Description
Pneumatic actuators offer proportional control of steam, hot, or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement units are available for older Honeywell actuators.
Features
Rolling diaphragm for long life and low hysteresis.
Easily attached to valve.
Can be installed after piping valve.
Slide lock feature permits simple engagement to valve stem.
Direct- or reverse-action control.
Includes Positioner
Rolling diaphragm for long life and low hysteresis.
Easily attached to valve.
Can be installed after piping valve.
Slide lock feature permits simple engagement to valve stem.
Direct- or reverse-action control.
Includes Positioner
Specifications
Actuator Type: Valve
Actuator Force: medium
Action: Direct Acting
Stroke: 3/4 in.
Maximum Safe Operating Pressure (psi): 25 psi
Temperature Range (F): 0 F to 140 F
Fail Safe Mode: Spring Return
Air Connections: Pilot barbed fitting for 5/32 in. O.D. and 1/4 in. O.D. plastic tubing
Operating Humidity Range: 5 to 95% RH
Specs
Diameter (Inches): |
8″ |
---|---|
Temperature Range (F): |
0°F – 140°F |
Max Pressure (PSI): |
25 |
Actuator Spring Range: |
4 to 11 psi |
Action: |
Direct Acting |
Fail Safe Mode: |
Spring Return |
PSI Range: |
5 PSI |