red burner control expansionThe Fireye E300 Expansion Module is designed to enhance the FLAME-MONITOR system by providing additional interlock supervision capability. It allows for the monitoring of up to sixteen interlock switches, improving system safety, diagnostic capabilities, and operational efficiency. When connected to a Fireye EB700 FLAME-MONITOR chassis, the E300 functions as a first-out annunciator, automatically displaying messages associated with specific interlock conditions. Additionally, it includes a fuel selection circuit to accommodate dual-fuel burner systems.

Technical Specifications

  • Model: E300
  • Compatible with: Fireye FLAME-MONITOR EB700 series chassis
  • Interlock Inputs: 16 monitored interlock switches
  • Display: FLAME-MONITOR system acts as a first-out annunciator
  • Fuel Selection: Standard fuel selection circuit for dual-fuel burners
  • Connectivity: Ribbon cable connection (P/N E350-3, E350-6)
  • Default Messages: Pre-programmed messages for each interlock terminal
  • Enclosure: Designed for panel mounting with industrial-grade protection

Key Features

  • Expands interlock supervision capabilities of the Fireye FLAME-MONITOR System
  • Monitors up to 16 interlocks, providing detailed first-out annunciation
  • Seamless integration with EB700 chassis through a ribbon cable connection
  • Pre-configured messages for each interlock terminal for easy troubleshooting
  • Fuel selection circuit for dual-fuel burner control
  • Industrial-grade construction, ensuring long-term reliability in harsh burner environments

Compatible Components & Related Parts

  • Fireye EB700 Flame-Monitor Chassis – Required for integration with the E300 Expansion Module
  • Fireye E350-3, E350-6 Ribbon Cables – Necessary for connecting the E300 module to the EB700 chassis
  • Fireye Burner Management Systems – Works with Fireye flame safeguard and burner control systems
  • Interlock Switches & Safety Controls – Connects with limit switches, pressure switches, and fuel control relays

Industry Applications

  • Industrial Burner Systems – Used in boilers, furnaces, and process heaters to monitor interlocks
  • Power Generation – Supports burner management systems in power plants and utility operations
  • Oil & Gas – Ensures safe fuel handling in refineries, pipelines, and petrochemical facilities
  • Food & Beverage Processing – Monitors burner interlocks in ovens and sterilization processes
  • Pharmaceutical & Chemical Manufacturing – Provides critical safety monitoring for industrial burners

Compliance & Certifications

  • UL Listed, FM Approved – Meets industry flame safeguard and safety standards
  • CE Marked – Complies with European safety and burner control regulations
  • NFPA 85 Compatible – Designed for boiler and combustion system safety compliance

Installation & Operational Notes

  • Requires connection to an EB700 FLAME-MONITOR chassis using E350-3 or E350-6 ribbon cables
  • Default messages are pre-programmed, but customization may be possible based on system requirements
  • Proper wiring of interlock switches is critical for ensuring accurate fault annunciation
  • Suitable for panel mounting in burner control systems

E300 Expansion Module

  • E300: Expansion module – use with E110/E211
  • E320: Expansion module – use with E210 or E120 (wire per E110 for E120)
  • E350-3: Expansion module cable, 3 ft. length.
  • E350-6: Expansion module cable, 6 ft. length.

We ship this product nation wide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

E-300

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!