Asco 8263 Hot Water / Steam Solenoid Valve
Asco 8263 Hot Water / Steam Solenoid Valve

The Asco 8263G058 Solenoid Valve (8263G58) is a direct-acting, normally closed valve engineered for high-temperature steam applications. Its compact construction and pressure-independent actuation make it ideal for critical point-of-use service in thermal systems. It is optimized for autoclaves, commercial laundry, and process steam delivery.

Technical Specifications

  • Valve Type: Direct Acting, Normally Closed, 2-Way
  • Pipe Size: 1/8″ NPT
  • Flow Factor (Cv): 0.34
  • Operating Pressure Differential:
    • Steam: 0 to 90 psi (AC)
  • Maximum Fluid Temperature:
    • Steam (AC): 331°F (166°C)
  • Body Material: Brass
  • Seal Material: EPDM or PTFE
  • Voltage Options:
    • AC: 24, 120, 240, 480 V (60 Hz); 110, 220 V (50 Hz)
  • Watt Rating:
    • AC: 6.1/F
  • Solenoid Enclosure:
    • Standard: NEMA 4X, IP65 (Watertight, Corrosion-Resistant)
    • Optional: Explosionproof & Watertight (Types 3-9), Raintight (Types 3, 7, 9)

Key Features and Functionality

  • Steam-Resistant Build: Handles continuous steam up to 331°F.
  • Direct Acting Operation: Activates with zero pressure differential.
  • Small Form Factor: Compact design fits tight installations.
  • Thermal System Ready: Supports high-temp cleaning applications.
  • Universal Mounting Flexibility: Can be installed in any position.

Compatible Components and Related Parts

  • ASCO RedHat II Coil Series
  • ASCO Mounting Brackets
  • ASCO Seal Kit for 8263 Series
  • ASCO Explosionproof Solenoid Enclosure

Industry Applications

  • Laundry Equipment: Releases steam into heat cycle piping.
  • Autoclaves and Sterilizers: Controls internal steam pressure release.
  • Food Service Equipment: Supports sanitizing and steam spray control.
  • Steam Atomization Systems: Directs pressurized steam bursts.
  • Molding Equipment: Regulates the heating phase during molding.

Compliance and Approvals

  • CSA Certified
  • CE Compliant

Installation and Operational Notes

  • Verify solenoid voltage matches supply before energizing.
  • Keep valve internals clean to prevent malfunction.
  • Depressurize the system thoroughly before performing maintenance.
  • Mount the valve upright unless otherwise specifically approved.
  • Install an upstream strainer to block particulate contamination.

Series Catalog

Asco Hot Water and Steam Valves Two-Way

 

We ship these products worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!