Modular 120V System with Prepurge and Global Certifications

The Honeywell RM7895E1010 is a microprocessor-based primary burner control designed for automatic operation of single-burner gas, oil, or combination-fuel systems. Built for safety and performance, this model features modular compatibility, selectable prepurge timing, and flexible flame detection options. With CE, UL, CSA, and SIL-3 certifications, the RM7895E1010 meets stringent international safety standards and is ideal for both commercial and industrial combustion applications.

Technical Specifications

  • Model: RM7895E1010
  • Series: RM7800
  • Product Type: Primary Burner Control
  • Voltage: 120V AC
  • Application: On-Off Burner with Prepurge
  • Mounting: Cabinet mount (IP00, Europe) or wall/cabinet mount (NEMA 1, Americas)
  • Ambient Temperature Range: -40°C to +60°C
  • Maximum Humidity: 85% RH
  • PrePurge: Selectable via ST7800A1xxx/U purge timer module
  • Flame Detector Type: UV, IR, or rectification (via plug-in amplifier)
  • Flame Amplifier Compatibility: R7847, R7848, R7849, R7851, R7861, and others
  • Failure Response Time (FFRT):
  • EU Models: 1.0 or 2.0 seconds
  • US Models: 0.8 or 3.0 seconds (depends on amplifier)
  • Certifications: CE (EN 298), CSA/UL (US), SIL-3 Capable, APAVE (EU)
  • Protection Class: IP00 (EU); NEMA 1 (US)
  • Condition: New

Key Features

  • Modular design accepts all Honeywell flame amplifiers and detectors
  • Selectable prepurge timing through plug-in purge card
  • Stores lockout history, flame signal, and operational hours
  • Keyboard display module provides system data and diagnostics
  • Fully compatible with Honeywell flame rods and optical detectors
  • SIL-3 capable for high-integrity safety applications
  • Global approvals for use in EU and US burner systems

Compatible Accessories

  • Q7800A or Q7800B Subbase
  • ST7800A Purge Timer Module
  • S7800A Keyboard Display Module
  • Flame rods and UV/IR flame sensors
  • DATA CONTROLBUS™ communication modules

Industry Applications

  • Boilers and hot water systems
  • Fuel-fired furnaces and ovens
  • Process heating and thermal systems
  • Commercial and industrial burner applications

Installation & Maintenance Notes

  • Use appropriate subbase and amplifier based on system type
  • Ensure grounding and wiring follow local standards
  • Review last six lockout conditions using the display module
  • Adjust prepurge timing via ST7800A module selection
  • Monitor flame strength and cycle hours for proactive maintenance

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!