The Asco 8262G086 Solenoid Valve (8262G86) is a compact, direct-acting valve designed for high-pressure shutoff in systems handling compressed air, fuel gas, or corrosive fluids. Its stainless steel construction provides corrosion resistance in harsh environments, while its fast-acting, zero-pressure design makes it ideal for critical control where rapid response and safety are essential.
Technical Specifications
- Valve Type: Direct Acting, Normally Closed, 2-Way
- Pipe Size: 1/4″ NPT
- Flow Factor (Cv): 0.17
- Operating Pressure Differential:
- Max Air/Inert Gas: 360 psi (AC), 150 psi (DC)
- Max Water: 340 psi (AC), 125 psi (DC)
- Max Light Oil: 160 psi (AC), 125 psi (DC)
- Maximum Fluid Temperature:
- AC: 180°F (82°C)
- DC: 120°F (49°C)
- Body Material: Stainless Steel
- Seal Material: NBR
- Voltage Options:
- AC: 24, 120, 240, 480 V (60 Hz); 110, 220 V (50 Hz)
- DC: 6, 12, 24, 120, 240 V
- Watt Rating:
- AC: 6.1/F
- DC: 10.6/F
- Solenoid Enclosure:
- Standard: Watertight, Types 1, 2, 3, 3S, 4, and 4X
- Optional: Explosionproof and Watertight, Types 3, 3S, 4, 4X, 6, 6P, 7, and 9
Key Features and Functionality
- Stainless Steel Body: Corrosion-resistant for process and outdoor use.
- Metered Flow Design: Low Cv for dosing and pilot service.
- Direct-Acting Operation: No line pressure required to actuate.
- Multi-Media Compatibility: Air, water, and light oil capable.
- Installable in Any Position: No orientation restrictions during mounting.
Compatible Components and Related Parts
- ASCO RedHat II Coil Series
- ASCO Mounting Brackets
- ASCO Seal Kit for 8262 Series
- ASCO Explosionproof Solenoid Enclosure
Industry Applications
- Oil and Gas: Used in burner isolation and valve actuation panels.
- Chemical Processing: Handles solvent or ammonia dosing duties.
- Water and Wastewater: Controls small flows in chlorination skids.
- Food and Beverage: Fits CIP systems with compact shutoff.
- General Industrial and OEM: Used in automated fluid modules and test stands.
Compliance and Approvals
- CSA Certified
- Meets Applicable CE Directives
- FM Approved
- UL Listed: Safety Shutoff Valve
Installation and Operational Notes
- Verify the catalog number, voltage, pressure, and media before installation.
- Pipe to correct ports; use compound on male threads only.
- Mount in any position; an upright solenoid is preferred.
- Install a filter or strainer close to the valve inlet.
- Depressurize and disconnect power before cleaning or maintenance.
Series Catalog
Asco 8262 & 8263 General Service Solenoid Valves
We ship these products worldwide! Delivery is normally stock.