Description
The Honeywell C7076A1007 UV Flame Detector is a solid-state device designed for burner management and flame safety systems, ensuring optimal sensitivity to ultraviolet radiation emitted by gas, oil, and pulverized coal flames. It integrates seamlessly with BC7000, R4140, or FSP5075 controllers, paired with R7476 or R7886 amplifiers from the 7800 Series. This detector offers adjustable sensitivity, ideal for applications requiring precise flame discrimination and reliable operation. Its robust solid-state circuitry ensures longevity and stable performance across varying temperatures and voltages, while its high-level output supports long-distance signal transmission without requiring specialized wiring. The C7076A model is tailored for standard installations, providing enhanced safety and efficiency in industrial and commercial settings reliant on accurate flame detection and control.
Features:
- Detect ultraviolet radiation from flames.
- Includes dual sensitivity adjustment.
- C7076A meets NEMA 4 standards with viewing window rated to 20 psi.
- C7076D has an explosion-proof housing for use in hazardous atmospheres with a viewing window rated to 100 psi.
- Adjustable Sensitivity Ultraviolet Flame Detector
- Type: Ultraviolet, Adjustable Sensitivity
- Electrical Connections: Terminal block
- Vibration: 0.5 G max
- Mounting: 1″ NPT
- Electrical Ratings: 120 Vac
- Dynamic self-checking flame detector with adjustable sensitivity
Specs
Application: |
Gas fired burners, Oil fired burners |
---|---|
NEMA Rating: |
4 |
Max Temp (F): |
160°F |
Min Temp (F): |
-40°F |
Temperature Range (F): |
-40°F to 160°F |
Frequency: |
60 Hz |
Height: |
4″ |
Width (Inches): |
4″ |
Depth (Inches): |
10-1/4″ |
Power Consumption: |
7.0 W |
Used With: |
R7476, R7886 |
We ship this product worldwide! Delivery is normally stock.