Primary Flame Safeguard with Pre/Post Purge and Interrupted Pilot

The Honeywell RM7896C2010 is a microprocessor-based primary burner control designed for on-off single-burner applications using gas, oil, or combination fuels. It offers integrated flame safeguard capabilities, automatic burner sequencing, and advanced diagnostics. This model includes built-in pre-purge and post-purge functionality, making it suitable for high-performance burner systems that require enhanced safety and NFPA-compliant sequencing.

Technical Specifications

  • Model: RM7896C2010
  • Series: RM7800
  • Product Type: Primary Burner Control
  • Power Supply: 120V AC (+10%, -15%), 50/60 Hz
  • Application: On-Off Burner with Pre and Post Purge
  • Burner Type: Automatically Fired, Interrupted Pilot
  • Flame Establishing Period – Pilot: 4 or 10 seconds
  • Flame Establishing Period – Main: 10 seconds
  • PrePurge: Determined by ST7800A Purge Timer Card
  • PostPurge: Fixed at 15 seconds
  • Interlocks: Selectable
  • Delayed Main Valve: Yes
  • Mounting: Q7800A or Q7800B Subbase required
  • Weight: 1 lb 15 oz (0.9 kg)
  • Dimensions (with Q7800A): 5″ W x 5″ H x 5-1/4″ D
  • Dimensions (with Q7800B): 5″ W x 5″ H x 6-3/32″ D
  • Temperature Range (Shipping & Storage): -40°F to +140°F (-40°C to +60°C)
  • Vibration Tolerance: 0.5 G environment
  • Condition: New

Key Features

  • Integrated pre-purge and post-purge control for enhanced safety
  • Interrupted pilot control for increased fuel efficiency
  • Microprocessor-based sequencing and diagnostics
  • Five LED indicators provide real-time sequence and fault info
  • Interchangeable plug-in flame amplifiers for UV, IR, or rectification sensing
  • Retains operational history and fault logs in nonvolatile memory
  • Supports remote reset and annunciation options
  • Optional display modules and software interfaces available

Compatible Accessories

  • Q7800A or Q7800B Subbase
  • ST7800A Purge Timer Card
  • R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Amplifiers
  • S7800A or other Honeywell Keyboard Display Modules
  • Flame rods, UV and IR scanners

Industry Applications

  • Commercial and industrial boilers
  • Packaged burner systems
  • Process heating and thermal control
  • Combustion safety systems requiring pre/post purge

Installation & Maintenance Notes

  • Must be mounted with compatible Q7800 subbase
  • Flame amplifier and sensor must match burner type
  • PrePurge duration set via ST7800A purge timer card
  • Confirm proper interlock wiring and airflow switch operation
  • Review sequence and lockout status via onboard LEDs or remote display