TCI Supply is a master distributor of the FIREYE 25SU3-2000 and has been working with Fireye Flame Safety devices for over 30 years. We provide the best prices, delivery, and customer service in the game. Whether you have an obsolete part, a large quantity, or a rebuild / repair, make us your first supply stop. We will not be beat on the full Fireye line, including burner boiler controls, flame scanners (UV & IR), programmers, amplifiers, and more.
Request a Quote now or call us at 1-800-755-2883 for expert assistance.
FIREYE 25SU3-2000 Overview
The 25SU3-2000 is a Flame Safeguard Amplifier used to detect the presence or absence of a flame in a single or multi-burner environment. The 25SU3-2000 also maximizes burner discrimination with its ability to accurately differentiate the pulse rates produced by the scanners. The 25SU3-2000 has the capacity to receive pulse inputs from two flame scanners, “A” and “B,” either separately or in combination. In addition, the 25SU3-2000 has two logic programs available, called “Scanner Option 1” and “Scanner Option 2.” Within these two scanner options, the user may select different operating parameters, and select the scanner or scanners that will provide the pulse input for that option. Switching between “Scanner Option 1” and “Scanner Option 2” is accomplished by an external dry contact input to the amplifier. The dynamic range for the 25SU3-2000 amplifier is 1900 pulses per second, which is consistent with the output range provided by Fireye scanners. The pulse rate output of each scanner can be checked by the user, thus facilitating the
maintenance of each scanner. The design platform of the 25SU3-2000 is based on the global 19 inch format with the unit operating on either 24 VAC or 24 VDC. Fireye offers a full rack (60-2471-3), half-rack (60-2471-1) or surface mount rack (60-2530), and filler plates for mounting the 25SU3-2000 amplifiers, as well as several different power supplies for various scanner/amplifier combinations. See Ordering Information. The 25SU3-2000 amplifier provides remote communications capability to a PLC using either Allen-Bradley DF1 or MODBUS communication protocol. Consult factory for details.
FIREYE 25SU3-2000 Features
• Keypad Entry system
• Password protection to avoid unauthorized alteration of the user-set (programmed) parameters.
• Eight character alpha-numeric display.
• Front panel LED Status Indicator.
• Adjustable Independent Flame Relay Pull-In and Drop-Out Thresholds.
• Adjustable Flame Failure Response Time (FFRT) (1 to 6 secs.).
• Adjustable Independent Flame Relay Delay On Time (0 to 10 secs.).
• Capable of analyzing signals from two scanners.
• One Form C SPDT Marginal Alarm relay.
• One fused DPDT Form C Flame relay.
• One 4 – 20mA analog output (used to measure flame signal—scalable).
• Remote communications capability to a PLC. Consult factory for details.
FIREYE 25SU3-2000 Compatible Flame Scanners
FREQ. | WAVE- | MOUNT | AMBIENT | SAFETY | ||
Hz | LENGTH | THREADS | TEMP. MAX., | APPROVALS | BULLETIN | |
(nanometers) | MIN. | |||||
TYPE/MODEL | When TUV Agency approval is required, select one of the following: | |||||
45UV5-1101 | 50 | 180 – 250 | 1″ BSP | 200°F (93°C) – 40°F (-40°C) | APAVE, FM | CU-22 |
