The Asco 8262G263 Solenoid Valve (8262G263) is a direct-acting, normally open 2-way valve designed for low-to-moderate pressure fluid control where uninterrupted flow is required during power-off conditions. With a 0.49 Cv rating and brass body construction, this valve provides higher flow capacity in compact assemblies handling air, water, and light oil.
Technical Specifications
- Valve Type: Direct Acting, Normally Open, 2-Way
- Pipe Size: 1/4″ NPT
- Flow Factor (Cv): 0.49
- Operating Pressure Differential:
- Max Air/Inert Gas: 85 psi (AC), 45 psi (DC)
- Max Water: 75 psi (AC), 30 psi (DC)
- Max Light Oil: 60 psi (AC), 30 psi (DC)
- Maximum Fluid Temperature:
- AC: 180°F (82°C)
- DC: 150°F (66°C)
- Body Material: Brass
- Seal Material: NBR
- Voltage Options:
- AC: 24, 120, 240, 480 V (60 Hz); 110, 220 V (50 Hz)
- DC: 6, 12, 24, 120, 240 V
- Watt Rating:
- AC: 10.1/F
- DC: 11.6/F
- Solenoid Enclosure:
- Standard: Watertight, Types 1, 2, 3, 3S, 4, and 4X
- Optional: Explosionproof and Watertight (Types 3, 3S, 4, 4X, 6, 6P, 7, and 9)
Key Features and Functionality
- Normally Open Design: Provides an open flow path when the solenoid is de-energized.
- 0.49 Cv Flow Capacity: Supports moderate flow rates in compact piping systems.
- Direct-Acting Poppet Valve: Enables reliable shutoff without pressure differential.
- Low Voltage Control: Compatible with both AC and DC power systems.
- Compact 1/4″ NPT Construction: Ideal for tight installations in utility panels or OEM equipment.
Compatible Components and Related Parts
- ASCO RedHat II Coil Series
- ASCO Mounting Brackets
- ASCO Seal Kit for 8262 Series
- ASCO Explosionproof Solenoid Enclosure
Industry Applications
- Car Wash Systems: Opens rinse or air circuits during the rest state.
- Laundry Equipment: Controls chemical or water flow in unpowered cycles.
- Compressors and Pumps: Acts as a vent or bypass control.
- Boilers and Burners: Maintains purge air or start-up fuel line access.
- Food Processing Equipment: Allows fluid drainage or CIP flushing.
Compliance and Approvals
- UL Listed for General Purpose Valve
- CSA Certified
- Meets Applicable CE Directives
Installation and Operational Notes
- Ensure seal material matches media and temperature requirements.
- Mount the solenoid upright when possible to avoid debris accumulation.
- Install an inlet strainer for internal protection.
- Apply thread compound to male threads only.
- Always shut off power and pressure before servicing.