The Honeywell RM7830A1011 Burner Control is a microprocessor-based integrated control system designed for full modulation burner applications. It offers automatic burner sequencing, precise flame supervision, and clear system status indications. With built-in system and self-diagnostics, troubleshooting is streamlined, ensuring operational reliability and safety. Operating at 120V and 50/60Hz, this control unit includes a 15-second post-purge feature to enhance efficiency and safety. Ideal for complex heating systems, the RM7830A1011 provides comprehensive control and monitoring to maintain optimal burner performance.
Technical Specifications
- Model: RM7830A1011
- Series: RM7800
- Voltage: 120V AC (+10%, -15%)
- Frequency: 50/60 Hz
- Application: Fully Modulating Burner Systems
- Flame Establishing Period – Pilot: 3 or 5 seconds
- Flame Establishing Period – Main: 3 sec, 5 sec, or Intermittent
- PrePurge: Determined by ST7800A Plug-in Purge Timer
- PostPurge: 15 seconds
- Preignition: Yes
- Early Spark Termination: Yes, after 5 seconds
- Interlocks: Lockout
- Mounting: Q7800A or Q7800B Subbase required
- LED Indicators: 5 LEDs for sequence and fault status
- Run/Test Switch: 5-position selector for diagnostics and function testing
- Memory: Nonvolatile memory retains status and lockout history
- Compatible Flame Amplifiers: R7847, R7848, R7849, R7851, R7861, R7886
- Condition: New
Key Features
- Designed for full modulation burner sequencing and control
- Early spark termination and timed post-purge for energy-efficient operation
- Accepts plug-in amplifiers for UV, IR, or flame rod flame detection
- Five LED indicators provide real-time system status
- Supports both local and remote annunciation options
- Stores burner operation history and lockout codes for quick troubleshooting
- Communication-capable for integration with advanced monitoring systems
- Access terminals for voltage testing and safety diagnostics
Compatible Accessories
- Q7800A / Q7800B Universal Subbases
- ST7800A Purge Timer Module
- S7800A Keyboard Display Module
- R7847, R7848, R7849, R7851, R7861, R7886 Amplifiers
- S7830 Expanded Annunciator
- S7810 Communication Modules
Industry Applications
- Full-modulation commercial boilers
- Industrial process burners
- High-efficiency heating systems
- Burner management systems with sequencing and flame supervision
Installation & Maintenance Notes
- Install with proper subbase and matched amplifier
- Set purge timing with ST7800A module
- Use the Run/Test switch for startup and service operations
- Monitor sequence and diagnostics through built-in LEDs or optional display
- Inspect flame sensor regularly and verify flame signal strength