The Fireye EP163 Programmer Module is a burner management component designed for industrial and commercial combustion control applications. This module is compatible with Fireye Flame-Monitor Series, ensuring precise burner sequencing, flame supervision, and enhanced safety. EP163 characteristics are programmed via the ED510 Display Module, rather than by dipswitch. The EP163 offers non-recycling operation, selectable trial-for-ignition (TFI) timing, and built-in system diagnostics, making it ideal for boiler and burner applications requiring strict flame monitoring.
Technical Specifications
- Manufacturer: Fireye
- Model Number: EP163
- Series: Flame-Monitor
- Voltage: 120 VAC, 50/60 Hz
- Trial for Ignition (TFI): Selectable timing options
- Flame Failure Response Time (FFRT): Adjustable to meet safety requirements
- Non-Recycle Operation: Requires manual reset after a fault condition
- Lockout on Flame Failure: Ensures safe shutdown in case of burner malfunction
- Diagnostic LED Indicators: Provide real-time status updates and troubleshooting information
- Compatible Control Chassis: Fireye EB700 Series
Key Features
- Advanced Burner Control Sequencing for safe and efficient operation
- Selectable TFI Timing for tailored system configurations
- Non-Recycling Operation for enhanced safety compliance
- Built-in System Diagnostics to simplify troubleshooting
- Lockout Protection on Flame Failure to prevent unsafe conditions
- Automatic or Manual Reset Options depending on application needs
- Compatible with Fireye Flame-Monitor System for seamless integration
Compatible Components & Accessories
- Fireye EB700 Flame-Monitor Control Chassis
- Fireye Flame Scanners (UV, IR, and Flame Rod Sensors)
- Fireye Flame Amplifiers
- Fireye Expansion Modules for Remote Monitoring
- Fireye Display Modules for Local Status Indication
Industry Applications
- Industrial and Commercial Boilers
- Steam and Hot Water Heating Systems
- Power Generation and Utility Plants
- Food Processing and Pharmaceutical Facilities
- Chemical and Petrochemical Industries
- Metal Processing and Heat-Treating Applications
Installation & Maintenance Notes
- Ensure proper wiring and secure module installation in Fireye EB700 chassis
- Select appropriate TFI timing based on burner system requirements
- Verify proper operation of flame scanner and safety interlocks
- Perform routine system checks and maintenance as per Fireye recommendations
- Use Fireye diagnostic tools to monitor and troubleshoot burner operation