FIREYE 25SU3-2000

The Fireye 25SU3-2000 Flame Amplifier is a highly advanced flame safeguard amplifier designed for detecting flame presence in single or multi-burner environments. It provides enhanced burner discrimination by analyzing pulse rates from compatible flame scanners, ensuring reliable operation in industrial combustion systems.

This amplifier is capable of receiving pulse inputs from two flame scanners (A and B), either separately or in combination, offering maximum flexibility. It features two logic programs, “Scanner Option 1” and “Scanner Option 2,” allowing users to configure independent operating parameters for each scanner. Switching between these two options is accomplished through an external dry contact input, enabling seamless integration with automation systems.

The 25SU3-2000 Flame Amplifier operates within a dynamic range of 1900 pulses per second, ensuring compatibility with Fireye scanners. Its design follows the global 19-inch format and supports operation on 24 VAC or 24 VDC power supplies.

Technical Specifications

  • Model: 25SU3-2000
  • Power Supply: 24 VAC / 24 VDC
  • Compatible Scanners: Works with Fireye UV and IR scanners
  • Pulse Rate Range: 1900 pulses per second
  • Flame Relay: DPDT Form C, fused
  • Marginal Alarm Relay: SPDT Form C
  • Flame Failure Response Time (FFRT): Adjustable (1 to 6 seconds)
  • Flame Relay Delay On Time: Adjustable (0 to 10 seconds)
  • Output Signal: 4-20mA analog output (scalable flame signal measurement)
  • Communication Protocols: Supports Allen-Bradley DF1 and MODBUS for remote PLC integration
  • User Interface:
    • Keypad Entry System with Password Protection
    • Eight-Character Alpha-Numeric Display
    • Front Panel LED Status Indicators

Key Features

  • Dual Scanner Input Support – Can analyze and process signals from two independent flame scanners
  • Selectable Scanner Logic Programs – Provides operational flexibility with “Scanner Option 1” and “Scanner Option 2”
  • Independent Relay Controls – Adjustable pull-in and drop-out thresholds
  • Advanced Burner Discrimination – Differentiates flame signals to improve system accuracy
  • Multiple Mounting Options:
    • Full Rack (60-2471-3)
    • Half Rack (60-2471-1)
    • Surface Mount Rack (60-2530)

Compatible Fireye Components

  • Fireye Flame Scanners, including UV and IR models
  • Fireye 60-2471-1 Half Rack or 60-2471-3 Full Rack for modular mounting
  • Fireye 60-2530 Surface Mount Rack for compact installations
  • Fireye 60-2206-1 Wiring Base for connectivity
  • Fireye Power Supplies for various amplifier/scanner combinations

Applications

  • Industrial Burner Control Systems
  • Boiler Flame Supervision
  • Gas, Oil, and Dual-Fuel Combustion Monitoring
  • Process Heating and Power Generation Facilities

Installation & Operation Notes

  • Designed for secure rack mounting with modular flexibility
  • Requires proper wiring to Fireye flame scanners for optimal performance
  • Supports PLC communication for remote monitoring and diagnostics

Alternate Part Number

  • Forney DP7000

Spec Sheet (.pdf)

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

 

FIREYE 25SU3-2000 Compatible Flame Scanners

 

