Black programmer card with PCB visableThe Fireye MEP560 is a versatile plug-in programmer module designed for use with the Fireye MicroM Series burner management system. It supports safe burner sequencing with advanced control features including selectable recycle or non-recycle operation, pilot stabilization, configurable timing for purge and ignition, and a run-check switch for system testing. With comprehensive control logic, the MEP560 is ideal for applications requiring reliable, flexible flame supervision.

Qty 1 in stock

Technical Specifications

  • Model: MEP560
  • Series: MicroM
  • Operation Mode: Selectable Recycle / Non-Recycle
  • Pilot Stabilization: 8 seconds
  • Main Trial-for-Ignition (TFI): 10 seconds
  • Purge Time: Selectable (per system setup)
  • Post Purge: Supported
  • Air Proving: Requires proof of air switch open at start
  • Test Mode: Integrated run-check switch
  • Mounting: Plug-in module for MicroM chassis
  • Application: Gas, oil, or combination fuel burners

Key Features

  • Selectable recycle or non-recycle function to meet safety or operational requirements
  • 8-second pilot stabilization period ensures stable flame before transferring to main
  • 10-second main TFI supports dependable flame establishment
  • Selectable purge and post-purge functions enhance combustion chamber safety
  • Verifies air switch is open before startup for secure operation
  • Run-check switch allows safe testing and operational verification
  • Plug-in format simplifies installation and replacement

Compatible Components & Accessories

  • Fireye MicroM control chassis
  • Flame amplifiers (UV, IR, rectification)
  • Flame scanners (e.g., UV1, 45UV5, C7061)
  • Burner control panels, fuel valves, and safety interlocks
  • System wiring harnesses and test accessories

Industry Applications

  • Commercial and industrial boilers
  • Power generation combustion controls
  • Food processing and drying systems
  • Petrochemical burner systems
  • High-efficiency HVAC burner control

Installation & Maintenance Notes

  • Confirm all safety interlocks and flame detection components are properly wired and functional
  • Set purge and post-purge durations per system safety requirements
  • Utilize run-check switch for safe operational testing during commissioning or maintenance
  • Periodically verify flame signal strength, amplifier performance, and lockout functionality
  • Installation and servicing should be conducted by qualified personnel trained in burner management systems

 