Description
This device is employed for pneumatic proportional control of variable volume terminal units and small dampers. It comes in different operating ranges suitable for individual use or in sequence with other actuators. Replacement units are offered for Johnson, Powers, Robertshaw, and older models of Honeywell actuators
Features
Rugged ribbed aluminum body.
Low-friction shaft bearing.
Close tolerance on operating range and stroke.
Protected barb connector.
Versatile mounting and connecting hardware options.
Positive leakproof seal.
Specs
Air Connections: |
1/8″ NPT Barbed fitting for 3/32″ O.D. tubing |
---|---|
Product Type: |
Actuator |
Actuator Type: |
Pneumatic |
Temperature Range (F): |
50°F to 140°F |
Actuator Spring Range: |
8 to 13 psi |
Fail Safe Mode: |
Spring Return |
Stroke: |
2.4″ |
Max Pressure (PSI): |
30 |
Request a Quote now or call us at 1-800-755-2883 for expert assistance.