RM7800L1012 honeywell controllerDescription

120 V Burner Control with airflow switch check option, for Automatic Single Burner Systems. Replaces the BC7000/PM720L series of Honeywell products. Please order the Base Amplifier, Wiring Subbase & Purge Timer Separately. Includes Keyboard Display Module S7800A1001 / S7800A1142.

Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls.

Features

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting.
  • Access for external electrical voltage checks.
  • Application flexibility and communication interface capability.
  • Five LEDs provide sequence information.
  • Five function Run/Test Switch.
  • Interchangeable plug-in flame amplifiers.
  • Local or remote annunciation of operation and fault information (optional).
  • Nonvolatile memory retains history files and lockout status after loss of power.
  • Compatible with existing Honeywell flame detectors.
  • Includes Keyboard Display Module.

 

The Honeywell RM7800L1012 is an advanced microprocessor-based burner control relay module designed for continuous operation in industrial and commercial burner management systems. Part of the Honeywell 7800 Series, the RM7800L1012 provides flame safeguard control for single-burner applications, ensuring safe and reliable operation with integrated diagnostics, status indication, and remote monitoring capabilities.


Technical Specifications:

  • Model: Honeywell RM7800L1012
  • Series: 7800 Series Burner Control
  • Voltage: 120 VAC, 50/60 Hz
  • Flame Detection: Compatible with rectification, UV, and infrared flame sensors
  • Ignition Trial Time (TFI): 4 seconds
  • Pre-Purge Time: 30 seconds
  • Recycle/Non-Recycle: Non-recycle
  • Operating Temperature: -40°F to 140°F (-40°C to 60°C)
  • Relative Humidity: Up to 85% (non-condensing)
  • Diagnostics: Built-in LED status indication and remote diagnostics capability
  • Communication: Compatible with Honeywell Modbus communication and remote monitoring solutions
  • Approval Standards: UL, FM, CSA Approved

Compatible Components & Accessories:

The Honeywell RM7800L1012 is used in conjunction with various Honeywell flame safeguard components, including:

  • Honeywell 7800 Series Keyboard Display Modules (KDM) – Provides real-time burner status and diagnostics.
  • Honeywell Q7800A/B Subbase – Required for mounting and wiring connections.
  • Honeywell Flame Sensors:
    • C7027A, C7035A UV Flame Detectors
    • C7061A Flame Sensor
    • Rectification Flame Rods
  • Honeywell R7847A Flame Amplifier – Provides UV flame signal processing.
  • Honeywell R7886A Dynamic Self-Check Amplifier – Supports continuous burner operation with enhanced safety.

Applications & Industry Uses:

The Honeywell RM7800L1012 Burner Control Module is designed for use in commercial and industrial burner applications, including:

  • Industrial Boilers – Ensures safe and efficient combustion control.
  • Process Burners – Used in petrochemical, power generation, and refinery industries.
  • Furnaces & Ovens – Provides flame safety and monitoring.
  • Commercial HVAC Systems – Used in large-scale heating applications.