The Fireye MBCE-230FR-1CEX is a flame sensor module designed for industrial combustion applications, providing reliable flame monitoring using the ionization principle. This self-contained module operates at 230 VAC, 50/60 Hz, and is compatible with flame rods for flame detection. It features a Flame Failure Response Time (FFRT) of 1 second, ensuring prompt detection of flame loss to enhance system safety. The MBCE-230FR-1CEX is CE approved and carries ATEX/IECEx Ex d IIC T6 certifications, making it suitable for use in hazardous environments. For installation, it requires the 60-2886 plug-in wiring base, which supports both DIN rail and panel surface mounting. The module provides a 4-20mA output for direct reading of flame signal strength and includes a flame ON/OFF LED indicator for visual status confirmation. It is important to note that when using the MBCE-230FR-1CEX, additional means must be furnished to provide functions usually handled by flame safeguard control systems, such as safe start checks, valve closure, and safety timings, to meet local regulations.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
Part Number | MBCE-230FR-1CEX |
Supply Voltage | 230 VAC (+10%, -15%), 50/60 Hz |
Flame Failure Response Time (FFRT) | 1 second |
Flame Detection Method | Flame rod (ionization principle) |
Output Signal | 4-20mA for flame signal strength |
Indicators | Flame ON/OFF LED |
Mounting Base | 60-2886 plug-in wiring base (DIN rail or panel surface mount) |
Certifications | CE approved, ATEX/IECEx Ex d IIC T6 |
Operating Temperature Range | -40°F to 150°F (-40°C to 65°C) |
Humidity | 85% RH (max), non-condensing |