Description
Note: To replace this item, in addition to purchasing RM7890A1015, you will need to purchase these items as well: R7849A1023 & Q7800A1005.
The RA890G1260 is a Rectification flame safety control. With a 15-second safety switch, 3-second flame response. 120V 50/60.With SPDT alarm contact. Use flame rod or photo cell. Replaces RA890E in most applications and mounts on same Q270A1024 Subbase
Features:
- Uses rectification principle of electronic flame detection.
- Replaces RA890E in most applications and mounts on same Q270A1024 Subbase.
- Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout.
- Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit.
- Includes built-in protection against ignition crossover in flame rod systems.
- Includes SPDT alarm contacts.
- Solid state circuitry.
- Mounts and removes easily through use of captive mounting screws.
- Mounting base is made of strong thermoplastic.
Specs
Safety Timing: |
15 Seconds |
---|---|
Application: |
Primary control for rectification application |
Voltage: |
120v |
We ship this product worldwide! Delivery is normally stock.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.