Modular 120V System with Prepurge and Global Certifications
The Honeywell RM7895E1010 is a microprocessor-based primary burner control designed for automatic operation of single-burner gas, oil, or combination-fuel systems. Built for safety and performance, this model features modular compatibility, selectable prepurge timing, and flexible flame detection options. With CE, UL, CSA, and SIL-3 certifications, the RM7895E1010 meets stringent international safety standards and is ideal for both commercial and industrial combustion applications.
Technical Specifications
- Model: RM7895E1010
- Series: RM7800
- Product Type: Primary Burner Control
- Voltage: 120V AC
- Application: On-Off Burner with Prepurge
- Mounting: Cabinet mount (IP00, Europe) or wall/cabinet mount (NEMA 1, Americas)
- Ambient Temperature Range: -40°C to +60°C
- Maximum Humidity: 85% RH
- PrePurge: Selectable via ST7800A1xxx/U purge timer module
- Flame Detector Type: UV, IR, or rectification (via plug-in amplifier)
- Flame Amplifier Compatibility: R7847, R7848, R7849, R7851, R7861, and others
- Failure Response Time (FFRT):
- EU Models: 1.0 or 2.0 seconds
- US Models: 0.8 or 3.0 seconds (depends on amplifier)
- Certifications: CE (EN 298), CSA/UL (US), SIL-3 Capable, APAVE (EU)
- Protection Class: IP00 (EU); NEMA 1 (US)
- Condition: New
Key Features
- Modular design accepts all Honeywell flame amplifiers and detectors
- Selectable prepurge timing through plug-in purge card
- Stores lockout history, flame signal, and operational hours
- Keyboard display module provides system data and diagnostics
- Fully compatible with Honeywell flame rods and optical detectors
- SIL-3 capable for high-integrity safety applications
- Global approvals for use in EU and US burner systems
Compatible Accessories
- Q7800A or Q7800B Subbase
- ST7800A Purge Timer Module
- S7800A Keyboard Display Module
- Flame rods and UV/IR flame sensors
- DATA CONTROLBUS™ communication modules
Industry Applications
- Boilers and hot water systems
- Fuel-fired furnaces and ovens
- Process heating and thermal systems
- Commercial and industrial burner applications
Installation & Maintenance Notes
- Use appropriate subbase and amplifier based on system type
- Ensure grounding and wiring follow local standards
- Review last six lockout conditions using the display module
- Adjust prepurge timing via ST7800A module selection
- Monitor flame strength and cycle hours for proactive maintenance