On-Off Flame Safeguard with Prepurge and Intermittent Pilot

The Honeywell RM7895A1030 is a microprocessor-based primary burner control built for on-off burner systems using gas, oil, or combination fuels. Designed in collaboration with Fulton, this control module provides flame safeguard, burner sequencing, and diagnostic functionality in a modular, reliable format. It supports prepurge timing, intermittent pilot operation, and advanced system status indication with nonvolatile memory for enhanced system insight.

Technical Specifications

  • Model: RM7895A1030
  • Series: RM7800 (Fulton Edition)
  • Application: On-Off Primary Burner Control with Prepurge
  • Voltage: 120V AC (+10%, -15%)
  • Frequency: 50/60 Hz (±10%)
  • Flame Establishing Period – Pilot: 4 or 10 seconds (limited)
  • Flame Establishing Period – Main: Intermittent
  • PrePurge: Determined by ST7800A Purge Timer Card
  • Pilot Type: Intermittent
  • Delayed Main Valve: No
  • Interlocks: Selectable
  • Airflow Switch Check: Included
  • Used With: R7847, R7849 Flame Amplifiers
  • Required Components:
  • Q7800A or Q7800B Universal Wiring Subbase
  • ST7800A Purge Timer Card
  • Compatible Flame Amplifier (R7847, R7848, R7849, R7851, R7852, R7861, R7886)
  • Weight: 1 lb 15 oz (0.9 kg)
  • Dimensions (with Q7800A): 5″ W x 5″ H x 5-1/4″ D
  • Dimensions (with Q7800B): 5″ W x 5″ H x 6-3/32″ D
  • Vibration Tolerance: 5 G environment
  • Temperature Range (Storage/Shipping): -40°F to +140°F (-40°C to +60°C)
  • Condition: New

Key Features

  • Automatic burner sequencing, flame supervision, and system lockout
  • Prepurge capability controlled by ST7800A module
  • Interchangeable flame amplifiers for flexible detection options
  • Five LEDs indicate burner sequence and system status
  • Optional keyboard display, remote display, or annunciator integration
  • Nonvolatile memory stores history and sequence after power loss
  • Selectable relight or lockout on flame loss
  • Optional remote reset and PC interface options

Compatible Accessories

  • Q7800A or Q7800B Subbase
  • ST7800A Plug-in Purge Timer
  • R7847, R7849, and other Honeywell Flame Amplifiers
  • S7800A Keyboard Display Modules
  • DATA CONTROLBUS™ and COMBUSTION SYSTEM MANAGER™ Modules

Industry Applications

  • Fulton boilers and packaged burner systems
  • Industrial combustion systems
  • Commercial heating plants
  • Fuel-fired ovens and kilns

Installation & Maintenance Notes

  • Install with correct subbase and amplifier module
  • Confirm purge time with ST7800A card
  • Use with compatible flame rods or sensors
  • Monitor operation using LED indicators or display module
  • Review last lockouts and operating hours from memory