FREQ. WAVE- MOUNT AMBIENT SAFETY  
Hz LENGTH THREADS TEMP. MAX., APPROVALS BULLETIN
    (nanometers) MIN.  
 TYPE/MODEL When TUV Agency approval is required, select one of the following:
45UV5-1101 50 180 – 250 1″  BSP 200°F (93°C) – 40°F (-40°C) APAVE, FM CU-22
45RM1-1003 50/60 450 – 1,000 1″  BSP 150°F (65°C)- 40°F (-40°C) FM, APAVE CU-26
45RM2-1001 50/60 700 – 2,500 1″  BSP 150°F (65°C)- 40°F (-40°C) FM, APAVE CU-26
45RM4-1001 24VDC 700-2,500 1″  BSP 150°F (65°C)- 40°F (-40°C) FM, APAVE CU-31
When TUV Agency approval is NOT required, select any scanner from either above or below.
45UV5-1000 60 180 – 250 1″ NPT 200°F (93°C)- 40°F (-40°C) FM, UL CU-22
45UV5-1010 60 180-250 1″ BSP 200°F (93°C)- 40°F (-40°C) FM CU-22
45RM1-1001 50/60 450 – 1,000 1″  NPT 150°F (65°C)- 40°F (-40°C) FM CU-26
45RM2-1000 50/60 700-2,500 1″  NPT 150°F (65°C)- 40°F (-40°C) FM CU-26
45RM4-1000 24VDC 700 – 2,500 1″  NPT 150°F (65°C)- 40°F (-40°C) FM CU-31
45FS1-1000 24VDC 700 – 2,500 1″  NPT 150°F (65°C)- 4°F (-20°C) FM CU-32
45FS1-1001 24VDC 700 – 2,500 1″  BSP 150°F (65°C)-4°F (-20°C) FM CU-32
45UVFS1-1000 24VDC 290-390 1″  NPT 131°F (55°C)- 4°F (-20°C) FM CU-32
45UVFS1-1001 24VDC 290-390 1″  BSP 131°F (55°C) FM CU-32

 

 

FIREYE 25SU3-2000 Accessories

 

Part Number Description
25SU3-2000 Rack mount flame amplifier
Mounting Racks
60-2471-1 Half mounting rack. Includes one (1) 60-2478 connector.
60-2471-3 Full mounting rack. Includes one (1) 60-2478 connector.
60-2530-1 Surface mount rack. Refer to Bulletin CU-44.
60-2530-2 Surface mount rack with clear hinged cover. Refer to Bulletin CU-44.
Mounting Adaptors
192SU3-2120 Adaptor (120 VAC) to retrofit 25SU3-2000 to 60-1706 or 60-1499 wiring rack.
192SU3-2220 Adaptor (220 VAC) to retrofit 25SU3-2000 to 60-1706 or 60-1499 wiring rack.
Filler Plates
60-2490-2 Front filler plate for mounting racks. Approx .4″ (2 HP)
60-2490-4 Front filler plate for mounting racks. Approx .8″ (4 HP)
60-2490-6 Front filler plate for mounting racks. Approx 1.2″ (6 HP)
60-2490-8 Front filler plate for mounting racks. Approx 1.6″ (8 HP)
60-2490-10 Front filler plate for mounting racks. Approx 2.0″ (10 HP)
Power Supplies
60-2470-1 Power supply. 110 VAC Input/24 VDC, 2.5 Amps Output for 25SU3-2000 amplifiers and low voltage scanners. Includes 60-2482 connector.
60-2470-2 Power supply. 220-240 VAC Input/24 VDC, 2.5 Amps Output for 25SU3-2000 amplifiers and low voltage scanners. Includes 60-2482 connector.
19UVPS-2120 Power supply. 110 VAC Input for up to six (6) line voltage scanners only.
19UVPS-2220 Power supply. 220 VAC Input for up to six (6) line voltage scanners only.
19MPS-2000 Multi-purpose power supply for two (2) 25SU3-2000 amplifiers and up to four (4) low
Connectors
60-2478 Screw terminal straight style (12 AWG) connector for 25SU3-2000 amplifier and 19UVPS power
60-2480 Screw terminal Y style (12 AWG) connector for 25SU3-2000 amplifier and 19UVPS power supply.
60-2481a Screw terminal connector (12 AWG) for 60-2470 and 19MPS-2000 power supplies.
60-2482 Spade terminal connector for 60-2470 and 19MPS-2000 power supplies.
Replacement Fuses
23-93 Replacement power fuse for 25SU3-2000 (3.0 Amp. fast-acting type).
23-182 Replacement fuse for RF1 flame relay contacts for 25SU3-2000 (1.5 Amp. fast-acting type).

Get A Quote