flow when valve is closed
  • Designed for use with a remote sensing bulb for flexible installation

Repair and Replacement Parts

  • Seat Repair Kit: STT14A-600R
  • Replacement Sensing Element: SET29A-623R
  • Bulb Well (Order Separately): WEL18A-602R

Industry Applications

  • Compressor cooling and heat jacket systems
  • Industrial and commercial heat exchangers
  • Process control applications requiring high-temperature water regulation
  • HVAC and mechanical room thermal management

Installation & Maintenance Notes

  • Install valve vertically with bellows at the bottom and spring cage facing up
  • Place the sensing bulb in a representative thermal zone using a compatible well
  • Avoid damaging or sharply bending the capillary tubing
  • Inspect periodically for sediment, corrosion, or reduced thermal response
  • Ensure the sensing bulb is not exposed to temperatures exceeding the valve’s maximum range

We ship this product worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

 

Code
Number1
Pipe
Size, in.
Range
(Opening Point) °F
Bulb Size, in.
(Dia length)
Std Bypass
Orifice Dia in.
Seat Repair Kit Replacement
Sensing Element
Bulb Well Number
Order Separately
V47AA-2C 3/8 160 to 230 Heating 11/16 x 3 1/4 0.062 STT14A-600R SET29A-623R WEL18A-602R