The Fireye EP113NR is a programmer module designed for use with the Flame-Monitor Burner Management Control System. This module provides start-up programming, safe start check, and flame monitoring supervision, ensuring the safe and efficient operation of industrial burners.
Key Features:
-
Non-Recycle Operation: The EP113NR is configured for non-recycle operation, meaning it will initiate a safety shutdown if the running interlock circuit (3-P) opens during the firing cycle.
-
Selectable Purge Timings: Equipped with six dipswitches, the module allows for customization of purge durations to meet specific operational requirements.
-
Interlock Circuit Monitoring: Continuously supervises the running interlock circuit, which includes limit switches, airflow switches, and fuel pressure switches, to ensure system integrity.
-
Display Compatibility: Supports connection with the ED510 display module via an RJ45 connector, providing real-time system status and diagnostics.
Installation Notes:
-
Module Insertion: Ensure the EP113NR is correctly aligned with the designated slot in the EB720 or EB721 chassis. Do not force the module into place; it should fit securely when properly oriented.
-
Dipswitch Configuration: Set the dipswitches according to the desired operational parameters before powering up the system. Refer to the Flame-Monitor system manual for detailed configuration instructions.
-
Display Connection: If using the ED510 display module, connect it to the EP113NR via the RJ45 interface to access system diagnostics and real-time monitoring.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
Part Number | EP113NR |
Operation Mode | Non-Recycle |
Purge Timing | Selectable via dipswitches |
Flame Failure Response Time (FFRT) | 4 seconds |
Display Interface | RJ45 connector for ED510 display module |
Interlock Monitoring | Running interlock circuit (3-P) |
Mounting | Plugs into the second slot of the EB720 or EB721 chassis |