The Honeywell R7847C1005 Flame Amplifier is a solid-state, plug-in amplifier designed for use with Honeywell 7800 Series Relay Modules. It processes flame detector signals to confirm flame presence and ensures reliable burner operation. Featuring dynamic self-check functionality, this amplifier continuously monitors the flame detection system, providing enhanced safety and performance in industrial combustion applications.
Technical Specifications
- Model: R7847C1005
- Amplifier Type: Rectification flame amplifier
- Flame Failure Response Time: Selectable 2.0 or 3.0 seconds
- Flame Signal Strength: 0.0 to 5.0 VDC
- Self-Check Function: Dynamic self-checking for system monitoring
- Compatible Relay Modules: Honeywell 7800 Series Relay Modules
- Compatible Flame Sensors:
- Honeywell C7012E Ultraviolet Flame Sensor
- Honeywell C7012F Ultraviolet Flame Sensor
- Connection Type: Plug-in through a printed circuit board edge connector
- Diagnostic Features:
- Flame signal test jacks for measuring flame signal voltage
- Dynamic Self-Check function tests the detectors and all electronic components in the flame detection system
- System locks out on safety shutdown if a flame detection failure occurs
Key Features
- Solid-state plug-in amplifier for reliable flame supervision
- Dynamic self-checking technology enhances system safety and reliability
- Selectable 2.0 or 3.0-second flame failure response time for application flexibility
- Measures and displays flame signal strength from 0.0 to 5.0 VDC
- Color-coded labels for easy identification of flame detection type
- Designed for integration with Honeywell 7800 Series burner management systems
Compatible Components & Accessories
- Honeywell 7800 Series Relay Modules
- Honeywell C7012E and C7012F Ultraviolet Flame Sensors
- Honeywell burner control systems for industrial combustion safety
- Standard mounting and wiring accessories for installation
Industry Applications
- Industrial boiler and burner management systems
- Power generation combustion monitoring
- Process heating in manufacturing and chemical industries
- Petrochemical and refinery burner safety applications
- HVAC and heating systems requiring precise flame detection
Installation & Maintenance Notes
- Ensure compatibility with Honeywell 7800 Series Relay Modules before installation
- Plug directly into the relay module through the printed circuit board edge connector
- Use built-in flame signal test jacks to verify flame signal strength and system integrity
- Regularly inspect the amplifier and connected flame sensor for optimal performance
- Maintenance should be performed by qualified personnel familiar with flame safety systems