Burner control programming cardThe Fireye EP381 is a programmer module designed for use with the Fireye Flame-Monitor Burner Management Control System. This module provides start-up programming, safe-start check, and flame monitoring supervision for commercial and industrial burners. It ensures proof of low fire position and conducts fuel valve end switch safety checks, initiating a safety lockout if any monitored circuits are open at inappropriate points during the control cycle.

Key Features:

  • Selectable Purge Timing: The EP381 offers a base purge time of 15 seconds, which can be extended using dipswitch settings to accommodate specific application requirements.

  • Ignition Timing: It provides a 10-second Pilot Trial for Ignition (PTFI) and a 15-second Main Trial for Ignition (MTFI), ensuring reliable burner start-up sequences.

  • Flame Failure Response Time (FFRT): The module is equipped with a 4-second FFRT, promptly de-energizing fuel valve circuits within this timeframe following a flame failure or at the end of the trial for ignition period if no flame is detected.

  • Dipswitch Configurations: Six dipswitches allow customization of operational characteristics, including:

    • Recycle or Non-Recycle Operation: Determines the control’s response when the running interlock circuit (3-P) is opened during the firing cycle.

    • Intermittent or Interrupted Operation of Terminal 6: Configures terminal 6 to remain energized throughout the firing period or to de-energize after a specified time.

    • Extended Purge Timing: Enables adjustment of purge duration to meet specific safety or process requirements.

    • 3-P Running Interlock Circuit Verification: Option to require the 3-P running interlock circuit to be proven open at the start of the operating cycle.

We ship this product worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Part Number EP381
Purge Timing 15 seconds (extendable via dipswitches)
Pilot Trial for Ignition (PTFI) 10 seconds
Main Trial for Ignition (MTFI) 15 seconds
Flame Failure Response Time (FFRT) 4 seconds
Operational Modes Selectable via dipswitches
Compatibility Fireye Flame-Monitor Burner Management Control System