The Fireye EP381 is a programmer module designed for use with the Fireye Flame-Monitor Burner Management Control System. This module provides start-up programming, safe-start check, and flame monitoring supervision for commercial and industrial burners. It ensures proof of low fire position and conducts fuel valve end switch safety checks, initiating a safety lockout if any monitored circuits are open at inappropriate points during the control cycle.
Key Features:
-
Selectable Purge Timing: The EP381 offers a base purge time of 15 seconds, which can be extended using dipswitch settings to accommodate specific application requirements.
-
Ignition Timing: It provides a 10-second Pilot Trial for Ignition (PTFI) and a 15-second Main Trial for Ignition (MTFI), ensuring reliable burner start-up sequences.
-
Flame Failure Response Time (FFRT): The module is equipped with a 4-second FFRT, promptly de-energizing fuel valve circuits within this timeframe following a flame failure or at the end of the trial for ignition period if no flame is detected.
-
Dipswitch Configurations: Six dipswitches allow customization of operational characteristics, including:
-
Recycle or Non-Recycle Operation: Determines the control’s response when the running interlock circuit (3-P) is opened during the firing cycle.
-
Intermittent or Interrupted Operation of Terminal 6: Configures terminal 6 to remain energized throughout the firing period or to de-energize after a specified time.
-
Extended Purge Timing: Enables adjustment of purge duration to meet specific safety or process requirements.
-
3-P Running Interlock Circuit Verification: Option to require the 3-P running interlock circuit to be proven open at the start of the operating cycle.
-
We ship this product worldwide! Delivery is normally stock.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
Part Number | EP381 |
Purge Timing | 15 seconds (extendable via dipswitches) |
Pilot Trial for Ignition (PTFI) | 10 seconds |
Main Trial for Ignition (MTFI) | 15 seconds |
Flame Failure Response Time (FFRT) | 4 seconds |
Operational Modes | Selectable via dipswitches |
Compatibility | Fireye Flame-Monitor Burner Management Control System |