Asco 8220G019 Solenoid Valve 8220G19
Asco 8220G019 Solenoid Valve 8220G19

The Asco 8220G019 Solenoid Valve (8220G19) is a pilot-operated, normally closed valve built for high-efficiency control of steam and hot water in demanding systems. With a rugged brass body and Class H coil, it delivers long-lasting operation in high-temperature environments, such as autoclaves, food equipment, and dishwashing machines.

Technical Specifications

  • Valve Type: Pilot Operated, Normally Closed, 2-Way
  • Pipe Size: 3/8″ NPT
  • Flow Factor (Cv): 3.0
  • Operating Pressure Differential:
    • Steam: 5 to 125 psi
    • Hot Water: 5 to 150 psi
  • Maximum Fluid Temperature:
    • Steam: 353°F (178°C)
    • Hot Water: 210°F (99°C)
  • Body Material: Brass
  • Seal Material: EPDM or PTFE
  • Voltage Options:
    • AC: 24, 120, 240, 480 V
    • DC: 6, 12, 24, 120, 240 V
  • Watt Rating:
    • AC: 10.1 watts
  • Coil Insulation Class: H
  • Solenoid Enclosure:
    • Standard: RedHat II – Watertight, Types 1, 2, 3, 3S, 4, and 4X
    • Optional: Explosionproof & Watertight, Types 3, 3S, 4, 4X, 6, 6P, 7, and 9

Key Features and Functionality

  • Steam and Water Ready: Works with both media types.
  • Class H Coil Rating: Handles higher temperature environments.
  • EPDM/PTFE Sealing Disc: Long-lasting shutoff in thermal systems.
  • Threaded Bonnet Access: Enables fast and easy servicing.
  • Flexible Install Positioning: Can mount in any orientation.

Compatible Components and Related Parts

  • ASCO RedHat II Coil Series
  • ASCO Mounting Brackets
  • ASCO Seal Kit for 8220 Series
  • ASCO Explosionproof Solenoid Enclosure

Industry Applications

  • Autoclaves and Sterilizers: Controls heat and pressure discharge.
  • Commercial Laundry Equipment: Directs high-temp water flow.
  • Dishwashing Systems: Regulates rinse cycles under pressure.
  • Food Service Boilers: Delivers heated fluids to equipment.
  • Sanitation Equipment: Supports high-temp cleaning operations.

Compliance and Approvals

  • UL Listed
  • CSA Certified
  • Meets Applicable CE Directives

Installation and Operational Notes

  • Make sure the voltage matches before turning on the power.
  • Depressurize all lines before starting any work.
  • Put a fine strainer right before the valve.
  • Don’t let the pipes push or twist the valve.
  • Turn the power on and listen for a click from the solenoid.

Series Catalog

Asco Hot Water and Steam Valves Two Way

 

We ship these products worldwide! Delivery is normally stock.

Request a Quote now or call us at 1-800-755-2883 for expert assistance.

Get A Quote

Fill in the form below, or call us now at 1-800-755-2883

"*" indicates required fields

This field is for validation purposes and should be left unchanged.

Full Product Catalog

See our comprehensive product catalog!