The Asco 8220G025 Solenoid Valve (8220G25) is a pilot-operated, normally closed valve engineered for reliable high-temperature control in steam and hot water systems. With a high flow Coefficient of 13.5 and a Class H coil, it’s ideal for demanding applications. Once opened at higher pressure, the valve will remain open to 3 psi at the inlet.
Technical Specifications
- Valve Type: Pilot Operated, Normally Closed, 2-Way
- Pipe Size: 1″ NPT
- Flow Factor (Cv): 13.5
- Operating Pressure Differential:
- Steam: 5 to 125 psi
- Hot Water: 5 to 150 psi
- Maximum Fluid Temperature:
- Steam: 353°F (178°C)
- Hot Water: 210°F (99°C)
- Body Material: Brass
- Seal Material: EPDM or PTFE
- Voltage Options:
- AC: 24, 120, 240, 480 V
- DC: 6, 12, 24, 120, 240 V
- Watt Rating:
- AC: 10.1 watts
- Coil Insulation Class: H
- Solenoid Enclosure:
- Standard: RedHat II – Watertight, Types 1, 2, 3, 3S, 4, and 4X
- Optional: Explosionproof & Watertight, Types 3, 3S, 4, 4X, 6, 6P, 7, and 9
Key Features and Functionality
- Handles Extreme Temperatures: Capable of operating at steam temperatures up to 353°F.
- High Flow Capacity: Features a flow coefficient of 13.5 Cv, suitable for large system loads.
- EPDM/PTFE Sealing Disc: Ensures reliable performance even under thermal stress.
- Heavy-Duty Coil: Equipped with Class H insulation to resist heat buildup.
- Flexible Utility: Suitable for both hot water and steam applications.
Compatible Components and Related Parts
- ASCO RedHat II Coil Series
- ASCO Mounting Brackets
- ASCO Seal Kit for 8220 Series
- ASCO Explosionproof Solenoid Enclosure
Industry Applications
- Boiler Systems: Controls return or output pressure.
- Autoclaves: Manages high-temperature, pressurized flow.
- Food Processing Lines: Delivers consistent thermal control.
- Steam Heating Units: Regulates thermal output for load-bearing applications.
- Commercial Dishwashers: Ensures high-temperature rinse cycles.
Compliance and Approvals
- UL Listed
- CSA Certified
- Meets Applicable CE Directives
Installation and Operational Notes
- Confirm the coil voltage matches your power source.
- Depressurize the system before installing or servicing the valve.
- Use a fine strainer upstream to block debris and contaminants.
- Align pipes carefully to avoid straining the valve body.
- Apply power and listen for a click to confirm solenoid actuation.