The Fireye EP160 is a programmer module designed for use with Fireye Flame-Monitor burner control systems. It provides non-recycling, non-retry operation and ensures precise flame supervision in commercial and industrial burner applications. The EP160 module is engineered to monitor, control, and sequence burner functions while ensuring safe startup and shutdown.
Technical Specifications
- Compatible with Fireye E100 and E110 control modules, and the ED510 Display module
- Non-recycling operation – ensures the burner shuts down upon flame failure
- No auto-retry function, prioritizing safety over automatic restart
- Works with UV, IR, and flame rod scanners
- 120 VAC power supply
- Flame Failure Response Time (FFRT): 4 seconds standard
- Microprocessor-based for reliable performance
Features
- Precise burner sequencing for safe operation
- Continuous flame monitoring with various scanner types
- No automatic restart after flame failure for enhanced safety
- LED indicators for burner status and troubleshooting
- Quick plug-in installation into Fireye chassis
Compatible Fireye Components
- E110 Flame-Monitor Control Modules
- Fireye UV, IR, and flame rod scanners
- EP and EPD series programmer modules
Applications
- Commercial and industrial burner management systems
- Boiler, furnace, and incinerator flame monitoring
- HVAC, power generation, and process heating systems
Installation and Operation Notes
- Insert into Fireye E100 or E110 series chassis and plug in the cord jacks
- The Fireye ED510 Display module will plug in and snap into the EP160
- Use with compatible flame scanners for optimal flame detection
- Ensure proper wiring and configuration for safe burner sequencing
- Routine maintenance recommended for long-term system reliability
The Fireye EP160 Programmer Module is a critical component of the Flame-Monitor Burner Management Control System, designed to provide start-up programming, safe-start checks, and flame monitoring supervision for industrial burner applications. It ensures safe and efficient operation by managing burner sequencing and monitoring flame presence.
This module features a selectable purge time with a minimum of 30 seconds, and ignition trial-for-ignition (TFI) periods of 10 and 15 seconds, operating in a non-recycle mode. It is equipped with six dipswitches that allow customization of operational characteristics, including forced blower motor start delay and extended purge timing. The EP160 is compatible with Fireye’s E100 and E110 Flame-Monitor controls, facilitating integration into existing burner management systems.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
Manufacturer | Fireye |
Model | EP160 |
Compatible Systems | Flame-Monitor Burner Management Control System (E100 and E110) |
Purge Time | Selectable, 30 seconds minimum |
Ignition Trial-for-Ignition (TFI) Periods | 10 and 15 seconds |
Flame Failure Response Time (FFRT) | 4 seconds |
Operating Mode | Non-recycle |
Dipswitches | 6, for operational customization |
Safety Shutdown | De-energizes fuel valve circuits within 4 seconds of flame failure |
Communication Ports | RJ45 for ED510 display; two RJ12 for Modbus communications |
Applications | Industrial burner management requiring flame monitoring and safety control |