The Honeywell RM7895A2014 is a microprocessor-based primary burner control with a grounding pin, designed for use with on-off gas burners or burners requiring interrupted or intermittent pilot operation. As a core component of the Honeywell 7800 Series, this unit delivers dependable flame safeguard, burner sequencing, and safety shutdowns in industrial and commercial combustion systems.
Technical Specifications
- Model: RM7895A2014
- Series: Honeywell 7800 Series
- Product Type: Primary Burner Control Module
- Burner Type: On-Off, Intermittent or Interrupted Pilot
- Voltage: 120V AC
- Frequency: 50/60 Hz
- Amplifier Compatibility: R7847, R7848, R7849, R7851 Series
- Mounting: Panel Mount (Q7800A Subbase required)
- Flame Failure Response: 2–4 seconds (based on amplifier used)
- Lockout Feature: Yes, Manual Reset Required
- Communication: Optional via S7830A Keyboard Display Module
- Display Options: LED system status indicators
- 2000 series with grounding pin
- Condition: New or Reconditioned
- Warranty: 1-Year Replacement Warranty
Key Features
- Controls on-off burners and those requiring pilot operation
- Provides full flame safeguard and sequencing
- Compatible with UV, IR, and rectification flame sensors
- Manual reset lockout for fail-safe protection
- Built-in status LEDs for diagnostics and operation monitoring
Compatible Accessories
- Q7800A Subbase
- S7830A Keyboard Display Module
- R7847, R7848, R7849, R7851 Flame Amplifiers
- Flame rods and sensors
Industry Applications
- Industrial furnaces and boilers
- Heat processing equipment
- Packaged burner units
- HVAC and commercial heating systems
Installation & Maintenance Notes
- Always install with a Q7800A subbase
- Select the correct flame amplifier and sensor for your system
- Follow Honeywell wiring instructions and local codes
- Test flame signal and lockout features during commissioning
Request a Quote now or call us at 1-800-755-2883 for expert assistance.