The Fireye MART1, MART3, MART1T, MAUV1, MAUV3 and MAUV1T are Amplifier Modules used with the Fireye Modular M-SERIES II control. These amplifier modules provide flame scanning capabilities using any of the Fireye standard ultraviolet scanners (self-check scanners not applicable) and flame rods. The Flame Failure Response Time (F.F.R.T.) of the control is determined by the selection of the amplifier module. Test jacks are provided on the amplifier modules to permit flame signal measurement during operation.
M-Series II Amplifier Modules
- MAUV1: UV amp, 2-4 sec FFRT. Use with UV1, UV2, 45UV3.
- MAUV1T: UV amp, .8 sec FFRT. Use with UV1, UV2, 45UV3.
- MAUV3: UV amp, 3 sec FFRT. Use with IV1, UV2, 45UV3.
- MART1: Flame rect amp. 2-4 sec FFRT. Use with 69ND, 45CM.
- MART1T: Flame rect amp. .8 sec FFRT. Use with 69ND, 45CM.
- MART3: Flame rect amp. 3 sec FFRT. Use with 69ND, 45CM.
We ship this product nation wide! Delivery is normally stock.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
MA-UV1