The Fireye BLPS-200 is a pressure transducer designed to measure steam pressure in industrial boiler applications. It provides a 4-20 mA output signal that is linear with pressure, facilitating accurate monitoring and control within the BurnerLogiX and Nexus PPC4000 control systems.
Key Features:
-
Pressure Range: 0 to 200 psi (0 to 13.8 Bar)
-
Output Signal: 4-20 mA, linear with pressure
-
Mounting: 1/4″ NPT male fitting
-
Overpressure Protection: Maximum overpressure of 200% full scale; burst pressure up to 800% full scale
-
Compatibility: Designed for use with Fireye’s BurnerLogiX and Nexus PPC4000 control systems
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
Part Number | BLPS-200 |
Pressure Range | 0 to 200 psi (0 to 13.8 Bar) |
Output Signal | 4-20 mA, linear with pressure |
Mounting | 1/4″ NPT male fitting |
Overpressure Protection | 200% full scale (overpressure); 800% full scale (burst pressure) |
Operating Temperature Range | -40°F to 185°F (-40°C to 85°C) |
Accuracy | ±0.25% full scale (at constant temperature) |
Electrical Connection | 1/2″ conduit with terminal strip |
Installation Notes:
-
Mounting Location: Install the sensor above the water line of the boiler to ensure accurate steam pressure measurement.
-
Piping Requirements: Use a steam trap (siphon loop) between the boiler and the sensor to protect the transducer from high temperatures and contaminants.
-
Wiring: Utilize 2-conductor, 18-gauge, shielded cable for connections, ensuring the shield is grounded at the control system end only.