The Honeywell R7847B1031 Rectification Flame Amplifier is a dynamic Ampli-Check solid-state plug-in unit designed for reliable flame detection. It responds to flame detector signals, indicating the presence of a flame within three seconds. This amplifier is compatible with flame rod photo cells or the C7012A flame detector. It operates effectively in ambient temperatures ranging from -40°F to 140°F (-40°C to 60°C), ensuring versatility and durability in various industrial environments. The R7847B1031 integrates seamlessly with Honeywell’s 7800 Series relay modules, enhancing safety and functionality in combustion control systems.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Request a Quote now or call us at 1-800-755-2883 for expert assistance.