45RM1-1003 | 50/60 | 450 – 1,000 | 1″ BSP | 150°F (65°C)- 40°F (-40°C) | FM, APAVE | CU-26 |
45RM2-1001 | 50/60 | 700 – 2,500 | 1″ BSP | 150°F (65°C)- 40°F (-40°C) | FM, APAVE | CU-26 |
45RM4-1001 | 24VDC | 700-2,500 | 1″ BSP | 150°F (65°C)- 40°F (-40°C) | FM, APAVE | CU-31 |
When TUV Agency approval is NOT required, select any scanner from either above or below. | ||||||
45UV5-1000 | 60 | 180 – 250 | 1″ NPT | 200°F (93°C)- 40°F (-40°C) | FM, UL | CU-22 |
45UV5-1010 | 60 | 180-250 | 1″ BSP | 200°F (93°C)- 40°F (-40°C) | FM | CU-22 |
45RM1-1001 | 50/60 | 450 – 1,000 | 1″ NPT | 150°F (65°C)- 40°F (-40°C) | FM | CU-26 |
45RM2-1000 | 50/60 | 700-2,500 | 1″ NPT | 150°F (65°C)- 40°F (-40°C) | FM | CU-26 |
45RM4-1000 | 24VDC | 700 – 2,500 | 1″ NPT | 150°F (65°C)- 40°F (-40°C) | FM | CU-31 |
45FS1-1000 | 24VDC | 700 – 2,500 | 1″ NPT | 150°F (65°C)- 4°F (-20°C) | FM | CU-32 |
45FS1-1001 | 24VDC | 700 – 2,500 | 1″ BSP | 150°F (65°C)-4°F (-20°C) | FM | CU-32 |
45UVFS1-1000 | 24VDC | 290-390 | 1″ NPT | 131°F (55°C)- 4°F (-20°C) | FM | CU-32 |
45UVFS1-1001 | 24VDC | 290-390 | 1″ BSP | 131°F (55°C) | FM | CU-32 |
FIREYE 25SU3-2000 Accessories
Part Number | Description |
25SU3-2000 | Rack mount flame amplifier |
Mounting Racks | |
60-2471-1 | Half mounting rack. Includes one (1) 60-2478 connector. |
60-2471-3 | Full mounting rack. Includes one (1) 60-2478 connector. |
60-2530-1 | Surface mount rack. Refer to Bulletin CU-44. |
60-2530-2 | Surface mount rack with clear hinged cover. Refer to Bulletin CU-44. |
Mounting Adaptors | |
192SU3-2120 | Adaptor (120 VAC) to retrofit 25SU3-2000 to 60-1706 or 60-1499 wiring rack. |
192SU3-2220 | Adaptor (220 VAC) to retrofit 25SU3-2000 to 60-1706 or 60-1499 wiring rack. |
Filler Plates | |
60-2490-2 | Front filler plate for mounting racks. Approx .4″ (2 HP) |
60-2490-4 | Front filler plate for mounting racks. Approx .8″ (4 HP) |
60-2490-6 | Front filler plate for mounting racks. Approx 1.2″ (6 HP) |
60-2490-8 | Front filler plate for mounting racks. Approx 1.6″ (8 HP) |
60-2490-10 | Front filler plate for mounting racks. Approx 2.0″ (10 HP) |
Power Supplies | |
60-2470-1 | Power supply. 110 VAC Input/24 VDC, 2.5 Amps Output for 25SU3-2000 amplifiers and low voltage scanners. Includes 60-2482 connector. |
60-2470-2 | Power supply. 220-240 VAC Input/24 VDC, 2.5 Amps Output for 25SU3-2000 amplifiers and low voltage scanners. Includes 60-2482 connector. |
19UVPS-2120 | Power supply. 110 VAC Input for up to six (6) line voltage scanners only. |
19UVPS-2220 | Power supply. 220 VAC Input for up to six (6) line voltage scanners only. |
19MPS-2000 | Multi-purpose power supply for two (2) 25SU3-2000 amplifiers and up to four (4) low |
Connectors | |
60-2478 | Screw terminal straight style (12 AWG) connector for 25SU3-2000 amplifier and 19UVPS power |
60-2480 | Screw terminal Y style (12 AWG) connector for 25SU3-2000 amplifier and 19UVPS power supply. |
60-2481a | Screw terminal connector (12 AWG) for 60-2470 and 19MPS-2000 power supplies. |
60-2482 | Spade terminal connector for 60-2470 and 19MPS-2000 power supplies. |
Replacement Fuses | |
23-93 | Replacement power fuse for 25SU3-2000 (3.0 Amp. fast-acting type). |
23-182 | Replacement fuse for RF1 flame relay contacts for 25SU3-2000 (1.5 Amp. fast-acting type). |