The Fireye EP160 is a programmer module designed for use with Fireye Flame-Monitor burner control systems. It provides non-recycling, non-retry operation and ensures precise flame supervision in commercial and industrial burner applications. The EP160 module is engineered to monitor, control, and sequence burner functions while ensuring safe startup and shutdown.

Technical Specifications

  • Compatible with Fireye E100 and E110 control modules, and the ED510 Display module
  • Non-recycling operation – ensures the burner shuts down upon flame failure
  • No auto-retry function, prioritizing safety over automatic restart
  • Works with UV, IR, and flame rod scanners
  • 120 VAC power supply
  • Flame Failure Response Time (FFRT): 4 seconds standard
  • Microprocessor-based for reliable performance

Features

  • Precise burner sequencing for safe operation
  • Continuous flame monitoring with various scanner types
  • No automatic restart after flame failure for enhanced safety
  • LED indicators for burner status and troubleshooting
  • Quick plug-in installation into Fireye chassis

Compatible Fireye Components

  • E110 Flame-Monitor Control Modules
  • Fireye UV, IR, and flame rod scanners
  • EP and EPD series programmer modules

Applications

  • Commercial and industrial burner management systems
  • Boiler, furnace, and incinerator flame monitoring
  • HVAC, power generation, and process heating systems

Installation and Operation Notes

  • Insert into Fireye E100 or E110 series chassis and plug in the cord jacks
  • The Fireye ED510 Display module will plug in and snap into the EP160
  • Use with compatible flame scanners for optimal flame detection
  • Ensure proper wiring and configuration for safe burner sequencing
  • Routine maintenance recommended for long-term system reliability

The Fireye EP160 Programmer Module is a critical component of the Flame-Monitor Burner Management Control System, designed to provide start-up programming, safe-start checks, and flame monitoring supervision for industrial burner applications. It ensures safe and efficient operation by managing burner sequencing and monitoring flame presence.

This module features a selectable purge time with a minimum of 30 seconds, and ignition trial-for-ignition (TFI) periods of 10 and 15 seconds, operating in a non-recycle mode. It is equipped with six dipswitches that allow customization of operational characteristics, including forced blower motor start delay and extended purge timing. The EP160 is compatible with Fireye’s E100 and E110 Flame-Monitor controls, facilitating integration into existing burner management systems.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Specification Sheet .pdf

Manufacturer Fireye
Model EP160
Compatible Systems Flame-Monitor Burner Management Control System (E100 and E110)
Purge Time Selectable, 30 seconds minimum
Ignition Trial-for-Ignition (TFI) Periods 10 and 15 seconds
Flame Failure Response Time (FFRT) 4 seconds
Operating Mode Non-recycle
Dipswitches 6, for operational customization
Safety Shutdown De-energizes fuel valve circuits within 4 seconds of flame failure
Communication Ports RJ45 for ED510 display; two RJ12 for Modbus communications
Applications Industrial burner management requiring flame monitoring and safety control