The Asco 8215C063 Solenoid Valve (8215C63) is a direct-acting, normally open, 2-way valve optimized for high-capacity air-fuel gas flow in low-pressure systems. With its large Cv rating and ability to open with zero pressure differential, it excels in combustion safety loops, purge lines, and systems requiring uninterrupted flow until energized shutoff.
Technical Specifications
- Valve Type: Direct Acting, Normally Open, 2-Way
- Pipe Size: 1 1/4″
- Flow Factor (Cv): 33
- Gas Capacity: 1,793,250 Btu/hr
- Operating Pressure Differential:
- Air-Fuel Gas: 0 psi to 25 psi (AC); 0 psi to 15 psi (DC)
- Maximum Fluid Temperature:
- AC: 125°F (52°C)
- DC: 104°F (40°C)
- Body Material: Aluminum
- Seal Material: NBR
- Voltage Options:
- AC (60 Hz): 24V, 120V, 240V, 480V
- AC (50 Hz): 110V, 220V
- DC: 6V, 12V, 24V, 120V, 240V
- Watt Rating:
- AC: 15.4 watts
- Coil Insulation Class: F
- Solenoid Enclosure:
- Standard: Type I (General Purpose)
- Optional: Explosionproof and Watertight, Types 3, 3S, 4, 4X, 6, 6P, 7, 9
Key Features and Functionality
- Zero Pressure Operation: Opens without line pressure to start flow.
- High Flow Design: 33 Cv enables rapid purge and ventilation.
- Normally Open Design: Remains open unless energized to close.
- Wide Voltage Range: AC and DC compatibility for diverse installations.
- Corrosion-Resistant Housing: Aluminum body suited for harsh conditions.
Compatible Components and Related Parts
- ASCO RedHat II Coil Series
- ASCO Mounting Brackets
- ASCO Seal Kit for 8215 Series
- ASCO Explosionproof Solenoid Enclosure
Industry Applications
- Vent and Purge Lines: Maintains default open state for air-fuel gas.
- Combustion Airflow Management: Regulates open flow until ignition.
- Burner Bypass Circuits: Delivers gas in idle or safe states.
- Exhaust Stack Systems: Ensures flow continuity in open-loop designs.
- Air-Gas Mix Control: Supports continuous delivery during system standby.
Compliance and Approvals
- UL Listed General Purpose Valve
- CSA Certified to C22.2 No. 139
- Meets Z21.21 for Automatic Gas Valves
Installation and Operational Notes
- Mount the solenoid vertically and upright for optimal life.
- DC valves must always be installed upright.
- Do not overtighten pipe connections during installation.
- Apply pipe compound to male threads only.
- Check the nameplate for correct pressure, voltage, and service.